PUMP <br />TAG LOCATION MANUFACTURER & <br />MODEL No.SERVING GPM HEAD <br />(ft)RPM BHP HP MOTOR <br />ENCL. <br />PUMP <br />EFF % <br />PUMP <br />DUTY %VOLTAGE EMERGENCY <br />POWER VIB. ISO WEIGHT <br />(lbs) <br />VFD <br />(Y/N) <br />PRESSURE <br />RATING <br />(psi) <br />REMARKS <br />HHWP-1 ROOF BELL & GOSSETT <br />E-1510 1.5AD B-1 80 50 1734 1.48 2 -68.2 100 230V-3ɸ N N 173 Y 175 - <br />HHWP-2 ROOF BELL & GOSSETT <br />E-1510 1.5AD B-1 80 50 1734 1.48 2 -68.2 100 230V-3ɸ N N 173 Y 175 - <br />AIR SEPARATOR <br />TAG LOCATION MANUFACTURER & <br />MODEL No.SERVING GPM <br />PRESSURE <br />DROP <br />(ft w.c.) <br />INLET / <br />OUTLET <br />PRESSURE <br />RATING <br />(psig) <br />WEIGHT <br />(lbs)REMARKS <br />AS-1 ROOF BELL & GOSSETT <br />RL-2-1/2N B-1 80 1 2-1/2"125 108 - <br />CHEMICAL POT FEEDER <br />TAG LOCATION MANUFACTURER & <br />MODEL No.VOLUME (gal)WEIGHT <br />(lbs)REMARKS <br />CPF-1 ROOF WINGERT <br />5HD 5 37 - <br />MECHANICAL <br />MANDATORY MEASURES <br />Equipment Efficiencies (§110.2) <br />Ventilation (§120.1) <br />Controls (§120.2) <br />Pipe Insulation (§120.3) <br />Duct Construction and Insulation (§120.4) <br />Acceptance Tests (§120.5 and Reference Nonresidential Appendix NA7) <br />MECHANICAL EQUIPMENT INSTALLED IN A BUILDING SUBJECT TO THESE REGULATIONS MUST BE CERTIFIED AS <br />MEETING CERTAIN MINIMUM EFFICIENCY. THESE REQUIREMENTS ARE CONTAINED IN §110.2. THE AFUE, COP, EER, IPLV, <br />COMBUSTION EFFICIENCY, AND THERMAL EFFICIENCY VALUES OF ALL EQUIPMENT MUST BE DETERMINED USING THE <br />APPLICABLE TEST METHOD SPECIFIED IN THE STANDARDS. <br />BUILDINGS, OTHER THAN HEALTHCARE FACILITIES, SHALL COMPLY WITH THE APPLICABLE DEMAND RESPONSIVE <br />CONTROL REQUIREMENTS OF SECTION 110.12(a) THRU 110.12(e). <br />ALL GAS AND OIL FIRED AIR FURNACES WITH INPUT RATING >225,000 BTU/HR SHALL HAVE AN INTERMITTENT IGNITION <br />OR INTERRUPTED DEVICE (IDD), AND HAVE EITHER POWER VENTING OR A FLUE DAMPER. <br />ALL OCCUPIABLE SPACES IN HIGH-RISE RESIDENTIAL, HOTEL/MOTEL AND NONRESIDENTIAL BUILDINGS OTHER THAN <br />HEALTHCARE FACILITIES SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF SECTION 120.1(a) THROUGH 120.1(g). <br />HEALTHCARE FACILITIES SHALL BE VENTILATED IN ACCORDANCE WITH CHAPTER 4 OF THE CALIFORNIA MECHANICAL <br />CODE. <br />THE OUTDOOR AIR-VENTILATION RATE AND AIR-DISTRIBUTION ASSUMPTIONS MADE IN THE DESIGN OF THE VENTILATING <br />SYSTEM