<br />LIGHTING PLAN NOTES
<br />1. ALL LUMINAIRES SHALL BE HIGH-EFFICACY IN
<br />ACCORDANCE WITH CBEES TABLE 150.0-A
<br />2. ALL LED LUMINAIRES AND LAMPS SHALL BE
<br />MARKED "JA8-2016" AND LISTED IN THE CALIFORNIA
<br />ENERGY COMMISSION DATABASE AT
<br />HTTPS://CACERTAPPLIANCES.ENERGY.CA.GOV/PAG
<br />ES/ APPLIANCESEARCH.ASPX
<br />3. ALL RECESSED DOWNLIGHT AND ENCLOSED
<br />LUMINAIRES SHALL BE MARKED "JA8-2016-E" AND
<br />LISTED IN THE CALIFORNIA ENERGY COMMISSION
<br />DATABSE AT
<br />HTTPS://CACERTAPPLIANCES.ENERGY.CA.GOV/PAG
<br />ES/APPLIANCESEARCH.ASPX
<br />4. RECESSED DOWNLIGHT LUMINAIRES IN CEILINGS
<br />SHALL NOT BE SCREW-BASED
<br />5. BATHROOMS, GARAGES, LAUNDRY ROOMS, AND
<br />UTILITY ROOMS: AT LEAST ONE LUMINAIRE IN EACH
<br />SPACE SHALL BE CONTROLLED BY A VACANCY
<br />SENSOR
<br />6. ALL LUMINAIRES REQUIRING "JA8-2016" OR
<br />"JA8-2016-E" MARKING SHALL BE CONTROLLED BY A
<br />DIMMER OR VACANCY SENSOR. EXCEPTION:
<br />CLOSETS LESS THAN 70 S.F. & HALLWAYS
<br />7. OUTDOOR LIGHTING PERMANENTLY MOUNTED TO
<br />BUILDINGS SHALL BE CONTROLLED BY ONE OF THE
<br />FOLLOWING:
<br />-PHOTOCONTROL AND MOTION SENSOR
<br />-PHOTOCONTROL AND AUTOMATIC TIME-SWITCH
<br />CONTROL
<br />-ASTRONOMICAL TIME CLOCK
<br />-ENERGY MANAGEMENT CONTROL SYSTEM PER
<br />CBEES 150.0(K)3AIIIC
<br />SOLAR READY KEY NOTES
<br />1. THE MAIN ELECTRICAL SERVICE PANEL SHALL NOT
<br />BE OF A TYPE WITH A CENTER-FED MAIN CIRCUIT
<br />BREAKER AND SHALL INCLUDE RESERVED SPACE
<br />ALLOWING FOR INSTALLATION OF DOUBLE-POLE
<br />CIRCUIT BREAKERS FOR A FUTURE SOLAR
<br />PHOTOVOLTAIC SYSTEM. SUCH RESERVED SPACE
<br />SHALL BE POSITIONED AT THE OPPOSITE (LOAD)
<br />END FROM THE INPUT FEEDER OR MAIN CIRCUIT
<br />BREAKER LOCATION. THE RESERVED SPACE SHALL
<br />BE PERMANENTLY AND VISIBLY MARKED AS "FOR
<br />FUTURE SOLAR PHOTOVOLTAIC"
<br />2. APPROVED MINIMUM 4-INCH SQUARE ELECTRICAL
<br />JUNCTION BOX LOCATED WITHIN 72 INCHES
<br />HORIZONTALLY AND 12 INCHES VERTICAL OF MAIN
<br />ELECTRICAL SERVICE PANEL
<br />3. MINIMUM 1 INCH DIAMETER LISTED ELECTRICAL
<br />METALLIC RACEWAY ORIGINATING AT READILY
<br />ACCESSIBLE ATTIC LOCATION WITH PROXIMITY TO
<br />SOLAR ZONE AREA AND TERMINATING AT THE
<br />REQUIRED ELECTRICAL JUNCTION BOX
<br />4. MINIMUM 1 INCH DIAMETER LISTED ELECTRICAL
<br />METALLIC RACEWAY ORIGINATING AT THE
<br />REQUIRED ELECTRICAL JUNCTION BOX AND
<br />TERMINATING AT THE MAIN ELECTRICAL SERVICE
<br />PANEL ELECTRICAL JUNCTION BOX AND SEGMENT
<br />OF METALLIC
<br />5. RACEWAY IN THE ATTIC SHALL BE PERMANENTLY
<br />AND VISIBLY MARKED AS "FOR FUTURE SOLAR
<br />PHOTOVOLTAIC"
<br />6. PV SIZE (KWdc) TO BE. DESIGN & CALCULATIONS TO
<br />BE PROVIDE BY OTHERS
<br />UTILITY PLAN NOTES
<br />1. LOCAL EXHAUST FANS TO EXTERIOR TO PROVIDE MINIMUM 50 CFM
<br />INTERMITTENT OR 20 CFM CONTINUOUS VENTILATION.
