<br />-ROJECT NOTES:
<br />THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE 2022 CALIFORNIA
<br />ELECTRICAL CODE (CEC) ARTICLE 690, ALL MANUFACTURER'S LISTING AND
<br />INSTALLATION INSTRUCTIONS. AND THE RELEVANT CODES AS SPECIFIED
<br />BY THE AUTHORITY HAVING JURISDICTION'S (AHJ) APPLICABLE CODES.
<br />THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED ANO
<br />PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION
<br />?GROUND FAULT DETECTION AND INTERRUPTION {GFDI} DEVICE IS
<br />INTEGRATED WITH THE MICROINVERTER IN ACCORDANCE WITH 2022 CEG
<br />890 418)
<br />ALL PV SYSTEM COMPONENTS: MODULES, UTILITY-INTERACTIVE
<br />INVERTERS, AND SOURCE CIRGUIT COMBINER BOXES ARE IDENTIFIED AND
<br />LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY 2022 CEC 690.4
<br />PV MODULES: UL1703, 1E.C61730, AND IEC61215, AND NFPA 70
<br />CLAGS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519
<br />COMBINER BOX(ES) UL 1703 OR UL 1741 ACCESSORY,
<br />MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP
<br />COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX OC VOLTAGE CALCULATEO.
<br />ACCORDING TO 2022 CEC 690 7.
<br />ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS. AND
<br />SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC
<br />POWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION
<br />PER 690.4 (0). SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONS,
<br />FROM LISTING OR LABELING [2022 CEC 110.3}
<br />ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING
<br />CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL
<br />PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE CEC
<br />AND AHJ.
<br />SCOPE OF WOR!
<br />PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND
<br />?SPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT.
<br />PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTING
<br />ONSITE REQUIREMENTS TO DESIGN, SPECIFY. AND INSTALL THE
<br />EXTERIOR ROOF-MOUNTEO PORTION OF THE PHOTOVOLTAIC SYSTEMS
<br />DETAILED IN THIS DOCUMENT.
<br />?WORK INCLUDES:
<br />BV ROOF ATTACHMENTS - UNIRAC FLASHKIT PRO FOR COMP SHINGLE ROOF
<br />BV RACKING SYSTEM INSTALLATION - UNIRAC SOLAR MOUNT ROOF MOUNT
<br />RACKING HARDWARE
<br />PV MODULE AND INVERTER I N S T A L L A T I O N -SOLARIA POWER X-390R (390)
<br />[BLK] MODULES / ENPHASE 108M-72-2-US MICROINVERTERS
<br />BV EQUIPMENT GROUNDING
<br />PV SYSTEM WIRING TO A ROOF-MOUNTEO JUNCTION BOX
<br />PV LOAD CENTERS (IF INCLUDED)
<br />PV METERING:MONITORING (FF INCLUDED)
<br />PV DISCONNECTS
<br />PV GROUNDING ELECTRODE & BONDING TO (E) GEC.
<br />PV FINAL COMMISSIONING.
<br />(E) ELECTRICAL EQUIPMENT RETROFIT FOR PV
<br />SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE
<br />\.SITE NOTES:
<br />ALLADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA,
<br />REGULATIONS.
<br />?THE PY MODULES ARE CONSIDERED NON.COMBUSTIBLE AND THIS
<br />SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE
<br />BATTERIES.
<br />?THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING,
<br />MECHANICAL. OR BUILDING ROOF VENTS.
<br />PROPER ACCESS AND WORKING CLEARANGE AROUND EXISTING AND.
<br />PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION
<br />2022 CEC 110.28.
<br />ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN
<br />ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S
<br />INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT
<br />?THE BUILDING OR STRUCTURE.
<br />1.30,
<br />3
<br />432,
<br />1.33)
<br />4.34,
<br />1.35,
<br />1.38,
<br />4a.