SHALL BE CLEARLY IDENTIFIED ON THE BUILDING PLANS REQUIRED BY §10-103 OF TITLE 24, PART 1. <br />THERMOSTATIC CONTROLS FOR EACH ZONE. THE SUPPLY OF HEATING AND COOLING ENERGY TO EACH <br />SPACE-CONDITIONING ZONE OR DWELLING UNIT SHALL BE CONTROLLED BY AN INDIVIDUAL THERMOSTATIC CONTROL <br />THAT RESPONDS TO TEMPERATURE WITHIN THE ZONE AND THAT MEETS THE APPLICABLE REQUIREMENTS OF <br />SECTION 120.2(b). <br />CRITERIA FOR ZONAL THERMOSTATIC CONTROLS. THE INDIVIDUAL THERMOSTATIC CONTROLS REQUIRED BY <br />SECTION 120.2(a) SHALL MEET THE FOLLOWING REQUIREMENTS: FOR HEATING SHALL BE CAPABLE OF BEING SET, <br />LOCALLY OR REMOTELY, DOWN TO 55°F OR LOWER, OR FOR COOLING IT SHALL BE CAPABLE OF BEING SET, LOCALLY OR <br />REMOTELY, UP TO 85°F OR HIGHER. <br />FOR HOTEL/MOTEL GUEST ROOM THERMOSTATS; SHALL HAVE: NUMERIC TEMPERATURE SETPOINTS IN °F; AND <br />SETPOINT STOPS ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, SUCH THAT OCCUPANTS CANNOT ADJUST MORE <br />THAN +/-5°F. THERMOSTATS SHALL ALSO COMPLY WITH SECTION 110.2(c). <br />HEAT PUMP CONTROLS. ALL HEAT PUMPS WITH SUPPLEMENTARY ELECTRIC RESISTANCE HEATERS SHALL BE <br />INSTALLED WITH CONTROLS THAT COMPLY WITH SECTION 110.2(b). <br />DAMPERS FOR AIR SUPPLY AND EXHAUST EQUIPMENT. OUTDOOR AIR SUPPLY AND EXHAUST EQUIPMENT SHALL BE <br />INSTALLED WITH DAMPERS THAT AUTOMATICALLY CLOSE UPON FAN SHUTDOWN. <br />ISOLATION AREA DEVICES. EACH SPACE-CONDITIONING SYSTEM SERVING MULTIPLE ZONES WITH A COMBINED <br />CONDITIONED FLOOR AREA OF MORE THAN 25,000 SQUARE FEET SHALL BE DESIGNED, INSTALLED, AND CONTROLLED <br />TO SERVE ISOLATION AREAS. <br />THE PIPING FOR ALL SPACE-CONDITIONING AND SERVICE WATER-HEATING SYSTEMS WITH FLUID TEMPERATURES <br />LISTED IN TABLE 120.3-A SHALL INSTALL THE AMOUNT OF INSULATION SPECIFIED. <br />ALL AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS, INCLUDING, BUT NOT LIMITED TO, BUILDING CAVITIES, <br />MECHANICAL CLOSETS, AIR-HANDLER BOXES AND SUPPORT PLATFORMS USED AS DUCTS OR PLENUMS, SHALL BE <br />INSTALLED, SEALED AND INSULATED TO MEET THE REQUIREMENTS OF THE CMC SECTIONS 601, 602, 603, 604, 605, <br />AND SMACNA-006-2006 HVAC DUCT CONSTRUCTION STANDARDS METAL & FLEXIBLE, 3RD EDITION. <br />BEFORE AN OCCUPANCY PERMIT IS GRANTED THE CERTIFICATE OF ACCEPTANCE SHALL BE SUBMITTED TO THE <br />ENFORCEMENT AGENCY THAT CERTIFIES THAT THE EQUIPMENT AND SYSTEMS MEET THE ACCEPTANCE REQUIREMENTS. <br />2022 <br />ALL NEWLY INSTALLED AIR HANDLER UNITS GREATER THAN 33,000 BTU/HR WITH AN AIR ECONOMIZER SHALL HAVE <br />FAULT DETECTION AND DIAGNOSTICS. <br />DDC CONTROLS TO ZONE SHALL BE PROVIDED AS SPECIFIED BY TABLE 120.2-A. SPACE CONDITIONING SYSTEMS <br />WITH DDC CONTROLS SHALL HAVE OPTIMUM START/STOP CONTROLS. <br />Nonresidential Building Commissioning (§120.8) <br />NEW NONRESIDENTIAL BUILDINGS <10,000 SQ. FT. SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF <br />SECTIONS 120.8(a) THRU 120.8(i) IN THE BUILDING DESIGN AND CONSTRUCTION PROCESSES. <br />Commercial Boilers (§120.9) <br />ALL NEW BOILERS OVER 2,500,000 BTU/HR SHALL COMPLY WITH COMBUSTION AIR AND COMBUSTION AIR FAN <br />REQUIREMENTS. <br />OCCUPANCY SENSING ZONE CONTROLS. WHERE THE SYSTEM PROVIDING SPACE CONDITIONING ALSO PROVIDES <br />THE VENTILATION REQUIRED BY SECTION 120.1 AND INCLUDES OCCUPANT SENSOR VENTILATION CONTROL AS <br />SPECIFIED IN SECTION 120.1(d)5, THE OCCUPANT SENSING ZONE CONTROLS SHALL ADDITIONALLY COMPLY WITH <br />THE FOLLOWING: PLACE THE ZONE IN OCCUPIED STANDBY MODE WHEN ALL ROOMS SERVED BY THE ZONE ARE <br />UNOCCUPIED FOR MORE THAN 5 MINUTES AND RESET COOLING AND HEATING SETPOINTS BY 2°F (0.5°F FOR DDC <br />SYSTEMS), AND SHUTOFF AIRFLOW TO THE ZONE WHEN IN DEADBAND. <br />Demand Management (§110.12, 120.1(d)3) <br />ALL DEMAND RESPONSIVE CONTROLS SHALL BE CERTIFIED OPEN ADR 2.0A OR B VIRTUAL END NODE. DEMAND <br />RESPONSIVE CONTROL THERMOSTATS SHALL COMPLY WITH REFERENCE JOINT APPENDIX 5 (JA5). <br />NONRESIDENTIAL HVAC SYSTEMS WITH DDC TO THE ZONE LEVEL SHALL ALLOW CENTRALIZED DEMAND SHED FOR <br />NON-CRITICAL ZONES AS FOLLOWS: INCREASE COOLING SETPOINT AND DECREASE HEATING SETPOINT BY MIN. 4°F, <br />ALLOW FOR REMOTE RESET TO ORIGINAL SETPOINTS, ADJUSTABLE RATE OF CHANGE FOR TEMPERATURE INCREASE, <br />DECREASE AND RESET, DISABLED OR MANUAL CONTROL BY AUTHORIZED FACILITY OPERATOR, AUTOMATIC DEMAND <br />SHED CONTROL UPON RECEIPT OF DEMAND RESPONSE SIGNAL. <br />A CRITICAL ZONE IS DEFINED AS A ZONE SERVING A PROCESS WHERE RESET OF THE ZONE TEMPERATURE DURING A <br />DEMAND SHED EVENT MIGHT DISRUPT THE PROCESS, INCLUDING BUT NOT LIMITED TO COMPUTER ROOMS, DATA <br />CENTERS, TELECOM, PRIVATE BRANCH EXCHANGE ROOMS AND LABORATORIES. <br />PROVIDE MIN. 2" DEPTH MERV 13 FILTRATION TO SYSTEMS SUPPLYING AIR THROUGH DUCTWORK EXCEEDING 10FT IN <br />LENGTH, MECHANICAL SUPPLY-ONLY VENTILATION SYSTEMS, OR