<br />2. SMOKE DETECTORS TO BE INTERCONNECTED PER CRC R314.4 AND
<br />HARD-WIRED WITH BATTERY BACK-UP PER CRC R314.6
<br />3. CARBON MONOXIDE ALARMS TO BE INTERCONNECTED PER CRC
<br />R315.7 AND HARD-WIRED WITH BATTERY BACK-UP PER CRC R315.5
<br />4. 4" Ø DRYER VENT WITH MAXIMUM 14 FOOT COMBINED HORIZONTAL
<br />AND VERTICAL LENGTH WITH TWO 90 DEGREE ELBOWS.
<br />5. A MECHANICAL EXHAUST VENTILATION SYSTEM, SUPPLY
<br />VENTILATION SYSTEM, OR COMBINATION THEREOF SHALL BE
<br />INSTALLED FOR EACH DWELLING UNIT TO PROVIDE WHOLE-
<br />BUILDING VENTILATION WITH OUTDOOR AIR IN COMPLIANCE WITH
<br />ASHRAE STANDARD 62.2 AS ADOPTED BY THE CALIFORNIA ENERGY
<br />COMMISSION.
<br />6. AN INTERMITTENTLY OR CONTINUOUSLY OPERATING LOCAL
<br />MECHANICAL EXHAUST VENTILATION SYSTEM SHALL BE INSTALLED
<br />IN EACH BATHROOM WITH A BATHTUB, SHOWER, OR SIMILAR
<br />MOISTURE SOURCE AND IN EACH KITCHEN IN COMPLIANCE WITH
<br />ASHRAE STANDARD 62.2 AS ADOPTED BY THE CALIFORNIA ENERGY
<br />COMMISSION. INTERMITTENT LOCAL EXHAUST VENTILATION
<br />AIRFLOW RATES SHALL BE 50 CFM IN BATHROOMS AND 100 CFM IN
<br />KITCHENS. CONTINUOUS LOCAL EXHAUST VENTILATION AIRFLOW
<br />RATES SHALL BE 20 CFM IN BATHROOMS AND 5 AIR CHANGES PER
<br />HOUR IN KITCHENS BASED ON KITCHEN VOLUME.
<br />7. WATER HEATER OR FURNACE SHALL BE A DIRECT-VENT APPLIANCE
<br />8. LISTED GASKETED SㄩELF CLOSING DOOR REQUIRED FOR GAS FA)
<br />9. A HOOD ABOVE THE RANGE TOP A MINIMUM OF 30”ABOVE THE
<br />COOKING SURFACE. HOUSEHOLD COOKING APPLIANCES SHALL
<br />HAVE A VERTICAL CLEARANCE ABOVE THE COOKING TOP OF NOT
<br />LESS THAN 30 INCHES TO COMBUSTIBLE MATERIAL AND THE HOOD
<br />SHALL HAVE A 100 CFM EXHAUST WHICH VENTS DIRECTLY TO THE
<br />EXTERIOR OF THE ADU. (920.0, 922.3 CMC, ASHRAE 62.2)
<br />10. BATHROOM RECEPTACLES SHALL BE SERVED BY A 20-AMP
<br />CIRCUIT. THE CIRCUIT SHALL HAVE NO OTHER OUTLETS. THE
<br />CIRCUIT MAY SERVE OTHER BATHROOM RECEPTACLES. (CEC
<br />210.11 (C) (3))
<br />11. A MINIMUM OF 2–20-AMP CIRCUITS ARE REQUIRED TO SERVE THE
<br />KITCHEN COUNTERTOP OUTLETS. THESE CIRCUITS MAY ALSO
<br />SERVE THE PANTRY, BREAKFAST ROOM, DINING ROOM OR OTHER
<br />SIMILAR AREAS.
