Laserfiche WebLink
TO E.603.AF <br />UTILITY-DLX8 <br /> Utility Company - <br />SystemNominalVoltage 480.0 V <br />SC Contribution 3P 9021.0 Amps <br />SC Contribution SLG 5638.0 Amps <br />CBL-SWBD MSB <br />500 kcmil <br />85.0 ft <br />5 per phase <br />MF-SWBD MSB <br />BUSSMANN <br />KTU <br />Sensor/Trip 2000.0 A <br />InterruptingRating 200.0 kA <br />SWBD MSB <br />61.1 Cal/cm^2 <br />17.066 kA <br />211 inches <br />480.0 V <br />F-PNL HC <br />BUSSMANN <br />JKS <br />Sensor/Trip 200.0 A <br />InterruptingRating 200.0 kA <br />CBL-PNL HC <br />4/0 AWG <br />435.0 ft <br />1 per phase <br />S <br />P <br />T-PNL LC <br />75 kVA <br />5.0000 % <br />480 V <br />208 V <br />CBL-PNL LC <br />4/0 AWG <br />15.0 ft <br />1 per phase <br />PNL HC <br />0.09 Cal/cm^2 <br />5.672 kA <br />4 inches <br />480.0 V <br />CB-T-PNL LC <br />SQUARE D <br />ED <br />Sensor/Trip 100.0 A <br />Plug 100.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-T-PNL LC <br />2 AWG <br />15.0 ft <br />1 per phase <br />MCB-PNL LC <br />SQUARE D <br />QB <br />Sensor/Trip 225.0 A <br />Plug 225.0 A <br />Settings <br /> Fixed <br />InterruptingRating 10.0 kA <br />PNL LC <br />5.45 Cal/cm^2 <br />3.084 kA <br />46 inches <br />208.0 V <br />F-PNL HK <br />BUSSMANN <br />JKS <br />Sensor/Trip 200.0 A <br />InterruptingRating 200.0 kA <br />F-PNL HL <br />BUSSMANN <br />JKS <br />Sensor/Trip 200.0 A <br />InterruptingRating 200.0 kA <br />F-PNL HM <br />BUSSMANN <br />JKS <br />Sensor/Trip 200.0 A <br />InterruptingRating 200.0 kA <br />CBL-PNL HM <br />3/0 AWG <br />45.0 ft <br />1 per phase <br />PNL HM <br />0.11 Cal/cm^2 <br />14.183 kA <br />4 inches <br />480.0 V <br />F-PNL DISTRIBUTION <br />BUSSMANN <br />KLU <br />Sensor/Trip 1200.0 A <br />InterruptingRating 200.0 kA <br />S <br />P <br />T-PNL LM <br />75 kVA <br />5.0000 % <br />480 V <br />208 V <br />CBL-PNL LM <br />4/0 AWG <br />15.0 ft <br />1 per phase <br />CB-T-PNL LM <br />SQUARE D <br />ED <br />Sensor/Trip 100.0 A <br />Plug 100.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-T-PNL LM <br />2 AWG <br />15.0 ft <br />1 per phase <br />MCB-PNL LM <br />SQUARE D <br />QB <br />Sensor/Trip 225.0 A <br />Plug 225.0 A <br />Settings <br /> Fixed <br />InterruptingRating 10.0 kA <br />PNL LM <br />6.4 Cal/cm^2 <br />3.546 kA <br />51 inches <br />208.0 V <br />CB-TERM-EF11/12 <br />SQUARE D <br />ED <br />Sensor/Trip 20.0 A <br />Plug 20.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-TERM-EF11/12 <br />10 AWG <br />190.0 ft <br />1 per phase <br />CBL-DS-EF-11 <br />10 AWG <br />31.0 ft <br />1 per phase <br />DS-EF-11 <br />0.02 Cal/cm^2 <br />1.025 kA <br />2 inches <br />480.0 V <br />CBL-DS-EF-12 <br />10 AWG <br />2.0 ft <br />1 per phase <br />DS-EF-12 <br />0.03 Cal/cm^2 <br />1.173 kA <br />2 inches <br />480.0 V <br />CB-TERM-EF15 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-DS-EF-15 <br />12 AWG <br />216.0 ft <br />1 per phase <br />DS-EF-15 <br />0.12 Cal/cm^2 <br />0.671 kA <br />4 inches <br />480.0 V <br />CBL-PNL HK <br />4/0 AWG <br />694.0 ft <br />1 per phase <br />PNL HK <br />0.16 Cal/cm^2 <br />3.987 kA <br />5 inches <br />480.0 V <br />CBL-PNL HL <br />3/0 AWG <br />349.0 ft <br />1 per phase <br />PNL HL <br />0.09 Cal/cm^2 <br />5.973 kA <br />3 inches <br />480.0 V <br />S <br />P <br />T-PNL LK <br />75 kVA <br />5.0000 % <br />480 V <br />208 V <br />CBL-PNL LK <br />4/0 AWG <br />15.0 ft <br />1 per phase <br />CB-T-PNL LK <br />SQUARE D <br />ED <br />Sensor/Trip 100.0 A <br />Plug 100.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-T-PNL LK <br />2 AWG <br />15.0 ft <br />1 per phase <br />MCB-PNL LK <br />SQUARE D <br />QB <br />Sensor/Trip 225.0 A <br />Plug 225.0 A <br />Settings <br /> Fixed <br />InterruptingRating 10.0 kA <br />PNL LK <br />4.94 Cal/cm^2 <br />2.828 kA <br />44 inches <br />208.0 V <br />S <br />P <br />T-PNL LL <br />75 kVA <br />5.0000 % <br />480 V <br />208 V <br />CBL-PNL LL <br />4/0 AWG <br />15.0 ft <br />1 per phase <br />CB-T-PNL LL <br />SQUARE D <br />ED <br />Sensor/Trip 100.0 A <br />Plug 100.