Laserfiche WebLink
NN <br />L1 L2 <br />MAIN LUGS <br />PV-D <br />5 B <br />(N) SUB-PANEL PV-D <br />(N) AC DISCONNECT <br />(NON-FUSED) <br />UTILITY <br />GROUNDING ROD(S) <br />SET @ 6' APART MIN. <br />MAIN SERVICE PANEL <br />UTILITY METER <br />·UPGRADING (E) MAIN TO (N) <br />175A MAIN | 200A BUSBAR <br />·(N) 60A PV OCPD C/B TO BE <br />INSTALLED OPPOSITE END <br />OF MAIN OCPD <br />CANADIAN SOLAR: CS3N-395MS MODULE <br />MOD. IMP: (10.68A) * (1 STRING) = 10.68A <br />MOD. ISC: (11.44A) * (1 STRING) = 11.44A <br />ARRAY 1: (9) MODULES <br />ARRAY 2: (8) MODULES <br />(2) #10 PV-WIRE <br />UNDER EACH MODULE <br />FREE-AIR (SECURED) <br />(MANUFACTURE WIRE)1 <br />2 <br />PV-A 3 <br />(N) <br />J-BOX <br />ELECTRICAL EQUIPMENT LIST <br />#ITEM DESCRIPTION QTY. <br />1 SUB-PANEL 100A, 240V, 1ɸ, NEMA 3R RATED <br />SURFACE MOUNT5 <br />1SUB-PANEL <br />BREAKER(S)20A-2P | 240VB <br />A <br />ENPHASE: <br />COMBINER BOX <br />BREAKERS <br />20A-2P, 240V (SOLAR) <br />1 <br />4 <br />ENPHASE: <br />COMBINER BOX <br />80A | 240V <br />AC COMBINER BOX W/ IQ+ ENVOY <br />MONITORING, SINGLE ENCLOSURE <br />CONSOLIDATES INTERCONNECTION <br />1 <br />15A-2P, 240V (MONITORING) <br />2 <br />17MODULE CANADIAN SOLAR: CS3N-395MS 1 <br />172MICRO <br />INVERTER ENPHASE: IQ7PLUS-72-2-US <br />1JUNCTION BOX UL-LISTED WATER-TIGHT <br />NEMA 3R RATED3 <br />6 <br />71 PV BREAKER <br />(OCPD)60A-2P, 240V 8 <br />7 MAIN SERVICE <br />PANEL (E) 200A MAIN | 200A BUSBAR 1 <br />6 160A, 2P-240V, BLADE TYPEAC DISCONNECT <br />(NON-FUSED) <br />ENPHASE: IQ7PLUS-72-2-US MICRO-INVS. <br />NOM. AC VOLTAGE: 240V <br />MAX. INPUT DC VOLTAGE: 60V <br />NOM. AC OUTPUT CURRENT: 1.21A <br />MAX. DC SHORT CIRCUIT CURRENT: 15A <br />MAX. MODS. PER 20A BRANCH: 13 <br />MOD. PAIRING: 235W - 440W <br />UTILITY <br />AMPACITY <br />TABLE 310.15(B)(16) <br />RATING @ 90° <br />(6) #10 THWN-2 <br />(40 A) <br />CORRECTION FACTOR <br />TABLE 690.31(A) <br />AMBIENT TEMP. @ 61 -70° C <br />TEMP. RATING @ 90° <br />(0.58) <br /> ( 40 A) * (0.87) * (1.00) = 34.80 A <br />(40 A) <br />CORRECTION FACTOR <br />TABLE 690.31(A) <br />AMBIENT TEMP. @ 41 - 45° C <br />TEMP. RATING @ 90° <br />(0.87) <br />ADJUSTMENT FACTOR <br />TABLE 310.15(B)(3)(a) <br /># OF COND. (3) MAX. <br />(1.00) <br />SYSTEM AC WIRING TOTAL: (N) SYSTEM ONLY <br />SYSTEM WAC: 6086.45WAC <br />MODULE ISC: 11.44A * 156% = 17.85A >PV-B DESIGN <br />SYSTEM IMP: 25.36A >PV-C DESIGN <br />SYSTEM PMAX: 25.71A ----> 60A C/B >SUB-PANEL C/B <br />SYSTEM AC WIRING TOTAL: BOTH SYSTEMS <br />COMBINED IMP: (E)30A + (N)25.36A = 55.36A >PV-D DESIGN <br />COMBINED OCPD: (E)30A + (N)60A = 90A >SYSTEM OCPD <br /> PV MODS. > J-BOX (PV-A) <br /> (6) #10 Q-CABLE (L1, L2, N) <br /> (1) #6 BARE COPPER - EGC CONT. (G) <br /> FREE-AIR SECURED <br /> J-BOX > COMB. BOX (PV-B) <br /> (6) #10 THWN-2 (L1, L2, N) <br /> (1) #8 THWN-2 AWG EGC CONT. (G) <br /> RAN THROUGH: 3/4 " EMT <br /> COMB. BOX > SUB-PANEL (PV-C) <br /> (3) #10 THWN-2 (L1, L2, N) <br /> (1) #8 THWN-2 AWG EGC CONT. (G) <br /> RAN THROUGH: 3/4 " EMT <br /> ( 75 A) * (0.87) * (1.00) = 65.25A > PV-D DESIGN (55.36A) > GROUND <br />AMPACITY <br />TABLE 310.15(B)(16) <br />RATING @ 90° <br />(3) #6 THWN-2 <br />(75 A) <br />CORRECTION FACTOR <br />TABLE 690.31(A) <br />AMBIENT TEMP. @ 41 - 45° C <br />TEMP. RATING @ 90° <br />(0.87) <br />ADJUSTMENT FACTOR <br />TABLE 310.15(B)(3)(a) <br /># OF COND. (3) MAX. <br />(1.00) <br /> SUB-PANEL > AC DISCO. > MSP (PV-D) <br /> (3) #6 THWN-2 (L1, L2, N) <br /> (1) #8 THWN-2 AWG EGC CONT. (G) <br /> RAN THROUGH: 1" EMT <br /> > PV-C DESIGN (25.36A) > GROUND <br /> > PV-B DESIGN (17.85A) > ROOFTOP <br />AMPACITY <br />TABLE 310.15(B)(16) <br />RATING @ 90° <br />(3) #10 THWN-2 <br />ADJUSTMENT FACTOR <br />TABLE 310.15(B)(3)(a) <br /># OF COND. (4 - 6) MAX. <br />(0.80 ) <br />8 <br /> (25°C - (24.4°C + 22°C) * (-0.34%/°C) = 7.29% VOLTAGE DROP <br /> (37.0VMP) * (7.29%) = 2.70V PER - (37.0VMP) = 34.3V VMP <br /> (34.3V) * (ARRAY OF 9) = 308.72V @ AVR. HIGH 24.4°C <br />(200A BUSBAR) * (120%) = 240A MAX. <br />175A MAIN BREAKER + 60A PV BACKFEED = 235A <br />235A ≤ 240A PER [CEC 705.12 (B)(2)(3)(b)] <br /> ( 40 A) * (0.58) * ( 0.80 ) = 18.56 A <br />SYSTEM AC WIRING RUN: BRANCH #1 <br />CONTINUOUS OUTPUT CURRENT (IMP): <br />(369.1 PTC RATING) * (9 MOD.) * (97.0% CEC INV. EFF.) = <br />3222.24WAC / 240VAC = 13.43A <br />MAX OUTPUT CURRENT (PMAX): <br />1.21A(9) * 125% = 13.61A ---> 20A COMBINER C/B <br />SYSTEM AC WIRING RUN: BRANCH #2 <br />CONTINUOUS OUTPUT CURRENT (IMP): <br />(369.1 PTC RATING) * (8 MOD.) * (97.0% CEC INV. EFF.) = <br />2864.22WAC / 240VAC = 11.93A <br />MAX OUTPUT CURRENT (PMAX): <br />1.21A(8) * 125% = 12.10A ---> 20A COMBINER C/B <br />CONDUCTOR AMPACITY CALCULATIONCONDUCTOR SCHEDULE <br />PROJECTED MINIMUM SYSTEM VOLTAGE <br />MAXIMUM OCPD CALCULATION <br />EQUIPMENT DATA SYSTEM CALCULATIONS <br />·DC SYSTEM AS UNGROUNDED TYPE <br />·ALL CONDUCTOR(S) TO BE RAN IN RACEWAY <br />·SYSTEM EQUIPPED WITH RAPID SHUTDOWN FUNCTION PER [CEC 690.12] <br />·PHOTOVOLTAIC SYSTEM GROUND WILL BE TIED INTO EXISTING GROUND AT <br />MAIN SERVICE FROM DC DISCONNECT/INVERTER AS PER [NEC 250.166(B)] <br />"THE GROUNDING ELECTRODE CONDUCTOR SHALL NOT BE SMALLER THEN <br />THE LARGEST CONDUCTOR SUPPLIED BY THE SYSTEM & NOT SMALLER THEN <br />#8 AWG." <br />· SYSTEM GROUNDING ELECTRODE CONDUCTOR FOR PHOTOVOLTAIC SYSTEM <br />SIZED TO MEET THE REQUIREMENTS OF 250.66 (AC) & 250.66 (DC), 690.74(C) <br />NOT SMALLER THEN #8 AWG <br />· EQUIPMENT OPERATING 150V OR GREATER SHALL ONLY BE SERVICED OR <br />REPLACED BY QUALIFIED PERSONNEL. FIELD PROTECTION MAY BE IN THE <br />FORM OF CONDUIT, CLOSED CABINET OR AN ENCLOSURE WHICH REQUIRES <br />USE OF TOOLS TO OPEN. <br />· SOLAR PHOTOVOLTAIC SYSTEM EQUIPMENT WILL BE INSTALLED IN <br />ACCORDANCE W/ REQUIREMENTS OF ARTICLE 