<br />12. ALL BRANCH CIRCUITS SUPPLYING OUTLETS OR DEVICES (SUCH AS
<br />LIGHTS AND SWITCHES) INSTALLED IN DWELLING UNIT KITCHENS,
<br />FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
<br />LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
<br />CLOSETS, HALLWAYS, LAUNDRY AREAS, OR SIMILAR ROOMS AND
<br />AREAS SHALL BE PROVIDED WITH ARC-FAULT CIRCUIT-
<br />INTERRUPTER (AFCI) PROTECTION. SEE CEC SECTION 210.12 (A)
<br />FOR PERMISSIBLE MEANS OF AFCI PROTECTION. (210.12 CEC)
<br />13. AT LEAST ONE GFCI AND AFCI RECEPTACLE SHALL BE INSTALLED IN
<br />AREAS DESIGNATED FOR THE INSTALLATION OF LAUNDRY
<br />EQUIPMENT ON A SEPARATE 20-AMP CIRCUIT WITH NO OTHER
<br />OUTLETS. (210.8(A)(10), 210.52 (F), 210.11 (C)(2), 210.12(A) CEC)
<br />14. INSTALL A LISTED RACEWAY TO ACCOMMODATE A DEDICATED
<br />208/240-VOLT BRANCH CIRCUIT. THE RACEWAY SHALL NOT BE LESS
<br />THAN TRADE SIZE 1 (NOMINAL 1-INCH INSIDE DIAMETER). THE
<br />RACEWAY SHALL ORIGINATE AT THE MAIN SERVICE OR SUBPANEL
<br />AND SHALL TERMINATE INTO A LISTED CABINET, BOX, OR OTHER
<br />ENCLOSURE IN CLOSE PROXIMITY TO THE PROPOSED LOCATION
<br />OF AN EV CHARGER. RACEWAYS ARE REQUIRED TO BE
<br />CONTINUOUS AT ENCLOSED, INACCESSIBLE OR CONCEALED
<br />AREAS AND SPACES. THE SERVICE PANEL AND/OR SUBPANEL
<br />SHALL PROVIDE CAPACITY TO INSTALL A 40-AMPERE MINIMUM
<br />DEDICATED BRANCH CIRCUIT AND SPACE(S) RESERVED TO PERMIT
<br />INSTALLATION OF A BRANCH CIRCUIT OVERCURRENT PROTECTIVE
<br />DEVICE. THE SERVICE PANEL OR SUB-PANEL CIRCUIT DIRECTORY
<br />SHALL IDENTIFY THE OVERCURRENT PROTECTIVE DEVICE
<br />SPACE(S) RESERVED FOR FUTURE EV CHARGING AS “EV CAPABLE”.
<br />THE RACEWAY TERMINATION LOCATION SHALL BE PERMANENTLY
<br />AND VISIBLY MARKED AS “EV CAPABLE”. (4.106.4, 4.106.4.1.1 CGC)
<br />PENDANT LIGHT FIXTURE
<br />ELECTRICAL LEGEND
<br />HIGH EFFICACY RECESSED LIGHT
<br />HIGH EFFICACY WALL MOUNT LIGHT
<br />SMOKE DETECTOR
<br />CARBON MONOXIDE ALARM
<br />SINGLE POLE SWITCH
<br />DUPLEX OUTLET
<br />FUEL GAS VALVE
<br />GFCI DUPLEX OUTLETGFCI
<br />FAN AND LIGHT COMBINATION
<br />HOSE BIBB
<br />EXHAUSET FAN
<br />IAQ FAN
<br />SWITCH W/MOTION SENSOR
<br />SWITCH W/VACANCY SENSOR
<br />SWITCH W/INTEGRAL PHOTOCONTROL
<br />THREE-WAY SWITCH3
<br />P
<br />VS
<br />MO
<br />SWITCH FOR IAQ FANWHF
<br />INDOOR AIR QUALITY (IAQ) CALCULATIONS
<br />LIVING AREA = 999 SQ.FT.