SUPPLY SIDE OF MECHANICAL BALANCED VENTILATION <br />SYSTEMS. <br />DEMAND VENTILATION CONTROLS COMPLYING WITH 120.1(d)4 ARE REQUIRED FOR A SPACE WITH A DESIGN OCCUPANT <br />DENSITY EQUAL TO 40 SQ. FT. PER PERSON OR LESS IF THE VENTILATION SYSTEM SERVING THE SPACE HAS EITHER <br />AN AIR ECONOMIZER, MODULATING OSA CONTROL OR DESIGN OUTDOOR AIRFLOW RATE GREATER THAN 3,000 CFM. <br />OCCUPANT SENSOR VENTILATION CONTROL DEVICES WHEN REQUIRED BY SECTION 120.2(e)3 SHALL BE USED TO <br />REDUCE THE RATE OF OUTDOOR AIR FLOW WHEN OCCUPANTS ARE NOT PRESENT, IN ACCORDANCE WITH 120.1(d)5. <br />DUCTING FOR ZONAL HEATING AND COOLING UNITS. WHERE A RETURN PLENUM IS USED TO DISTRIBUTE OUTDOOR AIR <br />TO A ZONAL HEATING OR COOLING UNIT WHICH THEN SUPPLIES THE AIR TO A SPACE IN ORDER TO MEET THE <br />REQUIREMENTS OF SECTION 120.1(c)3, THE OUTDOOR AIR SHALL BE DUCTED TO DISCHARGE EITHER: WITHIN 5 FEET OF <br />THE UNIT; OR WITHIN 15 FEET OF THE UNIT, SUBSTANTIALLY TOWARD THE UNIT, AND AT A VELOCITY NOT LESS THAN <br />500 FEET PER MINUTE. <br />NONRESIDENTIAL SYSTEMS NATURALLY VENTILATED SPACES SHALL BE DESIGNED IN ACCORDANCE WITH 120.1(c)2A <br />THROUGH 120.1(c)2C AND SHALL ALSO INCLUDE MECHANICAL VENTILATION IN ACCORDANCE WITH 120.1(c)3. <br />DESIGN AND CONTROL REQUIREMENTS FOR QUANTITIES OF OUTDOOR AIR. ALL MECHANICAL VENTILATION AND <br />SPACE-CONDITIONING SYSTEMS SHALL BE DESIGNED WITH AND HAVE INSTALLED DUCTWORK, DAMPERS, AND <br />CONTROLS TO ALLOW OUTSIDE AIR RATES TO BE OPERATED AT THE LARGER OF (1) THE MINIMUM LEVELS SPECIFIED IN <br />SECTION 120.1(c)3 OR (2) THE RATE REQUIRED FOR MAKE-UP OF EXHAUST SYSTEMS THAT ARE REQUIRED FOR A <br />PROCESS, FOR CONTROL OF ODORS, OR FOR THE REMOVAL OF CONTAMINANTS WITHIN THE SPACE. <br />TIMES OF OCCUPANCY. THE MINIMUM RATE OF OUTDOOR AIR REQUIRED BY SECTION 120.1(c) SHALL BE SUPPLIED TO <br />EACH SPACE AT ALL TIMES WHEN THE SPACE IS USUALLY OCCUPIED. <br />SHUT-OFF AND RESET CONTROLS FOR SPACE-CONDITIONING SYSTEMS; SHALL BE INSTALLED WITH CONTROLS CAPABLE <br />OF AUTOMATICALLY SHUTTING OFF THE SYSTEM DURING PERIODS OF NONUSE AND SHALL HAVE AN AUTOMATIC TIME <br />SWITCH CONTROL DEVICE AND ACCESSIBLE MANUAL OVERRIDE THAT ALLOWS OPERATION OF THE SYSTEM FOR UP TO <br />4 HOURS, AN OCCUPANCY SENSOR, OR A 4 HOUR TIMER THAT CAN BE MANUALLY OPERATED. <br />ALL HEATING OR COOLING SYSTEMS NOT CONTROLLED BY A CENTRAL ENERGY MANAGEMENT CONTROL SYSTEM (EMCS) <br />SHALL