PROJECT SITE
<br />OWNER:CHAD BARKER
<br />ADDRESS:2014 NORTH FLOWER ST
<br />SANTA ANA, CA 92706
<br />APN:39905105
<br />UTILITY:SCE
<br />AHJ:ORANGE COUNTY
<br />CONSTRUCTION TYPE: VB
<br />OCCUPANCY TYPE: R3
<br />ELEVATION: 138 FT ABOVE SEA LEVEL
<br />PROJECT INFO
<br />VICINITY MAP
<br />A0
<br />SOLAR PHOTOVOLTAIC SYSTEM NOTES
<br />1. ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED TESTING LABORATORY AND INSTALLED PER THE LISTING
<br /> REQUIREMENTS AND THE MANUFACTURER'S INSTRUCTIONS, CEC 110.2, 110.3, 690.4(B) AND 690.12(D).
<br />2. ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND SWITCHES.
<br />3. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH CEC ARTICLE 250.
<br />4. ALL PV CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL HAVE PROTECTION AGAINST OVERCURRENT PER CEC 690.9.
<br />5. DISCONNECTING MEANS OF THE PV SYSTEM (INCLUDING RAPID SHUTDOWN INITIATION) SHALL BE LOCATED IN READILY
<br /> ACCESSIBLE LOCATION NEAR THE EQUIPMENT, CEC 690.13, 690.15.
<br />6. ENERGY STORAGE SYSTEMS TERMINALS LOCATED MORE THAN 5 FEET AWAY OR ON OPPOSITE SIDE OF WALL FROM CONNECTED
<br /> EQUIPMENT MUST HAVE DISCONNECTING MEANS IN ACCORDANCE WITH CEC 706.7(E) AND LABELED PER 706.7(D). A SECOND
<br /> DISCONNECTING MEANS LOCATED AT THE CONNECTED EQUIPMENT SHALL BE INSTALLED WHERE THE DISCONNECTING MEANS AT
<br /> THE ESS END OF THE CIRCUIT IS NOT WITHIN SIGHT.
<br />7. RAPID SHUTDOWN EQUIPMENT TO COMPLY WITH CEC 690.12.
<br />8. THE UTILITY-INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED ELECTRICAL
<br /> PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND SHALL REMAIN IN THAT STATE UNTIL THE
<br /> ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED, CEC 705.40.
<br />9. ALL CONDUCTORS IN EXPOSED OUTDOOR LOCATIONS SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT AND FOR
<br /> THE APPLICATION. CEC310.10(D) AND 690.31(C) THROUGH (F).
<br />10. INSULATION OF EXPOSED CONDUCTORS UNDER THE MODULES SHALL BE USE-2 OR PV-WIRE TYPE FOR PV SYSTEMS, CEC 690.31(C).
<br />11. FINE-STRANDED CABLE CONNECTIONS MUST BE MADE IN LUGS AND TERMINALS LISTED AND MARKED FOR THE USE, CEC 110.14.
<br />12. ALL PV CIRCUIT CONDUCTORS SHALL BE MARKED ON EACH END AND GROUPED FOR UNIQUE IDENTIFICATION, CEC 690.31(B).
<br />13. ALL GROUNDED, (NEUTRAL), CONDUCTORS' INSULATION SHALL BE SOLID WHITE, GRAY, OR WITH 3-WHITE STRIPES, CEC 200.6,
<br /> 200.7, & 400.22; AND ALL GROUNDING CONDUCTORS SHALL BE OF BARE WIRE WITHOUT COVERING, OR WITH INSULATION OF
<br /> GREEN OR GREEN WITH YELLOW STRIPES, CEC 250.119 & 400.23. THE COLOR OF UNGROUNDED CONDUCTORS SHALL BE OTHER
<br /> THAN FOR GROUNDED, (NEUTRAL), AND GROUNDING CONDUCTORS, CEC 310.110(C).