<br />BEDROOM # = 2
<br />VENTILATION REQUIRED = 999 / 100 + (2+1) X 7.5 = 32.5 CFM
<br />(1) MIN. 50 CFM EXHAUST FAN > 32.5 CFM
<br />8'-0" CEILING, TYP.
<br />GFCI
<br />GFCI
<br />GFCI
<br />GFCI
<br />GFCI
<br />VS
<br />MIN. 50 CFM EXHAUST FAN
<br />TO REMAIN ON DURING
<br />ALL HOURS THE HOUSE IS
<br />OCCUPIED
<br />GFCI
<br />AT LEAST ONE WALL
<br />SWITCHED-CONTROLLED
<br />LIGHTING OUTLET SHALL BE
<br />INSTALLED TO PROVIDE
<br />ILLUMINATION ON THE
<br />EXTERIOR SIDE OF
<br />OUTDOOR ENTRANCES OR
<br />EXITS WITH GRADE LEVEL
<br />ACCESS. (210.70(A)(2)(2)
<br />CEC)
<br />GFCI GFCI
<br />GFCI
<br />GFCI GFCI
<br />TANKLESS W/H
<br />GFCI
<br />GFCI
<br />GFCI
<br />HOOD ABOVE RANGE
<br />TOP A MINIMUM OF 30”
<br />ABOVE; HAVE A 100
<br />CFM EXHAUST WHICH
<br />VENTS DIRECTLY TO
<br />THE EXTERIOR
<br />3
<br />-ELECTRIC PANEL,
<br />MIN. 250 AMP BUSBAR
<br />RATING
<br />-RESERVED FOR THE
<br />INSTALLATION OF A
<br />DOUBLE POLE CIRCUIT
<br />BREAKER FOR THE
<br />FUTURE SOLAR
<br />ELECTRIC
<br />INSTALLATION. (CENC
<br />110.10 (B)B4(E))
<br />-RESERVED FOR
<br />FUTURE EV CHARGING
<br />AS “EV CAPABLE”
<br />(4.106.4, 4.106.4.1.1
<br />CGC)
<br />VS
<br />GFCI
<br />GFCI
<br />GFCI
<br />GFCI
<br />P- MO
<br />GARAGE
<br />LIVING ROOM
<br />STORAGE
<br />LAUNDRY
<br />CLOSET
<br />PANTRY
<br />KITCHEN
<br />BEDROOM #1
<br />BATH #1
<br />DINING
<br />GFCI
<br />WHF
<br />GFCI
<br />GFCI
<br />GFCI
<br />P- MO
<br />P- MO
<br />P- MO
<br />W.P.
<br />GFCI
<br />3
<br />ATTIC ACCESS
<br />22" X 36"
<br />GFCI
<br />VS VS
<br />GFCI
<br />7'-4" CEILING, TYP.
<br />ATTIC ACCESS DOOR
<br />ABOVE 22" X 36"
<br />ATTIC MOUNTED
<br />EQUIPMENT, EXACT
<br />LOCATION TBD
<br />SOLID FLOOR
<br />PATHWAY 24" WIDE
<br />MIN. FROM ACCESS
<br />DOOR TO EQUIPMENT
<br />30" X 30"
<br />WORKING AREA
<br />120-VOLT OUTLET
<br />& SWITCH
<br />S O
<br />LIGHT FIXTURE
<br />WATER HEATER SYSTEM NOTES
<br />1. SYSTEMS USING GAS OR PROPANE WATER HEATERS
<br />TO SERVE INDIVIDUAL DWELLING UNITS SHALL
<br />DESIGNATE A SPACE AT LEAST 2.5 FEET BY 2.5 FEET
<br />WIDE AND 7 FEET TALL SUITABLE FOR THE FUTURE
<br />INSTALLATION OF A HEAT PUMP WATER HEATER
<br />A. IF THE DESIGNATED SPACE IS WITHIN 3 FEET FROM
<br />THE WATER HEATER:
<br />I. A DEDICATED 125 VOLT, 20 AMP ELECTRICAL
<br />RECEPTACLE THAT IS CONNECTED TO THE ELECTRIC
<br />PANEL WITH A 120/240 VOLT 3 CONDUCTOR, 10 AWG
<br />COPPER BRANCH CIRCUIT, WITHIN 3 FEET FROM THE
<br />WATER HEATER.
