GENERAL <br />1. All electrical work to be installed by a qualified licensed electrician and apprentices <br />working under the direct supervision of the licensed contractor. <br />2. All solar modules shall be listed 1703 & CEC approved. All inverters shall be UL listed <br />1741 certified & CEC approved. All electrical components and materials shall be listed <br />for <br />its purpose and installed in a workman-like manner. All customer equipment shall <br />meet <br />appropriate NEMA standards. <br />3. All fabrication and manufacturing shall be performed by certified individuals in <br />approved <br />assembly and fabrication shops. <br />4. Prior to commencement of any work, the contractor shall notify the engineer of any <br />discrepancies noted among site conditions, manufacturer recommendations or <br />authority <br />having jurisdiction (AHJ). <br />5. Contractor-initiated changes shall be submitted in writing to the engineer in the <br />form of a "RFI" (Request for Information), prior to making any changes. Approved <br />changes shall require a drawing revision to maintain control over the engineer <br />approved <br />design. <br />6. The electrical contractor is advised that all drawings and component manuals are to <br />be <br />understood prior to installation. The contractor is advised to have all switches in <br />"off "position and the fuses removed prior to the installation of fuse-bearing <br />components. <br />7. This proposed solar electric system is intended to operate in parallel with power <br />received <br />from the utility service provider. <br />8. Anti-islanding protection is requirement of UL 1741 and is intended to prevent the <br />operation of the PV System when the utility grid is not operational. <br />9. Permission to operate the system is not authorized until final inspections and <br />approvals are obtained from the local authority having jurisdiction and the local <br />utility service provider. <br />ELECTRICAL <br />1. PV installation shall comply with article 690 of 2017 NEC. <br />2. The inverter for the proposed solar electric system shall be identified for use in solar <br />photovoltaic systems. All equipment shall be UL approved. <br />3. This system is intended to connect to the existing facility power system at one point. <br />The point of common coupling (POCC). This connection shall be in compliance <br />with the NEC article 690.64 "POINT OF CONNECTION". <br />4. All circuits shall have individual source circuit protection for testing and isolation. <br />All combiner boxes shall have disconnecting means near the combiner <br />for isolation and testing. <br />5. All disconnects and combiners shall be secured from unauthorized / unqualified <br />personnel by locking location. <br />6.All disconnects, combiners, pull/ splice boxes and enclosures shall be listed for its <br />purpose. <br />7. Equipment shall be installed in a secure area. Inverter performance may be affected <br />if installed in direct sunlight. <br />8. DC array conductors are to remain outside of building prior to fused combiner box or <br />fused DC disconnecting means. <br />9. Raceway for grounding electrode conductor shall be bonded at each end. <br />10.The DC grounding electrode conductor shall be bonded to the AC grounding <br />electrode conductor to make a grounding electrode system according to CEC 250.52 <br />and 250.53. The bonding conductor shall be no smaller than the largest grounding <br />electrode conductor, either DC or AC, 690.47(c)(1) <br />11.Grounding electrode conductor from inverter to grounding electrode shall be a <br />minimum of bare copper armor sheathed cable and sized for the largest conductor <br />supplied by the system. CEC 250.64(b), 250.166(b). <br />12. The PV connection in the panel board shall be positioned at the opposite load end <br />from <br />the input feeder location or main circuit location: CEC 690.64(b)(7). <br />RACKING <br />1. All fasteners shall be corrosion resistant appropiate for site conditions. Connectors <br />shall be torqued per device specifications or engineering recommendations. <br />2. The method of attachment creates a unified structure to meet dead / wind load and <br />seismic requirements. Solar modules will be secured to the existing roof as specified <br />on the structural sheets. Existing roof equipment will not be affected by the PV <br />system. <br />3. All roofing repair must maintain existing class and type of roof and all work shall be <br />in accordance with the roofing manufacturer installation requirements. <br />.. <br />..EPB <br />ECO PLANET BUILDERS <br />7127 Laurel Canyon Blvd., N.Hollywood, CA 91605 <br />(818)427-4249 <br />C0 PL.ANET BI.IJLCeRs License Number: 1031107 <br />Contractor Signature: <br />PHOTOVOLTAIC GENERAL NOTES <br />WIRING <br />1. All wiring methods and installation practices shall conform to the N.E.C., <br />local state codes and other local