The Enphase IQ System Controller 2 connects the
<br />home to grid power, the IQ Battery system, and solar
<br />PV. It provides microgrid interconnection device
<br />(MID) functionality by automatically detecting and
<br />seamlessly transitioning the home energy system
<br />from grid power to backup power in the event of a grid
<br />failure. It consolidates interconnection equipment into
<br />a single enclosure and streamlines grid independent
<br />capabilities of PV and storage installations by
<br />providing a consistent, pre-wired solution for
<br />residential applications.
<br />Enphase
<br />IQ System Controller 2
<br />To learn more about Enphase offerings, visit enphase.com
<br />Data Sheet
<br />Enphase Energy System
<br />Reliable
<br />• Durable NEMA type 3R enclosure
<br />• Ten-year limited warranty
<br />Smart
<br />• Controls safe connectivity to the grid
<br />• Automatically detects grid outages
<br />• Provides seamless transition to backup
<br />Simple
<br />• Connects to the load or service equipment¹ side of the main
<br />load panel
<br />• Centered mounting brackets support single stud mounting
<br />• Supports conduit entry from the bottom, bottom left side,
<br />and bottom right side
<br />• Supports whole home and partial home backup and
<br />subpanel backup
<br />• Up to 200A main breaker support
<br />• Includes neutral-forming transformer for split phase
<br />120/240V backup operation
<br />• IQ System Controller supports backward compatibility with
<br />older generation of PV microinverters (M215, M250 and S
<br />series), making it simple for home owners to upgrade their
<br />systems
<br />• Easy integration with generator from major manufacturers
<br />1. IQ System Controller 2 is not suitable for use as service equipment in Canada.
<br />To learn more about Enphase offerings, visit enphase.com
<br />© 2021 Enphase Energy. All rights reserved. Enphase, the Enphase logo, IQ System Controller 2, and other names are the trademarks of Enphase
<br />Energy, Inc. Data subject to change. 10-20-2021
<br />MODEL NUMBER
<br />EP200G101-M240US01 Enphase IQ System Controller 2 with neutral-forming transformer (NFT), Microgrid Interconnect Device (MID),
<br />breakers, and screws. Streamlines grid-independent capabilities of PV and battery installations.
<br />ACCESSORIES and REPLACEMENT PARTS
<br />EP200G-NA-XA-E3 Replacement IQ System Controller 2 printed circuit board
<br />EP200G-NA-HD-200A Eaton type BR circuit breaker hold-down screw kit, BRHDK125
<br />CT-200-SPLIT 200 A split core current transformers for Generator metering (+/- 2.5%)
<br />Circuit breakers (as needed)²,³
<br />• BRK-100A-2P-240V : Main breaker, 2 pole, 100A, 25kAIC, CSR2100
<br />• BRK-125A-2P-240V: Main breaker, 2 pole, 125A, 25kAIC, CSR2125N
<br />• BRK-150A-2P-240V: Main breaker, 2 pole, 150A, 25kAIC, CSR2150N
<br />• BRK-175A-2P-240V: Main breaker, 2 pole, 175A, 25kAIC, CSR2175N
<br />• BRK-200A-2P-240V: Main breaker, 2 pole, 200A, 25kAIC, CSR2200N
<br />Not included, must order separately:
<br />• BRK-20A-2P-240V-B: Circuit breaker, 2 pole, 20A, 10kAIC, BR220B
<br />• BRK-30A-2P-240V: Circuit breaker, 2 pole, 30A, 10kAIC, BR230B
<br />• BRK-40A-2P-240V: Circuit breaker, 2 pole, 40A, 10kAIC, BR240B
<br />• BRK-60A-2P-240V: Circuit breaker, 2 pole, 60A, 10kAIC, BR260
<br />• BRK-80A-2P-240V: Circuit breaker, 2 pole, 80A, 10kAIC, BR280
<br />EP200G-HNDL-R1 IQ System Controller 2 installation handle kit (order separately)
<br />EP200G-LITKIT
<br />BRK-20A40A-2P-240V 2 pole, 20A/40A, 10kAIC, BQC220240
<br />ELECTRICAL SPECIFICATIONS
<br />Assembly rating Continuous operation at 100% of its rating
<br />Nominal voltage / range (L-L) 240 VAC / 100 - 310 VAC
<br />Voltage measurement accuracy ±1% V nominal (±1.2V L-N and ±2.4V L-L)
<br />Auxiliary contact for load control, excess PV control, and generator two-wire control 24V, 1A
<br />Nominal frequency / range 60 Hz / 56 - 63 Hz
<br />Frequency measurement accuracy ±0.1 Hz
<br />Maximum continuous current rating 160A
<br />Maximum input overcurrent protection device 200A
<br />Maximum output overcurrent protection device 200A
<br />Maximum overcurrent protection device rating for Generator circuit 80A
<br />Maximum overcurrent protection device rating for storage branch circuit
<br />(the storage branch circuit can be replaced with PV)
<br />80A
<br />Maximum overcurrent protection device rating for IQ8 PV combiner branch circuit 80A
<br />Neutral Forming Transformer (NFT) • Breaker rating (pre-installed): 40A between L1 and Neutral; 40A between L2 and Neutral
<br />• Continuous rated power: 3600VA
<br />• Maximum continuous unbalance current: 30A @ 120V
<br />• Peak rated power: 8800VA for 30 seconds
<br />• Peak unbalanced current: 80A @ 120V for 30 seconds
<br />MECHANICAL DATA
<br />Dimensions (WxHxD) 50cm x 91.6cm x 24.6cm (19.7 in x 36 in x 9.7 in)
<br />Weight 39.4 kg (87 lbs)
<br />Ambient temperature range -40º C to +50º C (-40º F to 122º F)
<br />Cooling Natural convection, plus heat shield
<br />Enclosure environmental rating Outdoor, NEMA type 3R, polycarbonate construction
<br />Altitude To 2500 meters (8200 feet)
<br />WIRE SIZES
<br />Connections
<br />(All lugs are rated to 90C)
<br />• Main lugs and backup load lugs
<br />• CSR breaker bottom wiring lugs
<br />• BR breakers (wire provided)
<br />• AC combiner lugs, Encharge lugs, and generator lugs
<br />• Neutral (large lugs)
<br />Cu/Al: 1 AWG – 300 KCMIL
<br />Cu/Al: 2 AWG – 300 KCMIL
<br />6 AWG
<br />14 AWG – 2 AWG
<br />Cu/Al: 6 AWG - 300 KCMIL
<br />Neutral and ground bars Large holes (5/16-24 UNF)
<br />Small holes (10-32 UNF)
<br />14 AWG – 1/0 AWG
<br />14 AWG – 6 AWG
<br />COMPLIANCE
<br />Compliance UL 1741, UL 1741 SA, UL 1741 PCS, UL1998, UL869A , UL67 , UL508 UL50E
<br />CSA 22.2 No. 107.1, 47 CFR, Part 15, Class B, ICES 003, AC156.
<br />IQ System Controller 2 is approved for Use as Service Equipment in the United States .
<br />2. Compatible with BRHDK125 Hold-Down Kit to comply with 2017 NEC 710.15E for back-fed circuit breakers.
<br />3. The IQ System Controller 2 is rated 22 kAIC
<br />4. Not included. Installer must provide properly rated breaker per circuit breaker list above.