<br />II. ISOLATE BOTH ENDS OF THE UNUSED CONDUCTOR.
<br />III. A RESERVED SINGLE POLE CIRCUIT BREAKER SPACE
<br />IN THE ELECTRICAL PANEL ADJACENT TO THE CIRCUIT
<br />BREAKER
<br />IV. A CONDENSATE DRAIN THAT ALLOWS NATURAL
<br />DRAINING OF THE WATER HEATER.
<br />B. IF THE DESIGNATED SPACE IS MORE THAN 3 FEET
<br />FROM THE WATER HEATER: SEE ADDITIONAL CODE
<br />REQUIREMENTS.
<br />(S) ENERGY STORAGE SYSTEMS (ESS) READY.
<br />ALL SINGLE-FAMILY RESIDENCES THAT INCLUDE ONE OR
<br />TWO DWELLING UNITS SHALL MEET THE FOLLOWING:
<br />1. AT LEAST ONE OF THE FOLLOWING SHALL BE
<br />PROVIDED:
<br />A. ESS READY INTERCONNECTION EQUIPMENT [AUTO
<br />TRANSFER SWITCH AND PANEL] WITH A MINIMUM
<br />BACKED-UP CAPACITY OF 60 AMPS AND A MINIMUM OF
<br />FOUR ESS-SUPPLIED BRANCH CIRCUITS, OR
<br /> B. A DEDICATED, MINIMUM 1Â RACEWAY FROM THE
<br />MAIN SERVICE TO A SUBPANEL THAT SUPPLIES THE
<br />BRANCH CIRCUITS IN SECTION 150.0(S)(2).
<br />2. A MINIMUM OF FOUR BRANCH CIRCUITS SHALL BE
<br />SUPPLIED BY THE ESS: THE REFRIGERATOR, ONE
<br />LIGHTING CIRCUIT SHALL BE LOCATED NEAR THE
<br />PRIMARY EGRESS, AND AT LEAST ONE CIRCUIT SHALL
<br />SUPPLY A SLEEPING ROOM RECEPTACLE OUTLET.
<br />3. THE MAIN PANELBOARD SHALL HAVE A MINIMUM
<br />BUSBAR RATING OF 225 AMPERES WITH SPACE TO
<br />INSTALL FUTURE ISOLATION EQUIPMENT/TRANSFER
<br />SWITCH WITHIN 3 FEET.
<br />(T) HEAT PUMP SPACE HEATER (FURNACE) READY.
<br />SYSTEMS USING GAS OR PROPANE FURNACE TO SERVE
<br />INDIVIDUAL DWELLING UNITS SHALL INCLUDE THE
<br />FOLLOWING:
<br />1. A DEDICATED 240 VOLT, MINIMUM 30A BRANCH CIRCUIT
<br />WIRING SHALL BE INSTALLED WITHIN 3 FEET FROM THE
<br />FURNACE FOR A FUTURE HEAT PUMP SPACE HEATER
<br />INSTALLATION.
<br />(U) ELECTRIC COOKTOP READY.
<br />SYSTEMS USING GAS OR PROPANE COOKTOP TO SERVE
<br />INDIVIDUAL DWELLING UNITS SHALL INCLUDE THE
<br />FOLLOWING:
<br />1. A DEDICATED 240 VOLT, MINIMUM 50A BRANCH CIRCUIT
<br />WIRING SHALL BE INSTALLED WITHIN 3 FEET FROM THE
<br />COOKTOP FOR A FUTURE ELECTRIC COOKTOP
<br />INSTALLATION.
<br />(V) ELECTRIC CLOTHES DRYER READY.
<br />CLOTHES DRYER LOCATIONS WITH GAS OR PROPANE
<br />PLUMBING TO SERVE INDIVIDUAL DWELLING UNITS SHALL
<br />INCLUDE THE FOLLOWING:
<br />1. A DEDICATED 240 VOLT, MINIMUM 30A BRANCH CIRCUIT
<br />WIRING SHALL BE INSTALLED WITHIN 3 FEET FROM THE
<br />CLOTHES DRYER LOCATION FOR A FUTURE ELECTRIC
<br />CLOTHES DRYER INSTALLATION.