codes. <br />2. Exposed PV solar panel wiring will be USE-2 / RHW-2, 90 °C, wet rated, and <br />UV resistant. All exposed cables, such module leads, shall be secured with <br />mechanical or other sunlight resistant means. <br />3. All grounded conductors are white and equipment grounding conductors are <br />green or bare. (NEC 200-6). <br />4. Flexible metal conduit is generally suitable for installation in dry locations <br />(NEC 348.12) should it be employed, supports will be no more than 12 inches <br />from boxes (junction box, cabinets, or conduit fittings and no more than <br />54 inches apart (NEC 348.30). <br />5. Liquid tight flexible metal conduit is generally suitable for installation in wet <br />and dry locations , should it be employed, supports will be no more <br />than 12 inches from boxes (junction box, cabinets, or conduit fitting) and no more <br />than 54" apart (NEC 530.30). <br />6. Liquid tight flexible metal conduit is generally suitable for installation in wet <br />and dry locations, should it be employed, supports will be no more <br />than 12 inches from boxes (junction box, cabinets, or conduit fitting) and no more <br />than 36" apart (NEC 356.30). <br />7. Unless marked as UV resistant, PVC is not approved for installation in locations <br />subjected to direct sunlight and shall not be employed in any such location. <br />8. Long straight conduit runs, 100 feet or more, shall have expansion fittings. <br />9 If used, all wire nuts are to be suitable for theirs intended application. Where <br />installed in a moisture prone environment, wire nuts shall be <br />equivalent ideal blue, and shall be installed per manufactures <br />specifications by a qualified / certified person. <br />10. Fuses and wires subject to transformer inrush current shall be sized accordingly. <br />11.All DC materials shall be listed for 600V DC. <br />12. The Photovoltaic Source Circuits and Photovoltaic Output Circuits of this <br />proposed solar system shall not be contained in the same raceway, cable tray, cable <br />outlet box, junction box, or other similar fitting as feeders or branch circuits of <br />other systems unless the conductors of the different systems are separated by <br />a partition or are connected together. <br />13. Connectors to be torqued per devise listing or manufactures specifications. <br />14. Split bolts/ splices/ connectors shall be insulated with approved means. UL <br />listed electrical tape alone is not suitable as the only insulation means. <br />Follow manufactures instructions for application of insulating product. <br />15. AC wiring shall be cu. wire rated for 600V. <br />16. Use listed bridgeport raintight connectors as available. Like product may be <br />substituted so long as it is listed for its intended purpose. Seal all other electrical <br />connections with water resistant caulking or silicone. <br />17. Protect USE-2 / RHW-2 from sharp or other suitable means. <br />18. Label combiner box wiring red for positive, white for negative, and green for <br />grounded <br />conductor. <br />19. A field wiring larger than 6 AWG that is not color coded shall be tagged at both <br />ends with permanent wire markers to identified polarity and ground. <br />(See Electrical diagram and electrical detail for more grounding information). <br />20. Only one connection to DC circuits and one connection to AC circuits will be used for <br />system grounding (NEC 250.21) both the AC and DC ground will be referenced to the <br />same point. <br />21. Equipment grounding conductors and sys. grounding conductors will have as short a <br />distance to ground as possible and a minimum number of turns. <br />22. Non-current carrying metal parts shall be checked for proper grounding, noting that <br />terminal lugs bolted on an enclosures' finished surface may be insulated <br />because of the paint/finish, pain/finish at point of contact shall be properly removed <br />and repaired when necessary. <br />23. Modules shall be grounded with equipment grounding conductors bonded <br />to a location approved by the manufacturer with a mean of bonding <br />listed for this purpose. <br />24. The connection to the module or panel of this proposed solar electric system shall <br />be arranged so that the removal of a module or a panel from the photovoltaic <br />source circuit does not interrupt a grounded conductor to another <br />photovoltaic source circuit, sets of modules interconnected as systems rated <br />at S0V or less with or without blocking diodes, and having a single overcurrent <br />protection device shall be labeled as a single source circuit. <br />25. Grounding system components shall be listed for their purpose, included but not <br />limited to ground rods, grounding lugs, grounding clamps, etc. Grounding <br />devices exposed to the environment shall be rated for direct burial or listed for their <br />intended purpose. <br />PROJECT