Laserfiche WebLink
5322SHUDWLRQ <br />7KHIROORZLQJDFWLRQVRFFXULPPHGLDWHO\XSRQ532FLUFXLWDFWLYDWLRQ <br />• The SunVault operating mode switches to a standby state, which instantly ceases <br />SunVault power export to the premises wiring system (i.e., emergency shutdown) <br />[706.15(B)]. <br />• The Hub+ microgrid interconnect device (MID) contactor opens, which instantly <br />isolates source voltage output to the Hub+ generation pan; this then rapidly shuts down <br />all of the connected ACPV source circuits [690.12(C)]. <br />RPO Switch Compliance with NEC Requirements <br />RPO switch <br />Important! The RPO switch is not a substitute for the AC and DC breakers at the site. <br />• The RPO is a manual initiation device that can be used for both system rapid <br />shutdown and ESS emergency shutdown. <br />• The OFF position of the RPO button performs the ESS emergency shutdown. <br />• The RPO switch clearly indicates whether it is in the OFF or ON position. <br />• The RPO enclosure includes a transparent cover that provides protection from <br />inadvertent manual activation and deactivation. <br />• The RPO protective enclosure has a lockable cover, which ensures the RPO switch <br />remains in the open position. <br />Note: The provisions for locking the RPO always remain in place with or without a lock <br />being installed. <br />1402 W Meriday Ln - <br />201816051/10/2024