HAVE A SETBACK THERMOSTAT COMPLYING WITH 110.02c <br />Fans (§120.10) <br />EACH FAN OR FAN ARRAY WITH A COMBINED MOTOR NAMEPLATE HORSEPOWER GREATER THAN 1.00 HP OR WITH A <br />COMBINED FAN NAMEPLATE ELECTRICAL INPUT POWER GREATER THAN 0.89 kW SHALL HAVE A FAN ENERGY INDEX (FEI) <br />OF 1.00 OR HIGHER AT FAN SYSTEM DESIGN CONDITIONS. EACH FAN AND FAN ARRAY USED FOR A <br />VARIABLE-AIR-VOLUME SYSTEM THAT MEETS THE REQUIREMENTS OF SECTION 140.4(c)2 SHALL HAVE AN FEI OF 0.95 OR <br />HIGHER AT FAN SYSTEM DESIGN CONDITIONS. <br />GENERAL NOTES <br />1. <br />REMOVABLE CEILING PANEL OR PANELS AT FACE OF ALL FIRE AND FIRE/SMOKE DAMPERS BY GENERAL <br />CONTRACTOR (24" x 24" MIN.) UNLESS OTHERWISE NOTED. <br />2. <br />INCOMBUSTIBLE PLENUM ABOVE CEILING FOR RETURN/RECIRCULATING AIR BY GENERAL CONTRACTOR. CONCEALED <br />BUILDING SPACES USED AS RETURN AIR PLENUMS SHALL BE IN COMPLIANCE WITH 2022 CMC 602.2. <br />3. <br />ACCESS DOORS AND/OR ACCESS PANELS THROUGH FIRE RATED WALLS, SHAFTS, CEILINGS, ETC., MUST EQUAL THE <br />MATERIAL PENETRATED. <br />4. <br />ALL AIR SHAFTS SHALL BE MADE AIR TIGHT BY GENERAL CONTRACTOR. <br />5. <br />ALL UNDERCUT DOORS AND DOOR LOUVERS ARE BY GENERAL CONTRACTOR. <br />6. <br />ALL APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE SECURELY FASTENED IN PLACE. <br />7. <br />ALL SPACE CONDITIONING EQUIPMENT SHALL BE LABELED AS TO WHICH AREA IT SERVES. <br />INSTALLATION OF SOFT-COPPER REFRIGERANT PIPING SHALL FOLLOW THE INTERPRETATION THAT CEILING <br />STRUCTURES AND WALL STRUCTURES MEET THE REQUIREMENTS OF PIPING PROTECTION REQUIRED BY 2022 CMC <br />1109.7 <br />8. <br />EXCEPT AS MODIFIED BY A WRITTEN CONTRACT SIGNED BY THE DESIGN-BUILDER, THE DRAWINGS, SPECIFICATIONS, <br />AND OTHER DOCUMENTS, INCLUDING THOSE IN ELECTRONIC FORM PREPARED BY OR FOR AND/OR FURNISHED BY <br />DESIGN-BUILDER ARE “INSTRUMENTS OF SERVICE.” THE DESIGN-BUILDER, DESIGN-BUILDER'S CONSULTANTS AND <br />OTHER PROVIDERS OF PROFESSIONAL SERVICES INDIVIDUALLY SHALL RETAIN A FULLY PREPAID, UNRESTRICTED, <br />PERPETUAL LICENSE IN THE INSTRUMENTS OF SERVICE AS WELL AS ALL COMMON LAW, STATUTORY AND OTHER <br />RESERVED RIGHTS, INCLUDING COPYRIGHT IN THOSE INSTRUMENTS OF SERVICE FURNISHED BY THEM. <br />THE INSTRUMENTS OF SERVICE FURNISHED BY DESIGN-BUILDER ARE FOR SOLE USE BY DESIGN-BUILDER IN <br />CONSTRUCTING THE SUBJECT PROJECT. THE INSTRUMENTS OF SERVICE ARE NOT SUITABLE FOR BIDDING