<br />+30)
<br />1.40,
<br />1A
<br />1.42,
<br />1.431
<br />1a,
<br />148,
<br />148
<br />1.47,
<br />148.
<br />1.48,
<br />150,
<br />1st.
<br />321
<br />183)
<br />154,
<br />158.
<br />EQUIPMENT LOCATIONS:
<br />ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED @Y 2022 CEC
<br />110.28
<br />WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR
<br />EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY 2022 CEC 690.31 (AKC)
<br />AND CEG TABLES 310.15 (B)2MA) AND 20.15 (813)
<br />JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDERPV MODULES
<br />ACCORDING TO 2022 CEC 690 34
<br />ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE
<br />INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT
<br />ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED.
<br />PERSONNEL ACCORDING TO 2022 CEG APPLICABLE CODES.
<br />?ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR,
<br />?OUTDOOR USAGE WHEN APPROPRIATE,
<br />?STRUCTURAL NOTE!
<br />RACKING SYSTEM
<br />PV ARRAY WiLL BE INSTALLED ACCORDING TO CODE-COMPLIANT
<br />INSTALLATION MANUAL TOP CLAMPS REQUIRE & DESIGNATED SPACE BETWEEN
<br />MODULES, AND RAILS MUST ALSO EXTEND.
<br />AMINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY.
<br />?ACCORDING TO RAIL MANUFACTURER'S INSTRUCTIONS.
<br />JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S
<br />SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHEO SEALED
<br />PER LOCAL REQUIREMENTS.
<br />ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND
<br />SEALED WITH APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED
<br />CONTRACTOR,
<br />ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN
<br />?THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER.
<br />WHENPOSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE
<br />STAGGERED AMONGST THE ROOF FRAMING MEMBERS.
<br />WARING & CONDUIT NOTES:
<br />ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR
<br />PURPOSE C O N D U I T ANDWIRE SPECIFICATIONS ARE BASED ON MINIMUM
<br />CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING
<br />CONDUCTORS SIZEO ACCORDING TO 2022 CEC 690 8. 2022 CEC 690.7,
<br />VOLTAGE DROP LIMITED TO 1 5%.
<br />OC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRING
<br />?SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY WITH
<br />?SUITABLE WIRING CLIPS.
<br />AG CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1-
<br />BLACK PHASE BOR L2- REO, OR OTHER CONVENTION IF THREE PHASE
<br />PHASEC OR L3- BLUE, YELLOW, ORANGE?, OR OTHER CONVENTION.
<br />NEUTRAL. WHITE OR GREY IN 4:WIRE DELTA CONNECTED SYSTEMS THE
<br />PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [2022 CEC 110.15,
<br />ING NOTE
<br />GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR
<br />PURPOSE, AND GROUNDING DEVISES EXPOSED TO THE ELEMENTS SHALL
<br />BE RATED FOR SUCH USE.
<br />PY EQUIPMENT SHALL BE GROUNDED ACCORDING TO 2022 CEC 690.43 AND
<br />MINIMUM 2022 CEC TABLE 250.122.
<br />METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES
<br />CONSIDERED GROUNDED IN ACCORDING WITH 2022 CEG 250.134 AND 2022
<br />250 12644)
<br />EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO
<br />CEC 690-45 AND MICROINVERTER MANUFACTURER'S INSTRUCTIONS.
<br />156.
<br />187
<br />188.
<br />159
<br />180
<br />181.
<br />183
<br />184.
<br />185
<br />166
<br />187.
<br />1.58.
<br />1.70.
<br />ca
<br />173.
<br />1.74,
<br />EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CUPS AS
<br />SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE
<br />AK) (F WEBS ARE NOT USED MODULE GROUNDING LUGS MUST BE,
<br />INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE
<br />MANUFACTURERS? INSTALLATION REQUIREMENTS
<br />THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH
<br />THAT THE REMOVAL OF A MODULE DOES NOT I N T E R R U P TA GROUNDING.
<br />CONDUCTOR TO ANOTHER MODULE.
