G <br />EXISTING GROUNDING <br />ELECTRODE SYSTEM <br />N <br />(E) 200A-2P <br />(N) 40A-2P <br />(E) 200A MAIN SERVICE PANEL <br />(E) 200A / 2P MAIN BREAKER <br />(E) LOADS <br />4 <br />INTERCONNECTION NOTES: <br />1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE DETERMINED IN ACCORDANCE WITH [CEC 705.12], AND [CEC 690.64]. <br />3. GROUND FAULT PROTECTION IN ACCORDANCE WITH [CEC 215.9], [CEC 230.95] AND [CEC 690.5] <br />4. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. <br />5. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUSBAR RELATIVE TO THE MAIN BREAKER. <br />DISCONNECT NOTES <br />1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING LIVE ARE <br />CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) <br />2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH <br />N <br />G <br />BRANCH CIRCUIT (1): <br />12 MODULES <br />NEMA 3 <br />JUNCTION BOX <br />BRANCH CIRCUIT (2): <br />12 MODULES <br />DC <br />AC <br />DC <br />AC <br />DC <br />AC <br />DC <br />AC <br />DC <br />AC <br />DC <br />AC <br />1 2 <br />1 2 3 <br />JUNCTION <br />BOX <br />JUNCTION <br />BOX <br />(N) ENVOY <br />BREAKER <br />ENPHASE IQ7PLUS-72-2-US <br />MICROINVERTER(S) <br />THIS BREAKER MAY BE 10A OR 15A <br />AS PER MANUFACTURER, THIS <br />BREAKER ENERGIZES THE ENVOY <br />INSTALLED BY MANUFACTURER <br />(N) 125A <br />PV COMBINER <br />(2) 20A-2P <br />4 <br />PV AC DISCONNECT <br />VISIBLE, LOCKABLE, <br />LABELED, OPEN <br />60A, 240V, 2-POLE <br />M <br />(E) UTILITY METER <br />COMPLETE SOLAR <br />3000 EXECUTIVE PKWY,STE 504 <br />SAN RAMON, CA 94583 <br />LICENSE TYPE C10 <br />LICENSE # 961988 <br />PHONE # (877) 299-4943 <br />DESIGNED BY: ASHLEY HAHN <br />SITE INFORMATION: <br />MAX CONTINUOUS AC SYSTEM SIZE: <br />7.08 <br />DC SYSTEM SIZE: 8.76 <br />(24) CERTAINTEED - CT365HC11-06 <br />MODULES <br />(24) ENPHASE IQ7PLUS-72-2-US <br />INVERTER(S) <br />MOUNTING EQUIPMENT: <br />UNIRAC RM10 & UNIRAC RM10 <br />BALLAST SYSTEM <br />DEVEREAUX <br />SARIAH DEVEREAUX PROJECT <br />1417 S BROADWAY <br />SANTA ANA, CA 92707 <br />LAT , LONG: 33.7283283, <br />-117.8695679 <br />SINGLE LINE DIAGRAM <br />VISIBLE, LOCKABLE, <br />LABELED AC DISCONNECT <br />LOCATED WITHIN 10' <br />OF THE UTILITY METER <br />CALCULATIONS: <br />PER CEC 690.80, "WHERE A SINGLE OVERCURRENT DEVICE IS USED TO PROTECT A SET OF TWO OR <br />MORE PARALLEL-CONNECTED MODULE CIRCUITS, THE AMPACITY OF EACH OF THE MODULE <br />INTERCONNECTION CONDUCTORS SHALL NOT BE LESS THAN THE SUM OF THE RATING OF THE SINGLE <br />FUSE PLUS 125 PERCENT OF THE SHORT-CIRCUIT CURRENT FORM THE OTHER PARALLEL-CONNECTED <br />MODULES." <br />MODULE COUNT(24) * MICROINVERTER MAX OUTPUT CURRENT(1.21) * (1.25) = 36.30A < 40A <br />DATE:May 24, 2022 <br />Wire Tag <br /># <br />1 (1) 12 - 2 TC - ER, THWN-2, COPPER,(OR CODE APPROVED EQUIVALENT), (1) 6 AWG BARE, COPPER (GROUND) <br />2 (1) 10 AWG THWN - 2, OR THHN, COPPER - (POSITIVE),(1) 10 AWG THWN - 2, OR THHN, COPPER - (NEGATIVE),(1) 10 AWG THHN/THWN, COPPER - (GROUND),(1) 3/4"EMT <br /> (OR CODE APPROVED EQUIVALENT) <br />3 (2)10 AWG THHN/THWN-2,COPPER -(L1), (2)10 AWG THHN/THWN-2,COPPER -(L2), (1) 10 AWG THHN/THWN-2 (GROUND), CONDUIT: 3/4" EMT (OR CODE APPROVED EQUIVALENT) <br />4 (1) 8 AWG THWN-2 COPPER - (L1), (1) 8 AWG THWN-2 COPPER - (L2), (1) 8 AWG THWN-2 COPPER - (NEUTRAL), (1) 10 AWG THWN-2 COPPER - (GROUND),(1) CONDUIT: 3/4" EMT <br />(OR CODE APPROVED EQUIVALENT) <br />String1:12 <br />String2:12 <br />String3: <br />String4: <br />String5: <br />String6: <br />Scope of Work: <br />(24) CERTAINTEED - CT365HC11-06 <br />(24) ENPHASE IQ7PLUS-72-2-US INVERTER(S) <br />PV-6.0 <br />COMPLETE <br />SOLAR <br />REVIEWED BY: CT <br />1417 S Broadway - <br />101110019 & <br />2017587207/18/22