NAME <br />CARLOS/LUZ GUILLEN <br />624 E 3 RD ST, SAN TA AN A, CA 92701 <br />PROTECTION <br />1. Photovoltaic inverters shall be equipped with DC ground fault protection to reduce fire <br />hazards. Inverters are also equipped with anti-islanding circuitry. <br />2. Circuits, over current devices, and blocking diodes shall be permitted on the <br />photovoltaic side of the photovoltaic disconnection means. <br />3. Means shall be provided to disconnect equipment such as inverters, batteries, <br />charge controllers, and the like from all ungrounded conductors of all sources, if the <br />equipment is energized from more than one source, the disconnecting means shall be <br />grouped and identified. <br />4. A simple disconnecting means shall be permitted for the combined ac output of one <br />or more inverters in an interactive system. <br />5. Disconnecting means shall be provided to disconnect a fuse from all sources of <br />supply if the fuse is energized from both direction and is accessible to other than <br />qualified persons. Such a fuse in a photovoltaic source circuit shall be capable <br />of being disconnected independently of fuses in other photovoltaic source circuits. <br />6. Means shall be provided to disconnect all current carrying conductors of the <br />photovoltaic power source from all other conductors in the building. <br />7. Where a circuit grounding connection is not designed to be automatically interrupted <br />as <br />part of the ground fault protection system required by 690.5, a switch or circuit <br />breaker used as a disconnecting means shall not have a pole in the grounded <br />conductor. <br />8. The grounded conductor may have a bolted or terminal disconnecting means to allow <br />maintenance or troubleshooting by qualified personnel. <br />9. The disconnecting means shall not be required to be suitable as service <br />equipment and shall be rated in accordance with section 690. <br />LABELS <br />1. Required safety signs and labels shall be permanently attached by adhesive or other <br />mechanical means. Labels shall comply with Article 690 of the NEC or other applicable <br />state and local codes. See labels and marking page for more information. <br />2. Any switch, fuses, or circuit breakers that can be energized in either direction shall be <br />labeled as follows: <br />WARNING: <br />ELECTRICAL SHOCK HAZARD. DO NOT <br />TOUCH THE TERMINALS. <br />TERMINALS ON BOTH THE LINE AND <br />LOAD SIDE MAY BE <br />ENERGIZED IN THE OPEN POSITION. <br />3. This photovoltaic system will be equipped with a DC disconnect which will be labeled <br />as follows: <br />PHOTOVOLTAIC DISCONNECT MEANS <br />DC DISCONNECT <br />4. This photovoltaic system will be equipped with an AC disconnect which will be labeled <br />as follows: <br />PHOTOVOLTAIC DISCONNECTING MEANS <br />AC DISCONNECT <br />5. A marking specifying the photovoltaic power source rated as follows shall be proved <br />at <br />an accessible location at the disconnecting means for the power source. <br />6. Permanent labels shall be provided. No sharpie marking will be allowed within any <br />main service panel or Sub-Panel. <br />7. Marking shall have red background. <br />8. White lettering minimum 3/8" letter height and all capital letters "Arial" or similar font. <br />9. Reflective weather resistant material suitable for the environment (durable adhesive) <br />materials must meet this requirements. <br />10. Marking is required in all interior and exterior DC conduit, raceways, enclosures, cable <br />assemblies, and junction boxes to alert the fire service to avoid cutting them. <br />11. Marking shall be placed every 10 feet, at turns and above and/ or penetrations, <br />and at all DC combiner and junction boxes. <br />PV installation shall comply with 2019 CEC, 2019 CFC, 2019 CRC (or CBC where <br />applicable), 2019 CGBSC, 2019 CEnC and local jurisdiction code requirements. <br />PROJECT INFORMATION <br />NAME: CARLOS/LUZ GUILLEN <br />ADDRESS: 624 E 3RD ST, SANTA ANA, CA 92701 <br />APN / AHJ: 39848209 <br />CONTRACTOR INFORMATION <br />CONTRACTOR: ECO PLANET BUILDERS <br />ADDRESS: 7127 Laurel Canyon Blvd., N.Hollywood, CA 91605 <br />PHONE: (818)427-4249 <br />LICENSE#: 1 031107 <br />SYSTEM SPECIFICATIONS <br />SIZE (kW): <br />MODULE: <br />INVERTER: <br />13 <br />13 <br />4.485 <br />Mission Solar MSE345SX5T <br />Enphase IQ7Plus-72-2-US <br />SCOPE OF WORK <br />INSTALL <br />13 ROOF MOU NTE D PV SOLAR MODULES, <br />13 Enphase IQ7Plus-72-2-US Inverter <br />TITLE <br />A SHEETS <br />E SHEETS <br />S SHEETS <br />MAIN PANE L UPG RADE <br />TABLE OF CONTENTS <br />GEN ERAL NOTES & PROJ ECT INFO <br />ARCHITECHURAL <br />ELECTRICAL <br />STRUCTURAL <br />4.485 kW-DC 4.053 kW-AC Photovoltaic System Page: TITLE <br />Drawn By: VS. COVER PAGE Date: 5/26/22 Revision: O <br />BLDG # 101111693 <br />ELECT # 20177150 <br />ISSUED: 10/12/2022 <br />624 E 3rd St <br />10/12/22