ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF CALIFORNIA <br />ELECTRICAL CODE WILL BE INSTALLED AS REQUIRED <br />ALTERNATE POWER SOURCE PLACARD SHALL BE METALLIC OR PLASTIC, ENGRAVED, <br />OR MACHINE PRINTED LETTERS IN A CONTRASTING COLOR TO THE PLAQUE THIS <br />PLAQUE WILL BE ATTACHED BY POP RIVETS OR SCREWS OR OTHER APPROVED <br />METHOD IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT <br />PHOTOVOLTAIC DC CONDUCTORS SHALL BE LABELED."WARNING PHOTOVOLTAIC DC <br />POWER SOURCE" OR EQUIVALENT EVERY 10 FT AND KEPT MINIMUM 18 BELOW THE <br />ROOF SURFACE. PV DC CIRCUIT LABELS SHALL APPEAR ON EVERY SECTION OF THE <br />WIRING SYSTEM THAT IS SEPARTED BY ENCLOSURES. WALLS, PARTITIONS, CEILINGS, <br />OR FLOORS PV DC LABELS SHALL BE REFLECTIVE. SUITABLE FOR SURROUNDING <br />ENVIRONMENT, AND WHITE LETTERING ON A RED BACKGROUND [690 31(G)] <br />EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, <br />EQUIPMENTS, AND CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN <br />ACCORDANCE WITH 250.134 OR 250 136(A) REGARDLESS OF VOLTAGE. <br />EACH MODULE SHALL BE GROUNDED USING THE SUPPLIED CONNECTION POINT <br />IDENTIFIED ON THE MODULE AND THE MANUFACTURER'S INSTRUCTIONS. <br />IF THE EXISTING GROUNDING ELECTRODE SYSTEM CANNOT BE VERIFIED OR IS ONLY <br />METALLIC WATER PIPING. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A <br />SUPPLEMENTAL GROUNDING ELECTRODE <br />EQUIPMENT COMPLIES WITH RAPID SHUTDOWN REQUIREMENTS [690 12] <br />PLAQUES SHALL BE PLASTIC ENGRAVED IN A CONTRASTING COLOR TO THE PLAQUE. <br />NEC 705.10- ON MAIN SERVICE PANEL <br />CAUTION <br />POWER TO THIS BUILDING IS ALSO <br />SUPPLIED FROM THE FOLLOWING <br />SOURCES WITH DISCONNECTS <br />LOCATED AS SHOWN <br />MAI C , , p IC J <br />.0,,EXTEP <br />N8 T N8,81, 88, <br />801 E EIONSITANO AVE SANTA ANA CA 92707 <br />,IWARNINGELECTRIC SHOCK HAZARDTERMINALS ON BOTH THE LINE AND LOAD SIDES MAYBE ENERGIZED IN THE OPEN POSITION <br />NEC 690-13, 690.15- AT J-BOXES, ENCLOSURES, DISTRIBUTION <br />EQUIPMENT, AND AC/DC DISCONNECTS <br />WARNING <br />ELECTRICAL SHOCK HAZARD <br />TERMINALS ON BOTH THE LINE ANDLOAD SIDE MAY BE ENERGIZED IN THEOPEN POSITION <br />NEC 705,12(B)(2)(3)(b) - BY BREAKER AT DISTRIBUTION EQUIPMENT: <br />WARNING <br />POWER SOURCE OUTPUT CONNECTION <br />DO NOT RELOCATE THISOVERCURRENT DEVICE <br />NEC 705.12(B)(2)(3)(c) - BY BREAKER AT DISTRIBUTION EQUIPMENT: <br />WARNING <br />THIS EQUIPMENT FED BY MULTIPI F <br />SOURCES TOTAL RATING OF ALL <br />OVERCURRENT DEVICES. EXCLUDING MAIN <br />SUPPLY OVERCURRENT DEVICE.SHALL <br />NOT EXCEED AMPACITY OF BUSBAR <br />NEC 705.12(6)(3) - AT DISTRIBUTION EQUIPMENT <br />k WARNING k <br />MULTI - POWER SUPPLY <br />SOURCES INCLUDE <br />UTILITY GRID, PV SOLAR <br />NEC 690.56 - WITHIN 3FT OF SERVICE DISCONNECT. <br />1690 961C1)1101 YELLOW WITH BLACK LETTERING' <br />SOLAR PV SYSTEM EQUIPPED <br />WITH RAPID SHUTDOWN <br />TJRN RAPID SHUTDOWNSWITCH TO THE "OFF'POSITION TO SHUT DOWN PVSYSTEM AND REDUCE-SHOCKHAZARD IN ARRAY <br />NEC 690.56- ON RAPID SHUTDOWN DISCONNECT <br />(690 5610 RED WITH WHITE LETTERING) <br />i RAPID SHUTDOWN SWITCH FOR <br />SOLAR PV SYSTEM <br />cotonytucmotoormw 1 <br />LOCATION; MAIN PANEL <br />NEC 705.12.6.3 <br />WARNING <br />DUAL POWER SOURCE <br />SECOND SOURCE IS PHOTOVOLTAIC SYSTEM <br />RATED AC OUTPUT CURRENT:15.83 AMPS ACNORMAL OPERATING VOLTAGE·240 VOILS <br />_k WARNING k <br />TURN OFF PHOTOVOLTAIC i <br />AC DISCONNECT PRIOR TO <br />WORKING INSIE PANEL <br />PHOTOVOLTAIC SYSTEM <br />EQUIPPED WITH <br />RAPID SHUTDOWN <br />NEC 690.13, 690.15 - ON AC/DC DISCONNECT <br />NEC 690.53, 690 54 -ON AC/DC DISCONNECT <br />AC PHOTOVOLTAIC DISCONNECT <br />NEC 690.54 -ON AC DISCONNECT <br />AC PHOTOVOLTAIC DISCONNECT_ <br />OUTPUT CURRENT 25.7A <br />OPERATING VOLTAGE 240V <br />· 1 <br />W wu <br />· V) <br />co <br />co < Al: <br />0 (7) <br />O <br />> <br />O 0-- <br />0 <br />oa. c>o z <br />(N <br />Page <br />06 OF 11 <br />;27 <br />801 E Borchard <br />Ave04/13/22