<br />14. MAXIMUM CONDUCTOR LENGTH BETWEEN SUPPLY SIDE CONNECTION AND OVERCURRENT PROTECTION IS 10 FEET, CEC 705.31.
<br />15. CONNECTIONS ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER SOURCE(S) AT ANY DISTRIBUTION
<br /> EQUIPMENT ON THE PREMISES SHALL MEET THE FOLLOWING, CEC 705.12(B).
<br />16. DC WIRING INSIDE A BUILDING MUST BE IN METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, OR CABLE SHEATHINGS, CEC
<br /> 690.31(G).
<br />17. METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, AND CABLE SHEATHS CONTAINING CIRCUITS OVER 250-VOLTS TO GROUND
<br /> MUST BE BONDED IN ACCORDANCE WITH CEC 250.97.
<br />18. ALL EXTERIOR CONDUIT, FITTINGS AND BOXES SHALL BE RAIN TIGHT AND APPROVED FOR USE IN WET LOCATIONS, CEC 314.15
<br />19. FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES OR CONNECTOR THAT ARE
<br /> IDENTIFIED AND LISTED FOR SUCH USE, CEC 690.31(H) & 110.14.
<br />20. CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND OPERATING AT
<br /> OVER 30 VOLTS SHALL REQUIRE TOOL TO OPEN AND MARKED “DO NOT DISCONNECT UNDER LOAD” OR “NOT FOR CURRENT
<br /> INTERRUPTING”, CEC 690.33(C) & (E)(2).
<br />21. EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES SMALLER THAN 6 AWG SHALL BE PROTECTED FROM PHYSICAL DAMAGE
<br /> BY A RACEWAY OR CABLE ARMOR, CEC 690.46 & 250.120(C).
<br />22. THE INTERCONNECTION POINT SHALL BE ON THE SUPPLY SIDE OF ALL GROUND-FAULT PROTECTION EQUIPMENT, CEC 705.32.
<br />23. CABLES/WIRES THAT ARE SUBJECT TO PHYSICAL DAMAGE, SUCH AS THOSE NOT LOCATED UNDER THE MODULES, MUST BE
<br /> PROTECTED, CEC 300.4.
<br />24. PROPOSED LOCATIONS OF ELECTRICAL SERVICE REPLACEMENTS MUST ALSO BE APPROVED BY THE ELECTRICAL UTILITY
<br /> COMPANY.
<br />25. FOR ELECTRICAL SERVICE REPLACEMENTS, BONDING TO THE METAL PIPES OF NATURAL GAS, HOT WATER, AND COLD WATER MUST
<br /> BE PROVIDE, CEC 250.104.
<br />26. GROUNDING ROD ELECTRODES SHALL BE MINIMUM 5/8’’ IN DIAMETER AND INSTALLED 8’ MINIMUM IN CONTACT WITH
<br /> SOIL, CEC 250.52(A)(5), 250.53(G).
<br />27. MINIMUM 7/8’’ CLEARANCE FROM ROOF TO BOTTOM OF CONDUIT OR USE A TEMPERATURE ADDER OF 33 DEGREES C.
<br /> CEC 310.15(B)(3)(C)
<br />28. EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, & VENTILATIONS INTAKE AIR OPENINGS SHALL NOT BE COVERED OR
<br /> BLOCKED BY THE SOLAR PHOTOVOLTAIC SYSTEM.
<br />29. EXISTING DWV PLUMBING VENT TERMINATIONS THAT ARE HORIZONTALLY LOCATED CLOSER THAN 12" FROM THE PROPOSED
<br /> MODULES, MUST BE REROUTED, OR MUST BE EXTENDED A MINIMUM OF 6" ABOVE THE SURFACE OF THE MODULES, CPC 906.1.
<br />30. EXISTING B-VENT TERMINATIONS, FOR FUEL BURNING APPLIANCES, WHERE ADJACENT TO THE PROPOSED MODULES, MUST BE
<br /> EXTENDED 12" ABOVE THE MODULES' TOP SURFACE, CMC 802.6.1(1) & CPC 509.6.1(1).