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-T-PNL LL <br />2 AWG <br />15.0 ft <br />1 per phase <br />MCB-PNL LL <br />SQUARE D <br />QB <br />Sensor/Trip 225.0 A <br />Plug 225.0 A <br />Settings <br /> Fixed <br />InterruptingRating 10.0 kA <br />PNL LL <br />5.55 Cal/cm^2 <br />3.130 kA <br />47 inches <br />208.0 V <br />CB-DS-CF 11 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-DS-CF 11 <br />10 AWG <br />75.0 ft <br />1 per phase <br />DS-CF 11 <br />0.05 Cal/cm^2 <br />1.876 kA <br />2 inches <br />480.0 V <br />CB-DS-CF 12 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-DS-CF 12 <br />10 AWG <br />65.0 ft <br />1 per phase <br />DS-CF 12 <br />0.05 Cal/cm^2 <br />2.029 kA <br />2 inches <br />480.0 V <br />CB-DS-CF 15 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-DS-CF 15 <br />10 AWG <br />65.0 ft <br />1 per phase <br />DS-CF 15 <br />0.06 Cal/cm^2 <br />2.404 kA <br />3 inches <br />480.0 V <br />CB-HL-DS-SF-2 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-HL-DS-SF-2 <br />10 AWG <br />180.0 ft <br />1 per phase <br />HL-DS-SF-2 <br />0.03 Cal/cm^2 <br />1.113 kA <br />2 inches <br />480.0 V <br />CB-HK-DS-SF-2 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-HK-DS-SF-2 <br />10 AWG <br />148.0 ft <br />1 per phase <br />HK-DS-SF-2 <br />0.03 Cal/cm^2 <br />1.198 kA <br />2 inches <br />480.0 V <br />CB-DS-CF-G23 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-DS-CF-G23 <br />10 AWG <br />117.0 ft <br />1 per phase <br />DS-CF-G23 <br />0.03 Cal/cm^2 <br />1.417 kA <br />2 inches <br />480.0 V <br />CB-DS-CF-G27 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-DS-CF-G27 <br />10 AWG <br />203.0 ft <br />1 per phase <br />DS-CF-G27 <br />0.09 Cal/cm^2 <br />0.938 kA <br />4 inches <br />480.0 V <br />CB-DS-CF-E23 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-DS-CF-E23 <br />10 AWG <br />218.0 ft <br />1 per phase <br />DS-CF-E23 <br />0.09 Cal/cm^2 <br />0.886 kA <br />4 inches <br />480.0 V <br />CB-DS-CF-H19.5 <br />SQUARE D <br />ED <br />Sensor/Trip 15.0 A <br />Plug 15.0 A <br />Settings <br /> Fixed <br />InterruptingRating 18.0 kA <br />CBL-DS-CF-H19.5 <br />10 AWG <br />145.0 ft <br />1 per phase <br />DS-CF-H19.5 <br />0.03 Cal/cm^2 <br />1.333 kA <br />2 inches <br />480.0 V <br />CBL-PNL DISTRIBUTION <br />600 kcmil <br />53.0 ft <br />3 per phase <br />E.602.AF <br />Uninterruptible <br />Power Supply (UPS) <br />Bus - Panel (PNL), Switchboard <br />(SWBD), Disconnect Switch (DS), <br />or Control Panel (CP) <br />Auto/Manual Transfer Switch <br />(ATS/MTS) <br />Utility <br />Motor (M) <br />Fuse (F) <br />E N <br />Receptacle (R) <br />Transformer (T) <br />Generator <br />(GEN) <br />(Main) Circuit Breaker <br />(MCB, CB) <br />Capacitor Bank (C) <br />Utility MeterWH <br />Bus Duct (BD) <br />Battery (BAT) <br />Rectifier (REC) <br />Switch (SW) <br />Fuse Switch (FS) <br />1. NOT TO BE USED FOR CONSTRUCTION PURPOSES <br />2. THIS DRAWING WAS CREATED FROM FIELD <br /> NOTES TAKEN FROM THE SITE SURVEY ON <br /> THE DATE SHOWN IN THE DESCRIPTION BOX <br /> BELOW <br />3. ELECTRICAL DETAILS HAVE BEEN <br /> DOCUMENTED WHERE INFORMATION <br /> HAS BEEN VERIFIED WITH A SURVEY AND MAY BE A <br /> COMBINATION OF THE FOLLOWING: <br />• EQUIPMENT NAMEPLATES <br />• EXISTING EQUIPMENT LABELING <br />• EXISTING ELECTRICAL SITE DRAWINGS <br />Legend <br />Load (L) <br />(Main) Medium Voltage Circuit <br />Breaker (MCB, CB) <br />Relay (RLY) <br />C:\Users\Jeff Lunsford\Desktop\arc_flash_report\amazonlogo.jpg <br />515 E Dyer Rd - <br />2017714908/25/22