PHOTOVOLTAIC SYSTEM AC DISCONNECT
<br />RATED AC OPERATING CURRENT 32.4 AMP AC
<br />NOMINAL OPERATING VOLTAGE 240 VOLTS
<br />Project Information
<br />Salem Residence
<br />1230 W River Ln,
<br />Santa Ana, CA 92706
<br />SHEET INDEX
<br />PV-1 Plot Plan
<br />PV-2.1 Stringing
<br />PV-2.2 Single line diagram
<br />PV-3 Array Layout
<br />PV-4 Signage
<br />Sheet
<br /> 5-13 Additional Information
<br /> Data sheets,
<br /> Certifications...
<br />SOLAR SOURCE INC 2954 E 14TH
<br />ST, LONG BEACH, CA 90804 LIC#:
<br />925231, CLASS - C46, C10 Lisense
<br />Date 03/31/2023
<br />DUAL POWER SUPPLY
<br />SOURCES:
<br />UTILITY GRID
<br />AND
<br />PV SOLAR ELECTRIC SYSTEM
<br />(STICKER LOCATED
<br />NEXT RO MAIN BREAKER)
<br />175A
<br />10
<br />All system labels and warnings to be installed at the site
<br />and their locations in accordance with Article 690 of the
<br />2019 California Electric Code and the Fire Department
<br />having jurisdiction Guidelines. The following labeling
<br />requirements apply to the "Rapid Shutdown" equipment.
<br />690.56 Identification of Power Sources.
<br />(C) Facilities with Rapid Shutdown.
<br />Buildings or structures with both utility service and a PV
<br />system, complying with 690.12, shall have a permanent
<br />plaque or directory including the following wording:
<br />PHOTOVOLTAIC SYSTEM EQUIPPED WITH
<br />RAPID SHUTDOWN
<br />The plaque or directory shall be reflective, with all
<br />letters capitalized and having a minimum height of 9.5mm,
<br />in white on red background.
<br />Permanent directory or plaque providing location of service
<br />disconnecting means and photovoltaic system disconnecting means, if
<br />not located at the same location. Plaques shall be metal or plastic, with
<br />engraved or machine printed letters, or electro-photo plating, in a
<br />contrasting color to the plaque. Plaques shall be permanently
<br />attached to the equipment or in the required location using an approved
<br />method that is suitable to withstand the environment to which it is
<br />exposed. Plaques and signage shall meet legibility, defacement,
<br />exposure, and adhesion requirements of Underwriters Laboratories
<br />marking and labeling system 969(UL969).
<br />Plaques will have red background with white lettering.
<br />MARKINGS, LABELS, AND WIRING SIGNS
<br />A. Purpose: Provide emergency responders with appropriate warning
<br />and guidance with respect to isolating solar electric system.
<br />B. Main Service Disconnect
<br />1. Residential buildings - The marking shall be placed within the main
<br />service disconnect. The marking shall be placed outside cover if
<br />the main service disconnect is operable with the service panel
<br />closed.
<br />2. Commercial buildings - The marking shall be placed adjacent to
<br />the main service disconnect clearly visible from the location
<br />where the level is operated.
<br />3. Markings: Verbiage, Format, and Type of Material
<br />a. Verbiage: CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED
<br />b. Format: White lettering on a red background. Min 3/8" letter
<br />height. All letters capitalized. Arial or similar font, non bold.
<br />c. Material: Reflective, weather resistant material suitable for
<br />the environment (as per UL-969). Durable adhesive materials
<br />meet this requirement.
<br />C. Marking requirements on DC conduit, raceways, enclosures, cable
<br />assemblies, DC combiners, and junction boxes:
<br />1. Markings: Verbiage, Format, and Type of Material.
<br />a. Placement: Markings shall be placed every 10 feet on all interior
<br />and exterior DC conduits, raceways, enclosures, and cable
<br />assemblies, at turns, above and below penetrations, all DC
<br />combiners and junction boxes.
<br />b. Verbiage: CAUTION: SOLAR CIRCUIT (Note: the format and type
<br />of material shall adhere to "V. V-3b, c" of this requirement.)
<br />c. Inverters are not required to have caution markings.