OR <br />CONSTRUCTING BY OTHER CONTRACTORS. THEREFORE, IF DESIGN-BUILDER IS NOT RETAINED AS THE DESIGN-BUILD <br />CONTRACTOR TO PERFORM THE WORK DEPICTED IN THE INSTRUMENTS OF SERVICE, WITHOUT THE PRIOR WRITTEN <br />CONSENT OF THE DESIGN BUILDER, THE INSTRUMENTS OF SERVICE MAY NOT BE REPRODUCED OR USED FOR ANY <br />PURPOSE EXCEPT FOR GENERAL REFERENCE. DESIGN-BUILDER DISCLAIMS ALL LIABILITY FOR ANY ADAPTATION, <br />MODIFICATION, OR INTERPRETATION OF THE INSTRUMENTS OF SERVICE, OR FOR ANY OTHER UNAUTHORIZED USE OF <br />THESE INSTRUMENTS OF SERVICE. <br />THESE DOCUMENTS WERE PREPARED FOR CONSTRUCTION BY DESIGN-BUILDER ONLY. DESIGN-BUILDER DEVELOPED <br />THESE DOCUMENTS WITH ENGINEERING SOLUTIONS AND CONSTRUCTION MEANS AND METHODS UNIQUE TO <br />DESIGN-BUILDER FOR THE CONSTRUCTION OF THE SUBJECT PROJECT AND ARE NOT APPROPRIATE FOR OTHERS TO <br />BID OR BUILD FROM. IN ADDITION, THESE DRAWINGS WERE DEVELOPED FROM INFORMATION MADE KNOWN TO <br />DESIGN-BUILDER AS OF THE DATE OF THE DOCUMENT AND WOULD NOT INCLUDE LATER CHANGES. <br />9. <br />10. <br />PIPE INSULATION MINIMUM REQUIREMENTS (2019 & 2022) <br />(PER TABLE 120.3-A PIPE INSULATION THICKNESS) <br />SYSTEM <br />FLUID <br /> TEMPERATURE <br /> RANGE (°F) <br />CONDUCTIVITY <br />RANGE (IN <br />BTU-INCH PER HOUR <br />PER SQUARE FOOT <br />PER °F) <br />INSULATION <br />MEAN <br />RATING <br />TEMP. (°F) <br />NOMINAL PIPE DIAMETER (INCHES) <br /><1 1 TO <1.5 1.5 TO <4 4 TO <8 8 AND <br />LARGER <br />INSULATION THICKNESS REQUIRED (IN INCHES) <br />SPACE HEATING AND SERVICE WATER HEATING SYSTEMS (STEAM, STEAM CONDENSATE, SPACE HEATING, SERVICE HOT WATER) <br />HHW SYSTEM 141-200 0.25-0.29 125 1.5 1.5 2.0 2.0 2.0 <br />*2" AND LARGER PIPE FOR DOMESTIC HOT WATER WILL REQUIRE 2" INSULATION TO MEET 2022 CPC 609.12.2 <br />BOILER (GAS) <br />TAG LOCATION MANUFACTURER & <br />MODEL No.SERVING <br />HEATING CAPACITY <br />DUTY %DESIGN <br />GPM <br />MIN. <br />GPM <br />EWT <br />(°F) <br />LWT <br />(°F) <br />DPw <br />(ft w.c.) <br />CAT <br />VENT VOLTAGE EMERGENCY <br />POWER <br />OPERATING <br />WEIGHT (lbs) <br />PRESSURE <br />RATING <br />(psi) <br />REMARKSINPUT <br />MBH <br />OUTPUT <br />MBH EFF.GAS PRESS. <br />(in w.c.) <br />TURNDOWN <br />RATIO <br />B-1 ROOF <br />LOCHINVAR <br />COPPER FIN II <br />CHN0992 <br />HHW LOOP 990 842 85%4.5" - 14"4:1 100 80 29 160 180 -CAT I 120V-1ɸ N 773 160 FIELD INSTALLED, FACTORY PROVIDED INLINE PUMP, MODEL #:CF-0992-2072. 