Laserfiche WebLink
Check HVAC Unit Overturning - Transverse Direction <br />Lhvac 8.333 ft=length of HVAC <br />W hvac 5.5 ft=width of HVAC <br />Hhvac 7.167 ft=height of HVAC <br />W p 2340 lb=weight of HVAC Unit <br />OTM1 0.6 Fh.wind⋅( ) <br />Hhvac <br />2 <br />⋅:=OTM1 4312 lb ft⋅= <br />RM W p <br />W curb <br />2 <br />⋅:=RM 5655 lb ft⋅= <br />Uplift 1 <br />1 <br />2 <br />OTM1 0.6( ) RM⋅− <br />W curb <br />⋅ <br />1 <br />4 <br />0.6 Fv.wind( )⋅⋅+ <br />...277.336 lb=:=uplift at <br />each corner <br /> Check HVAC Unit for Overturning - Longitudinal Direction <br />Lhvac 8.333 ft=length of HVAC <br />W hvac 5.5 ft=width of HVAC <br />Hhvac 7.167 ft=height of HVAC <br />W p 2340 lb=weight of HVAC Unit <br />OTM2 0.6 Fh.wind⋅( ) <br />Hhvac <br />2 <br />⋅:=OTM2 4312 lb ft⋅= <br />RM W p <br />Lcurb <br />2 <br />⋅:=RM 9165 lb ft⋅= <br />Uplift 2 <br />1 <br />2 <br />OTM2 0.6( ) RM⋅− <br />Lcurb <br />⋅ <br />1 <br />4 <br />0.60 Fv.wind( )⋅⋅+ <br />...106.502 lb=:=uplift at <br />each corner <br /> Maximum Uplift <br />Uplift max Uplift1 Uplift2, 0, ():=Uplift 277 lb= <br />Anchorage required to resist uplift loads <br />__________________________ <br />BRAD YOUNG & ASSOCIATES <br />STRUCTURAL ENGINEERING <br />345 Pollasky Ave. <br />Clovis, California, 93612 <br />(559) 323-9600 (559) 323-9633 Fax <br />____________________________________________________ <br />Copyright 2024 Brad Young & Associates <br />Print Date: 10/21/2024 <br />File Name: 24297 - PC RESPONSE.xmcd <br />Engineer:_ CG _ <br />5 <br />1740 E Edinger Ave <br />11/27/2024