690 OF THE 2019 CEC. <br />·MIN. HEIGHT OF CONDUIT ABOVE ROOF TO MATCH TEMP. DE-RATING FACTOR <br />·PHOTOVOLTAIC DC CONDUCTORS ENTERING THE BUILDING SHALL BE <br />INSTALLED IN METAL CONDUIT & THE CONDUIT SHALL BE LABELED "CAUTION <br />DC CONDUIT" EVERY 10-FT. <br />· SMOKE ALARMS & CARBON MONOXIDE DETECTORS WILL MEET THE <br />NECESSARY REQUIREMENTS PER [CRC R314, R315] <br />·UTILITY COMPANY WILL BE NOTIFIED PRIOR TO ACTIVATION OF THE <br />PHOTOVOLTAIC SOLAR SYSTEM <br />·GROUNDING TO BE INSTALLED PER MODULE MANUFACTURE INSTRUCTIONS. <br />GROUND METHOD: GROUND LUGS W/ BARE COPPER WIRE <br />·CENTER-FED & OFF-SET SWITCHBOARDS / PANEL BOARDS ARE NOT RECOGNIZED TO <br />MEET THE REQUIREMENTS OF [CEC 705.12(D)(7)] <br />·FOR ELECTRICAL SERVICE REPLACEMENTS, PROVIDE BONDING TO THE METAL PIPES OF <br />NATURAL GAS, HOT & COLD WATER PER [CEC 250.104] <br />·IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE VERIFIABLE GROUNDING <br />ELECTRODE: IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ONE <br />·THE G.E.C. MUST BE CONTINUOUS AS PER CEC 690.47(A) & 250.64(C) <br />·A SINGLE ROD ELECTRODE SHALL BE SUPPLEMENTED BY AN ADDITIONAL ELECTRODE <br />PER 2019 CEC 250.53(A)(2) <br />· THE COLOR OF UNGROUNDED CONDUCTORS SHALL BE OTHER THEN FOR GROUNDED, <br />(NEUTRAL), CONDUCTORS (SOLID WHITE, GRAY, OR WITH 3 WHITE STRIPES, 200.6, 200.7 <br />& 400.22), AND GROUNDING CONDUCTORS (BARE W/O COVERING, GREEN, OR GREEN <br />WITH YELLOW STRIPES, 250.119 & 400.23) PER 310.110(C) <br />·METAL UNDERGROUND WATER PIPE: INDICATE THE CONNECTION TO THE INTERIOR <br />METAL WATER PIPING SHALL BE MADE W/IN 5' FROM THE POINT OF ENTRANCE PER <br />250.68(C)(1) <br />PREPARED BY:DATE: <br />PROJECT #: <br />SHEET NAME: <br />SHEET #: <br />PROPOSED EQUIPMENT:SCOPE OF WORK: HOMEOWNER:CONTRACTOR: <br />PV-G.01 <br />GENERAL NOTES4/28/2022 <br />HP-192 <br />THE DAI TRAN RESIDENCE <br />405 W ALPINE AVE. <br />SANTA ANA | CA | 92707 <br />APN #: 41018218 <br />ALL-AMERICAN <br />SOLAR SERVICES <br />L.L.C. <br />x AJC <br />(E) <br />AC DISCONNECT <br />(E) INVERTER <br />EXISTING ARRAY <br /> (17) TRINA SOLAR: TSM-305DD05A. 05(II) MODULES <br /> (1) SOLAREDGE: SE5000H-US INVERTER <br />(E) CONDUCTOR <br />(E) CONDUCTOR <br />PV-C <br />4 A <br />(N) COMBINER <br />BOXPV-B <br />LARSUN SOLAR <br />CSLB: #583458 (C-46) <br />ADDRESS: 439 E HARRISON ST. UNIT E <br />CITY|ZIP: CORONA | CA | 92879 <br />PHONE: (951) 298-9007 <br />best solar <br /> (17) CANADIAN SOLAR: CS3N-395MS <br /> MODULES <br /> (17) ENPHASE: IQ7PLUS-72-2-US <br /> MICRO-INVERTERS <br />INSTALL A NEW 6.71kW (DC)|6.08kW(AC)|6.12kW (CEC AC) PV SOLAR SYSTEM ON <br />AN (E) RESIDENTIAL ROOF. ALL WORK TO BE CONDUCTED UNDER AN ACTIVE CSLB <br />LICENSE & SHALL ADHERE TO ALL FEDERAL|STATE|LOCAL LAWS & CODES. PLEASE <br />REFERENCE ALL CODE(S) THROUGHOUT THIS PLAN SET FOR FULL COMPLIANCE. <br />405 W. Alpine Ave <br />- 2017720009/06/22