<br />GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE
<br />COLORED GREEN OF MARKED GREEN IF #4 AWG OR LARGER [2022 CEC.
<br />250 119]
<br />THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH CEC 690 47 AND
<br />?CEC 250 50 THROUGH 250.108 iF EXISTING SYSTEM IS INACCESSBLE. OR.
<br />INADEQUATE. A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO
<br />?CEC 250, CEC 690.47 AND AHI
<br />GROUND-FAULT DETECTION SHALL COMPLY WITH CEC 690.41 IN GENERAL
<br />AND CEC 690.41 {A\1) SPECIFICALLY.
<br />DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
<br />DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE
<br />SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE.
<br />CONNECTED TO THE TERMINALS MARKED ?LINE SIDE? (TYPICALLY THE
<br />UPPER TERMINALS)
<br />DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL. BE
<br />LOCKABLE, AND BE A VISIBLE-GREAK SWITCH
<br />RAPID SHUTDOWN OF ENERGIZED CONDUCTORS BEYOND 1FTOF PV
<br />ARRAY OR 5 FT INSIDE A BUILDING WITHIN 10 SECONDS. CONTROLLED
<br />CONDUCTORS S30V AND <240VA [CEG 690.12(6)} LOCATION OF LABEL
<br />ACCOROING TO AHS
<br />ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO CEC 690.8,
<br />8909 AND 240
<br />EQUIPMENT THAT IS LISTED, LABELED. OR BOTH SHALL BE INSTALLEDAND
<br />?USED IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING
<br />?OR LABELING. CEC 110.318)
<br />IF REQUIRED 6Y AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT
<br />PROTECTION ACCORDING TO CEC 690.11 AND UL16998.
<br />SSTERCONNECTION NOTES:
<br />LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH i2022 CEC
<br />705 121BV2K3nalt
<br />THE SUM OF THE UTILITY OCPD AND INVERTER CONTINUOUS INPUT MAY
<br />NOT EXCEED 120% OF BUSQAR RATING [2022 CEC 705 12(BKSN2i] [ene CEG
<br />705 1218%2)
<br />WHEN SUM OF THEPV SOURCES EQUALS >100% OF BUSBAR RATING. PV
<br />CEDICATED BACKFEED BREAKERS MUST 8E LOCATED OPPOSITE END OF
<br />THE BUS FROM THE UTILITY SOURCE OCPD {2022 CEC 705 12(B}23Nell
<br />AT MULTIPLE PV OUTPUT COMBINER PANEL. TOTAL RATING OF ALL
<br />QVERCURRENT DE. "''< SHALL NOT EXCEED AMPACITY OF BUSBAR
<br />HOWEVER THE: -ERGURRENT DEVICE MAY BE EXCLUDED
<br />ACCORDING 10 duc. 2 ?U5 121893)
<br />SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO 2022 CEC 706.11 HTH
<br />SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH 2022 CEC 290.42
<br />GACKFEEDING BREAKER FOR UTILTY-NTERACTIVE INVERTER OUTPUT (S
<br />EXEMPT FROM ADOITIONAL FASTENING [2022 CEC 705.12(E)I-
<br />C o m p l e t e S o l a r
<br />ABogtter Way
<br />3 0 0 0 E X E C U T I V E P K W Y ,
<br />S T E 5 0 4 S A N R A M O N ,
<br />C A 9 4 5 8 3
<br />L I C E N S E T Y P E C 1 0
<br />L I C E N S E # 9 6 1 9 8 8
<br />P H O N E # (8 7 7 ) 2 9 9 - 4 9 4 3
<br />DESIGNER: ORV
<br />JUAN SIANCASTAO
<br />RESIDENCE
<br />1646 E WASHI NGTON AVE
<br />SANTA A N A
<br />C A 9 2 7 0 1
<br />APN:40028711
<br />DATE:2/23/2023
<br />1646 E Washington
<br />Ave03/28/23
|