Laserfiche WebLink
10 Technical Data SMA Solar Technology AG <br />Installation ManualSBxx-1SP-US-41-IA-xx-12 66 <br />SB3.0-1SP-US-41 SB3.8-1SP-US-41 SB5.0-1SP-US-41 <br />AC voltage range at <br />240 V <br />211 V to 264 V 211 V to 264 V 211 V to 264 V <br />Nominal AC current at <br />208 V <br />14.4 A 16 A 24 A <br />Nominal AC current at <br />240 V <br />12.5 A 15.8 A 21 A <br />Maximum output cur- <br />rent at 208 V <br />14.5 A 16 A 24 A <br />Maximum output cur- <br />rent at 240 V <br />12.5 A 15.8 A 21 A <br />Total harmonic factor <br />of output current <br /><4 %<4 %<4 % <br />Maximum residual out- <br />put current <br />30.4 A 30.4 A 30.4 A <br />Duration of the maxi- <br />mum residual output <br />current <br />250 ms 250 ms 250 ms <br />Line synchronization <br />characteristics/inrush <br />current <br />Method 2/2.4 A Method 2/2.4 A Method 2/2.4 A <br />Rated power frequency 60 Hz 60 Hz 60 Hz <br />Operating range at AC <br />power frequency <br />60 Hz <br />59.3 Hz to 60.5 Hz 59.3 Hz to 60.5 Hz 59.3 Hz to 60.5 Hz <br />Output power at <br />+60°C (+140°F) <br />> 3300 W > 3300 W > 3300 W <br />Power factor at rated <br />power <br />1 1 1 <br />Range of the displace- <br />ment power factor (ad- <br />justable) <br />0.8overexcited to <br />0.8underexcited <br />0.8overexcited to <br />0.8underexcited <br />0.8overexcited to <br />0.8underexcited <br />Feed-in phases 1 1 1 <br />Phase connection 2 2 2 <br />Surge category in ac- <br />cordance with <br />UL 1741 <br />IV IV IV <br />EN <br />G <br />L <br />I <br />S <br />H <br />534 S Sycamore St <br />- 10110979707/01/22