ID CONDUCTOR EGC CONDUIT <br />NUMBER OF <br />CONDUCTORS <br />IN CONDUIT <br />CONDUIT <br />FILL <br />PERCENT <br />TEMP. <br />CORR. <br />FACTOR <br />CONDUIT <br />FILL <br />FACTOR <br />CONT. <br />CURRENT <br />MAX. <br />CURRENT <br />(125%) <br />BASE <br />AMP. <br />DERATED <br />AMP. <br />1 12 AWG THWN-2, COPPER 8 BARE, COPPER AIR N/A N/A 0.96 (32°C) 1 9A 11.25A 40A 38.4A <br />2 12 NM-B 12 NM-B ATTIC \ WALL N/A N/A 0.96 (32°C) 1 9A 11.25A 20A 19.2A <br />3 10 AWG THWN-2, COPPER 8 AWG THWN-2, COPPER 0.75" DIA. EMT 4 18.8% 0.96 (32°C) 1 9A 11.25A 40A 38.4A <br />4 6 AWG THWN-2, COPPER 8 AWG THWN-2, COPPER 0.75" DIA. EMT 4 38.2% 0.96 (32°C) 1 9A 11.25A 75A 72A <br />WIRE SEGMENTS <br />ELECTRICAL CHARACTERISTICS <br />LABEL DESCRIPTION EQUIPMENT <br />PM1-9 SOLAR MODULES BRAND HANWHA Q-CELLS Q.PEAK DUO BLK G10+ 360 (360W) Voc:41.18V, <br />Isc:11.04A <br />I1-9 INVERTER ENPHASE IQ7-60-2-US <br />SW1 AC BLADE TYPE DISCONNECT SQUARE D D221NRB FUSIBLE, 2-POLE, 30A, 240VAC <br />JB1 DC JUNCTION BOX TYP 4"x4" <br />CB1 PV BREAKER CIRCUIT BREAKER, 20A, 240VAC <br />CB2 BREAKER CIRCUIT BREAKER, 15A, 240VAC <br />F1-2 FUSE FUSE, 20A, 240VAC <br />LC1 COMBINER ENPHASE X-IQ-AM1-240-3 IQ COMBINER 3, 125A <br />MEP MAIN SERVICE PANEL BUS: 100A; MAIN: 100A <br />EQUIPMENT DESCRIPTION <br />INVERTER (9) ENPHASE IQ7-60-2-US <br />MODULE HANWHA Q-CELLS Q.PEAK DUO BLK G10+ 360 (360W) <br />NUMBER OF MODULES 9 <br />ARRAY CIRCUITS 1 BRANCH OF 9 (9A) <br />STC POWER OF ARRAY 3 240W <br />PTC POWER OF ARRAY 3 009W <br />CEC POWER OUTPUT 2 250W <br />MAX AC OUTPUT CURRENT 9A <br />A B C D E F G H <br />A B C D E F G H <br />1 <br />2 <br />3 <br />4 <br />5 <br />6 <br />NE <br />W <br /> <br />P <br />V <br /> <br />S <br />Y <br />S <br />T <br />E <br />M <br />: <br /> <br />3. <br />2 <br />4 <br />0 <br /> k <br />W <br />p <br />DA <br />V <br />E <br /> <br />H <br />A <br />R <br />D <br />Y <br />33 <br />1 <br />4 <br /> <br />S <br />. <br /> <br />L <br />O <br />W <br />E <br />L <br />L <br /> <br />S <br />T <br />. <br />, <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />AP <br />N <br />: <br /> <br />4 <br />1 <br />0 <br />2 <br />5 <br />3 <br />1 <br />5 <br />DATE: 06.2.2022 <br />DESIGN BY: V.P. <br />CHECKED BY: <br />REVISIONS <br />R.D. <br />ROBERT DEAN, ILUM SOLAR INC. <br />4135 NORTHGATE BLVD. SUITE 9. <br />SACRAMENTO, CA 95834 <br />PHONE: (916) 905-0941 <br />LIC. No.: 1009260, C-46 <br />E-3 <br />THREE LINE DIAGRAM <br />1. PHOTOVOLTAIC SYSTEM GROUND WILL BE TIED INTO EXISTING GROUND AT MAIN SERVICE FROM DC <br />DISCONNECT/INVERTER AS PER СEC 250.166(B). "THE GROUNDING ELECTRODE CONDUCTOR SHALL NOT BE SMALLER THAN <br />THE LARGEST CONDUCTOR SUPPLIED BY THE SYSTEM AND NOT SMALLER THAN #8AWG." <br />2. EQUIPMENT OPERATING 150 VOLTS OR GREATER SHALL ONLY BE SERVICED OR REPLACED BY QUALIFIED PERSONNEL. <br />FIELD PROTECTION MAY BE IN THE FORM OF CONDUIT, CLOSED CABINET OR AN ENCLOSURE WHICH REQUIRES USE OF <br />TOOLS TO OPEN. <br />3. SOLAR PHOTOVOLTAIC SYSTEM EQUIPMENT WILL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS OF ART. 690 OF <br />THE 2019 CEC. <br />4. BACKFEED BREAKER TO BE INSTALLED ON OPPOSITE END OF MAIN BREAKER <br />5. MINIMUM HEIGHT OF CONDUIT ABOVE ROOF TO MATCH TEMPERATURE DERATING FACTOR. <br />6. SMOKE ALARMS AND CARBON MONOXIDE DETECTORS WILL MEET THE NECESSARY REQUIREMENTS PER CRC R314, R315 <br />7. UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVATION OF THE SOLAR PV SYSTEM. <br />8. WHEN A BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, BREAKER SHALL NOT READ "LINE AND LOAD" <br />9. PER CEC 705.12 (D)(2)(3)(B) - MAIN PANEL BUS BAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUS BAR <br />3314 S. Lowell St <br />07/29/22