1/2 HP, ALL BRONZE, 90 GPM, 120V-1ɸ <br />EQUIPMENT WEIGHT COMPARISON <br />TAG EXISTING WEIGHT <br />(lbs) <br />REPLACEMENT WEIGHT <br />(lbs) <br />DIFFERENCE <br />(lbs) <br />DIFFERENCE <br />(%) <br />B-1 894 773 121 -13% <br />D <br />Scale <br />Drawn By <br />Job Number <br />Designed By <br />Title <br />No.Date <br />Project Manager <br />Checked By <br />Description By <br />Project <br />Revisions <br />THE PLANS AND SPECIFICATIONS HEREIN <br />ARE OWNED BY AND FOR THE SOLE USE OF <br />ACCO ENGINEERED SYSTEMS, INC. <br />(“ACCO”)THE "DESIGN BUILDER", AND MAY <br />NOT BE REPRODUCED OR USED <br />BY OTHERS FOR ANY PURPOSE UNLESS <br />AUTHORIZED BY ACCO IN WRITING. ACCO <br />CANNOT ACCEPT ANY LIABILITY, WARRANTY, OR <br />OBLIGATION IN THE EVENT OF UNAUTHORIZED USE. <br />X: <br />\ <br />6 <br />0 <br />6 <br />5 <br />0 <br />2 <br />7 <br />7 <br />_ <br />O <br />C <br /> <br />P <br />R <br />O <br />B <br />A <br />T <br />I <br />O <br />N <br /> <br />- <br /> <br />1 <br />7 <br />0 <br />0 <br />\ <br />0 <br />1 <br />3 <br />- <br />1 <br />0 <br />- <br />E <br />- <br />H <br />V <br />A <br />C <br />\ <br />D <br />W <br />G <br />\ <br />! <br />B <br />o <br />i <br />l <br />e <br />r <br /> <br />R <br />e <br />p <br />l <br />a <br />c <br />e <br />m <br />e <br />n <br />t <br />\ <br />6 <br />0 <br />6 <br />5 <br />0 <br />2 <br />7 <br />7 <br />_ <br />M <br />_ <br />G <br />E <br />N <br />E <br />R <br />A <br />L <br /> <br />S <br />H <br />E <br />E <br />T <br />S <br />20 <br />2 <br />5 <br />- <br />0 <br />1 <br />- <br />2 <br />7 <br /> <br />1 <br />0 <br />: <br />2 <br />4 <br /> <br />A <br />M <br />Ke <br />l <br />s <br />e <br />y <br /> <br />T <br />h <br />o <br />m <br />a <br />s <br />OC PROBATION <br />BOILER REPLACEMENT <br />1700 ST. ANDREW PL. <br />SANTA ANA, CA 92705 <br />K. THOMAS M. LAYTON <br />K. THOMAS J. PORTER <br />60650277 <br />A 09-06-2024 ISSUE FOR PERMIT KMT <br />265 McCORMICK AVENUE <br />COSTA MESA, CALIFORNIA 92626 <br />(714) 352-2226 <br />CONSTRUCTION <br />REQUIREMENTS & <br />EQUIPMENT SCHEDULES <br />NONE <br />M0.01 <br />D 12-18-2024 REISSUE FOR PERMIT KMT <br />EXP. 06/30/26 <br />No.M34053 <br />RE <br />G <br />ISTERED PROF E SSIONAL ENGINE <br />ER <br />STATE OF CALIFORNIAMECHANICAL <br />MICHAEL G . LAYTON <br />1700 E St Andrew Pl- <br />Boiler4/16/2025