<br />31. THE MARKINGS, "WARNING: PHOTOVOLTAIC POWER SOURCE", FOR DC RACEWAYS AND CABLE ASSEMBLIES MUST BE AT 10' O.C.;
<br /> AND BENDS, ABOVE OR BELOW PENETRATIONS OF ROOFS, CEILINGS, WALLS, OR BARRIERS, CEC 690.31(G)(4).
<br />32. PV COMBINER PANELBOARDS MUST HAVE PERMANENT MARKINGS INDICATING THAT THEY ARE DEDICATED FOR PV CIRCUITS ONLY
<br /> NO LOADS ARE TO BE CONNECTED.
<br />33. WORKING CLEARANCES TO BE PROVIDED AT NEW AND EXISTING ELECTRICAL EQUIPMENT, CEC 110.26.
<br />34. A LADDER MUST BE PROVIDED FOR INSPECTIONS IN ACCORDANCE WITH CAL-OSHA REGULATIONS, SECURED AND EXTENDING 3'
<br /> ABOVE THE ROOF.
<br />35. ALL OF THE REQUIRED MARKINGS, SIGNS, AND LABELS MUST BE INSTALLED ON ALL EQUIPMENT PRIOR TO ANY INSPECTIONS.
<br />36. LABELS SHALL BE REFLECTIVE, AND ALL LETTERS SHALL BE CAPITALIZED AND SHALL BE A MINIMUM HEIGHT OF 3/8'' IN WHITE ON A
<br /> RED BACKGROUND. CEC 690.31(G)(4)
<br />37. IDENTIFICATION OF POWER SOURCE RAPID SHUTDOWN AND LABELING SHALL BE IN ACCORDANCE WITH CEC 690.56(C).
<br />38. WHEN THE MAIN CIRCUIT BREAKER IS DERATED, A PERMANENT MARKING MUST BE PROVIDED ON THE PANELBOARD TO INDICATE
<br /> THAT THE MAIN CIRCUIT BREAKER HAS BEEN DOWNSIZED TO _______ AMPS, DO NOT UPSIZE IT.
<br />39. PANELS AND MODULES NOT TO BE INSTALLED ON ROOF BELOW AN EMERGENCY ESCAPE AND RESCUE OPENING. CRC R324.6.2.2
<br />40. GROUND-MOUNTED PV SYSTEMS MUST HAVE A CLEAR, BRUSH-FREE AREA OF 10-FEET AND A FIRE SEPARATION DISTANCE OF 5-FEET
<br /> MINIMUM TO OTHER STRUCTURES AND PROPERTY LINES, CRC R324.7 & R302.1.
<br />41. PLAN CHECK AND PERMIT FOR PV SYSTEM AND ASSOCIATED EQUIPMENT ONLY.
<br />42. ALL PROJECTS SUBJECT TO FIELD VERIFICATION FOR CODE COMPLIANCE.
<br />43. APPROVED SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN THE DWELLING UNIT AND SHALL BE FIELD
<br /> VERIFIED EITHER THROUGH FINAL BUILDING INSPECTION. SMOKE ALARMS ARE REQUIRED TO BE INSTALLED IN ALL
<br /> BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. CARBON MONOXIDE ALARMS
<br /> ARE REQUIRED OUTSIDE EACH BEDROOM AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. R314.1, R315.1
<br />44. ROOF ACCESS POINTS. ROOF ACCESS POINTS SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF
<br /> GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT STRONG POINTS OF BUILDING
<br /> CONSTRUCTION IN LOCATIONS WHERE THE ACCESS DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS
<br /> TREE LIMBS, WIRES OR SIGNS (R331.4.1).LADDERS SHALL BE OSHA APPROVED AND SECURED TO THE STRUCTURE FOR
<br /> INSPECTION PURPOSES.CONTRACTORS ARE REQUIRED TO BE PRESENT FOR THE FIRST AND/OR FINAL INSPECTIONS.