<br />2. Marking is required on all interior and exterior DC conduit,
<br />raceways, enclosures, cable assemblies, and junction boxes,
<br />combiner boxes, and disconnects. CFC 605.11.1
<br />3. The materials used for marking shall be reflective, weather
<br />reflective, weather resistant materials suitable for the
<br />environment. Minimum 3/8" letter height; all upper case, Arial or
<br />similar font; Red background with white lettering. CFC 605.11.1
<br />4. Marking shall contain the words: WARNING: PHOTOVOLTAIC POWER
<br />SOURCE. CFC 605.11.1.2
<br />5. Marking shall be placed adjacent to the main service disconnect in
<br />a location clearly visible from the location where the disconnect
<br />is operated. CFC 605.11.1.3
<br />AC DISCONNECT
<br />if applicable
<br />SUB-PANEL
<br />if applicable
<br />PV SUB-PANEL
<br />if applicable
<br />DC DISCONNECT
<br />if applicable
<br />INVERTER
<br />if applicable
<br />J BOX
<br />PV ARRAY
<br />MAIN SERVICE PANEL
<br />STICKER MAP
<br />PV-4
<br />CODE REQUIRED
<br /> PV SIGNAGE
<br />1
<br />5
<br />6
<br />7
<br />4
<br />1
<br />4
<br />2
<br />3 4
<br />5 6
<br />8
<br />4
<br />5 6
<br />7
<br />5
<br />5 6
<br />7
<br />9
<br />1
<br />N
<br />FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY
<br />AND CONDUCTORS LEAVING THE ARRAY: SIGH TO
<br />BE LOCATED ON OR NO MORE THAN 3 FT AWAY
<br />FROM SERVICE DISCONNECTING MEANS TO WHICH
<br />THE PV SYSTEMS ARE CONNECTED AND SHALL
<br />INDICATE THE LOCATION OF ALL IDENTIFIED RAPID
<br />SHUTDOWN SWITCHES IF NOT AT THE SAME
<br />LOCATION. [CEC 690.56(C)(1)(A)]
<br />CAUTION
<br />POWER TO THIS BUILDING IS ALSO SUPPLIED FROM
<br />THE FOLLOWING SOURCES WITH PV EQUIPMENT LOCATED AS SHOWN
<br />MAIN SERVICE PANEL
<br />YOU ARE HERE
<br />SOLAR COMBINER PANEL
<br />10
<br />(UNLESS BUSBAR IS FULLY RATED) (NEC 705.12(D)(2)(3)(B) WHITE LETTERS WITH RED BACKGROUND)
<br />WARNING
<br />INVERTER OUTPUT CONNECTION. DO NOT
<br />RELOCATE THIS OVERCURRENT DEVICE.
<br />SOLAR ELECTRIC
<br />PV PANELS
<br />SOLAR PV SYSTEM EQUIPPED
<br />WITH RAPID SHUTDOWN
<br />TURN RAPID SHUTDOWN
<br />SWITCH ON THE
<br />"OFF" POSITION TO
<br />SHUTDOWN PV SYSTEM
<br />AND REDUCE
<br />SHOCK HAZARD
<br />IN ARRAY
<br />IFC 605.11.3.1(1) & 690.56(C)(1)(a)
<br />NEC 690.31(G)(3)(4) & NEC 690.13(G)(4)
<br />TO BE PLACED AT LEAST EVERY 10FT
<br />WHITE LETTERS WITH RED BACKGROUND
<br />WARNING
<br />PHOTOVOLTAIC POWER
<br />SOURCE
<br />ELECTRIC SHOCK HAZARD
<br />DO NOT TOUCH TERMINALS
<br />TERMINALS ON BOTH LINE AND
<br />LOAD SIDES MAY BE ENERGIZED IN
<br />THE OPEN POSITION
<br />WARNING2
<br />!
<br />NEC 690.17(E), CB
<br />BLACK OUTLINE WITH BLACK TEXT /
<br />WARNING IS IN
<br />BLACK TEXT AND ORANGE BACKGROUND
<br />NEC 690.56 C
<br />WHITE LETTERS WITH RED BACKGROUND
<br />PHOTOVOLTAIC SYSTEM
<br />EQUIPPED WITH RAPID
<br />SHUTDOWN
<br />2
<br />CAUTION:
<br />SOLAR ELECTRIC SYSTEM CONNECTED
<br />NEC 690.15, 690.13(B)
<br />BLACK TEXT WITH YELLOW BACKGROUND
<br />2
<br />ELECTRIC SHOCK HAZARD.
<br />IF GROUND FAULT IS INDICATED,
<br />NORMALLY GROUNDED
<br />CONDUCTORS MAY BE
<br />UNGROUNDED AND ENERGIZED
<br />WARNING!!
<br />NEC 690.54
<br />WHITE LETTERS WITH RED BACKGROUND
<br />8
<br />PV SUB PANEL ONLY
<br />NEC 690.17(E)
<br />BLACK OUTLINE WITH BLACK TEXT / WARNING IS IN
<br />BLACK TEXT AND ORANGE BACKGROUND
<br />690.56(C)(3) Rapid Shutdown Switch. A rapid
<br />shutdown switch shall have a label located on or
<br />no more than 1 m (3 ft) from the switch that
<br />includes the following wording
<br />9
<br />11
<br />11
<br />11
<br />W River Ln
<br />1230 W River Ln
<br />12/15/22
|