Laserfiche WebLink
TECHNICAL BRIEF <br />© 2015 Enphase Energy Inc. All rights reserved. January 20151 <br />NEC 2014 — Enphase System Code Compliance <br />Overview <br />This technical brief discusses new NEC 2014 requirements that apply to Enphase Microinverter Systems. <br />It is useful for installers, electricians, and electrical inspectors or authorities having jurisdiction (AHJs) in <br />understanding how code-compliance is handled where NEC 2014 is adopted. Main topics discussed in <br />this document are: <br />• NEC 2014 Section 690.12 Rapid Shutdown of PV Systems on Buildings <br />• NEC 2014 Section 705.12 Point of Connection <br />• NEC 2014 Section 690.11 DC Arc-Fault Circuit Protection <br />NEC 2014 Section 690.12 Rapid Shutdown of PV Systems on <br />Buildings <br />Enphase Microinverter Systems fully meet the rapid shutdown requirement without the need to install <br />additional electrical equipment. Properly labeling the PV system power source and rapid shutdown ability <br />is required per NEC Section 690.56 (B) and (C). <br />Solar electric PV systems with Enphase Microinverters have one utility-interactive inverter directly <br />underneath each solar module, converting low voltage DC to utility grid-compliant AC. When the utility <br />grid is available and the sun is shining, each microinverter verifies that the utility grid is operating within <br />the IEEE 1547 requirements. Only then does it export AC power into the electric service for use by loads <br />onsite or export power to the utility grid for others to use. When the utility grid has a failure, or the PV <br />system AC circuits are disconnected from the utility service via an AC breaker, AC disconnect, or removal <br />of the solar or main utility service meter, the microinverters stop producing AC power in fewer than six AC <br />cycles. Enphase Microinverters are not capable of operating as an AC voltage source. This means that <br />without an AC utility source, Enphase Microinverters are not able to energize connected wiring and no AC <br />voltage or current can be injected into the inverter output circuits or the grid. <br />When the AC utility source is removed from the inverter output circuits via any means, such as an AC <br />breaker, AC disconnect or removal of the solar or main utility service meter, this equipment performs the <br />rapid shutdown function per 690.12. With an Enphase Microinverter System this shutdown occurs well <br />within the 690.12 required 10 seconds, and there are no oth er conductors energized more than 1.5 m (5 <br />ft) in length inside a building or more than 3 m (10 ft) from a PV array. <br />Code Reference <br />690.12 Rapid Shutdown of PV Systems on Buildings. PV system circuits installed on or in <br />buildings shall include a rapid shutdown function that controls specific conductors in accordance <br />with 690.12(1) through (5) as follows. <br />(1) Requirements for controlled conductors shall apply only to PV system conductors of <br />more than 1.5 m (5 ft) in length inside a building, or more than 3 m (10 ft) from a PV <br />array. <br />(2) Controlled conductors shall be limited to not more than 30 volts and 240 volt-amperes <br />within 10 seconds of rapid shutdown initiation. <br />(3) Voltage and power shall be measured between any two conductors and between any <br />conductor and ground. <br />(4) The rapid shutdown initiation methods shall be labeled in accordance with 690.56(B). <br />(5) Equipment that performs the rapid shutdown shall be listed and identified. <br />1338 N Custer St <br />05/01/23