<br />45. NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM.
<br />8.075 DC KW SOLAR PV AC MODULE SYSTEM- ROOF MOUNT
<br />BARKER RESIDENCE
<br />2014 NORTH FLOWER ST, SANTA ANA, CA 92706
<br />APPLICABLE CODES
<br />ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL
<br />COMPLY WITH THE FOLLOWING APPLICABLE CODES
<br />2019 CA BUILDING CODES (CBC)
<br />2019 CA RESIDENTIAL CODES (CRC)
<br />2019 CA MECHANICAL CODES (CMC)
<br />2019 CA PLUMBING CODES (CPC)
<br />2019 CA FIRE CODES (CFC)
<br />2019 CA ELECTRICAL CODES (CEC)
<br />2019 CA ENERGY CODES (CEnC)
<br />2019 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGreen)
<br />PROJECT SITE
<br />VICINITY MAP
<br />AERIAL VIEW
<br />OWNER
<br />PROJECT TITLE
<br />JOBSITE ADDRESS
<br />SHEET TITLE
<br />SHEET NUMBER
<br />CONTRACTOR
<br />15013 CALIFA STREET,
<br />VAN NUYS, CA 91411
<br />818-670-7769
<br />WWW.PLUGITINSOLAR.COM
<br />C-10 License # 986882
<br />CHAD
<br />BARKER
<br /> 8.075 DC kW
<br />AC MODULE
<br />SYSTEM
<br />7.296 kW CEC-AC RATING
<br />2014
<br />NORTH FLOWER ST
<br />SANTA ANA
<br />CA 92706
<br />DESIGN BY: NT
<br />NATALIA@PLUGITINSOLAR.COM
<br />DATE
<br />DRAWN
<br />DESIGN
<br />REVISION
<br />DATE DESCRIPTION
<br />REVISION
<br />SIGNATURE OF LICENSE HOLDER
<br />4-2-22
<br />PROJECT SCOPE
<br />INSTALLATION OF ROOF MOUNT SOLAR PV SYSTEM
<br />NEW
<br />EQUIPMENT:19 SPR-M425-H-AC
<br />SUNPOWER AC MODULES
<br />19 SPR-M425-H-AC (240V) [Sl1]
<br />SUNPOWER INVERTERS
<br />SYSTEM SIZE: 8.075 DC kW RATING
<br />7.296 CEC AC RATING
<br />SERVICE: EXISTING 200A MAIN SERVICE PANEL
<br />ARRAY AREA: 20.78 SQFT X 19 = 394.82 SQFT
<br />SHEET INDEX
<br />A0 PROJECT INFO, VICINITY MAP, NOTES
<br />A1 SITE PLAN
<br />A2 MOUNTING PLAN
<br />A3 MOUNTING DETAILS
<br />E1 SINGLE LINE DIAGRAM
<br />E2 ELECTRICAL CALCULATIONS
<br />E3 REQUIRED SIGNAGE
<br />E4 AC MODULE DATA SHEET
<br />S1 MOUNTING DATA SHEET
<br />S2 RACKING DATA SHEET
<br />S3 RACKING GROUNDING
<br />S4 RACKING CERTIFICATION
<br />www. Loyd W Martin .com
<br />Solar Structures Engineering
<br />#2022-3209 Structural Only August 09, 2022
<br />Exp. 3-31-19
<br />No. C58724
<br />NITRAMW.DYO
<br />REGISTEREDPROFESSIONALENGINEER
<br />C
<br />V
<br />L
<br />FOETATS
<br />ALIFORNIAICIL
<br />123
<br />***HISTORIC PROPERTY***
<br />Bldg #101111890
<br />Elect #20177292
<br />Permits issued on 9/12/22
<br />Plng ok per P. Gomez
<br />2014 N Flower St
<br />09/12/22
|