<br />CO
<br />P
<br />Y
<br />R
<br />I
<br />G
<br />H
<br />T
<br />
<br />©
<br />
<br />W
<br />A
<br />N
<br />G
<br />T
<br />A
<br />S
<br />T
<br />I
<br />C
<br />
<br />A
<br />R
<br />C
<br />H
<br />D
<br />E
<br />I
<br />S
<br />G
<br />N
<br />
<br />L
<br />L
<br />C
<br />
<br />
<br />2
<br />0
<br />2
<br />3
<br />P R O J E C T C O D E:
<br />I S S U E D A T E:
<br />R E V I S I O N S
<br />S H E E T N U M B E R
<br />D R A W I N G S
<br />P R E P A R E D F O R :
<br />S H E E T N A M E
<br />1005 S. VIRLEE ST.
<br />SANTA ANA, CA 92704
<br />C:
<br />\
<br />U
<br />s
<br />e
<br />r
<br />s
<br />\
<br />A
<br />l
<br />a
<br />n
<br />
<br />L
<br />i
<br />\
<br />D
<br />e
<br />s
<br />k
<br />t
<br />o
<br />p
<br />\
<br />B
<br />u
<br />s
<br />i
<br />n
<br />e
<br />s
<br />s
<br />\
<br />A
<br />r
<br />c
<br />h
<br />i
<br />t
<br />e
<br />c
<br />t
<br />u
<br />r
<br />a
<br />l
<br />
<br />P
<br />r
<br />o
<br />je
<br />c
<br />t
<br />s
<br />\
<br />2
<br />0
<br />2
<br />3
<br />
<br />P
<br />r
<br />o
<br />j
<br />e
<br />c
<br />t
<br />s
<br />\
<br />0
<br />1
<br />4
<br />_
<br />M
<br />S
<br />A
<br />_
<br />M
<br />a
<br />i
<br />
<br />S
<br />a
<br />n
<br />t
<br />a
<br />A
<br />n
<br />a
<br />
<br />A
<br />D
<br />U
<br />\
<br />3
<br />_
<br />D
<br />r
<br />a
<br />w
<br />in
<br />g
<br />s
<br />\
<br />2
<br />_
<br />R
<br />e
<br />v
<br />i
<br />t
<br />\
<br />M
<br />S
<br />A
<br />_
<br />M
<br />a
<br />i
<br />
<br />S
<br />a
<br />n
<br />t
<br />a
<br />
<br />A
<br />n
<br />a
<br />
<br />A
<br />D
<br />U
<br />.
<br />r
<br />v
<br />t
<br />3/
<br />5
<br />/
<br />2
<br />0
<br />2
<br />4
<br />
<br />8
<br />:
<br />0
<br />2
<br />:
<br />3
<br />0
<br />
<br />P
<br />M
<br />MA
<br />I
<br />
<br />S
<br />A
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />
<br />A
<br />D
<br />U
<br />10
<br />0
<br />5
<br />
<br />S
<br />
<br />V
<br />I
<br />R
<br />L
<br />E
<br />E
<br />
<br />S
<br />T
<br />
<br />U
<br />N
<br />I
<br />T
<br />
<br />2
<br />SA
<br />N
<br />T
<br />A
<br />
<br />A
<br />N
<br />A
<br />,
<br />
<br />C
<br />A
<br />
<br />9
<br />2
<br />7
<br />0
<br />4
<br />10/09/2023
<br />CD / PERMIT
<br />A2.3
<br />ELECTRICAL
<br />PLAN
<br />ANGIE MAI
<br />23-014
<br />DATE NO. DESCRIPTION
<br />02/23/2024 1 BUILDING
<br />COMMENTS
<br />1/4" = 1'-0"1 FIRST FLOOR REFLECTED CEILING PLAN
<br />1/4" = 1'-0"2 SECOND FLOOR
<br />1/4" = 1'-0"3 ATTIC APPLIANCE DIAGRAM
<br />1
<br />1
<br />1
<br />1005 S Virlee St
<br />Unit# 28/26/2024
|