Laserfiche WebLink
6 of 234 <br />Thornton Tomasetti <br />PROJECT 888 N Main St Santa Ana <br />SUBJECT ASCE41-13 Alternative Methods Summar, <br />PROJECT NO S18003.00 <br />REVIEWER LJ/CS/JP <br />DATE 8/13/2018 <br />CODE REFERENCE TOPIC RESPONSE <br />2.2 <br />2.2.3 <br />From Table C2-2, Target Building Perofrmance Levels 'c' and 'd' apply to the tower concrete <br />Performance Objective frame building structure. These levels correspond to Limited Objectives of Life Safety and <br />Collapse Prevention at the 50%/50 year Seismic Hazard Level. <br />The code lists four stipulations when achieving the Limited Performance Objective. The first thref <br />Limited Performance Objectives of which are satisfied and the final will be confirmed during the on-going connection design. <br />Target Building Performance At the 50%/50year mean recurrence interval (MRI) event, the Collapse Prevention (S-5) and Life <br />2.3 <br />Levels Safety (S-3) Levels will be achieved. See Table C2-4 for Concrete frames. <br />2.42.2 <br />3.2.1 <br />3.2.2 <br />Ground Motion Acceleration <br />Histories <br />Building Type <br />Building Configuration <br />Evaluation of the existing structure is being conducted with four separate acceleration histones <br />(each with two horizontal components). spectrally matched to a site-specific 72yr (50%/50yr) MR <br />Response Spectrum. See Wood PLC geotechnical report 225yr MRI acceleration histories are <br />used only to confirm dampers and their connections can sustain greater-than-72yr event <br />demands. <br />Cl Classification - Concrete Moment Frames <br />The tower floor geometry is regular at all levels. Continuous concrete diaphragms are integrated <br />with penmeter moment frames with few obstructions or irregularities <br />4.4 Tier 1 Checklist <br />Referencing the checklist for Cl Concrete Moment frames in 16.9LS in high seismicity, certain <br />applicable items are addressed below: <br />Redundancy: entire perimeter moment frame system contributes to lateral resistance. <br />Column Axial Stress Check Under the Tier 3 Nonlinear Time History Analysis, moment frame <br />columns will be assessed under axial and fiexural combined stresses to determine adequacy. <br />Likwise, column shear stress will be evaluated. <br />Captive Columns. Because all perimeter columns are captured to an extent by a penmeter <br />concrete infill panel, no irregularly captured columns are present. The effect of capture is renecte <br />in beam modeling and use of 50% rigid offsets. <br />Column/Beam Bar Splices: From field testing at Level 1, column splice extents appear to follow <br />column compression splice practice of the 1960s. Flexural demands are well below yield so this <br />is not a concern. <br />Column Tie Spacing Field testing of multiple columns at multiple floors shows ties typically at 18 <br />or doser. Shear capacity is checked using the ASCE 41-13 formula. At those columns receiving <br />damper connections, Fiber-Reinforced Polymer (FRP) wrap will provide additional column <br />confinement and shear capacity from ground floor to underside of L3 spandrel beams to address <br />possible increased column stiffness from the connections <br />Diaphragm Continuity: Visibly satisfied as mentioned above. <br />Wing Buildings: GPR scanning detected vertical and horizontal reinforcement in the wing end <br />walls. Tapered wing girder ends have bolted connections to the wing end walls and tower <br />columns. <br />The Tier 1 checklist is used to help Identify structural deficiencies in existing buildings <br />Considering this structure's limited performance objective, the pnmary components of interest art <br />the tower moment frame columns; MF beams will be checked to not control due to much greater <br />effective depth. Therefore this building performance will be evaluated at a Tier 3 level for <br />adequacy of penmeter moment frame columns <br />54 <br />54.22 <br />5.52.1 <br />Once deficiencies are identified in a Tier 1 screening, they are specifically addressed in Tier 2. In <br />the case of this project, the design team recognizes that the following potential deficiencies are k <br />Tier 2 Deficiency-Based Evaluation be evaluated within the eventual Tier 3 analysis: tower perimeter Ll -L3 column moment and <br />shear capacity, tower perimeter L3 through roof column moment and shear capacity <br />Soft Story Irregulanty <br />The nearly-double height moment frame columns extending from the ground floor the Level 3 <br />introduce a stiffness discontinuity which tends to form a soft story The pnmary retrofit measure c <br />introducing strategically-positioned viscous diagonal dampers aims to mitigate this primary <br />deficiency. As mentioned above, no significant irregulanties are present in this predominantly <br />symmetric, continuous structure. <br />General checks to be carried out for moment frames indude drifts and axial stress (in conjundior <br />with flexural). Deep perimeter moment frame beams combined with a thinner concrete infill panel <br />General Moment Frame Checks preclude this system from obeying the traditional strong column-weak beam framing proportions. <br />Thus, as noted in C5.5.2.1.5, additional column shear capadty studies will be performed via the <br />Tier 3 Nonlinear time history analyses.