Laserfiche WebLink
DIVISION 1 <br />GENERAL REQUIREMENTS <br />1. ALL WORK SHALL BE WARRANTED FOR 1 YEAR AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP. <br />2. ALL WORK PERFORMED SHALL BE COMPLETED IN ACCORDANCE WITH ALL STATE, FEDERAL, AND LOCAL CODES, <br />ORDINANCES, AND LAWS, INCLUDING THE 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.: <br />2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.: 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, <br />TITLE 24 C.C.R: 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R: AND 2022 CALIFORNIA PLUMBING <br />CODE (CPC), PART 5, TITLE 24 C.C.R <br />3. CONTRACTORS SHALL COORDINATE THEIR WORK WITH UTILITIES COMPANIES AND OTHER TRADES. ANY CONFLICTS <br />SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION PRIOR TO THE WORK BEING INSTALLED. FAILURE TO DO SO WILL MAKE <br />THE CONTRACTOR RESPONSIBLE FOR THE COST TO CORRECT THE WORK. <br />4. EACH CONTRACTOR SHOULD VISIT THE SITE OF THE PROPOSED WORK, VERIFY ALL DIMENSIONS AND EXISTING <br />CONDITIONS, INCLUDING EASEMENTS, NOTIFY THE ARCHITECT OF ANY DISCREPANCIES, AND FULLY ACQUAINT THEMSELF <br />WITH THE SITE CONDITIONS RELATING TO CONSTRUCTION. <br />5. EACH CONTRACTOR WILL BE REQUIRED TO PROVIDE CERTIFICATES OF INSURANCE ISSUED BY AN ACCEPTABLE <br />COMPANY PRIOR TO COMMENCEMENT OF WORK ON THE SITE. <br />6. MAINTAIN AREAS FREE OF WASTE MATERIALS, DEBRIS, AND RUBBISH. MAINTAIN SITE IN A CLEAN AND ORDERLY <br />CONDITION. THE CONTRACTOR SHALL DISPOSE OF ALL DEMOLITION AND CONSTRUCTION DEBRIS OFF SITE AND IN AN <br />APPROVED MANNER, ACCORDING TO STATE AND CITY CODES. NOTIFY ARCHITECT AT ONCE IF ANY HAZARDOUS <br />MATERIALS ARE ENCOUNTERED. <br />7. COMPLETE FINAL CLEANING PRIOR TO WALK-THROUGH AND PREPARATION OF PUNCH LIST. CLEAN ALL SURFACES <br />EXPOSED TO VIEW. REMOVE WASTE AND SURPLUS MATERIALS, RUBBISH, AND CONSTRUCTION FACILITIES FROM SITE. <br />8. ALL EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR <br />EFFORT. NO DEADBOLTS, SLIDING BOLTS, ETC. PROVIDE SELF RELEASING LOCKING DEVICES ON EXIT DOORS. <br />9. ALL PRIMARY ENTRANCES AND ALL FACILITIES IN THE BUILDING SHALL BE MADE ACCESSIBLE TO THE HANDICAPPED PER <br />CBC CHAPTER 11B. <br />10. CONTRACTOR TO SECURE PERMIT AS REQUIRED BY THE CITY FIRE MARSHALL, PRIOR TO OCCUPYING THIS SPACE. <br />11. POST OCCUPANT LOAD SIGNS COMPLYING WITH CFC 1003 AND CBC 1004.3 AS REQUIRED. <br />12. FINISH CONTRACTORS SHALL ENSURE ALL FINISH MATERIALS WILL BE FLUSH AND WASHABLE. INTERIOR FINISH MUST <br />CONFORM TO THE REQUIREMENTS OF CBC. <br />13. FIRE EXTINGUISHERS TO BE PROVIDED, PER CFC 906 & TABLE 906.3(1). TO BE TYPE 2A10BC WITH CURRENT FIRE <br />MARSHALL SERVICE TAG, MOUNTED IN VISIBLE LOCATION, NOT MORE THAN 75 FT. FROM ANY POINT IN THE SPACE, AS <br />INDICATED ON DWG.S. PROVIDE SEMI RECESSED CABINET INSTALLATION: J.L. INDUSTRIES (OR EQUIV.) STOCK CABINET W/ <br />FIRE EXTINGUISHER - ABC #5. <br />14. ALL ELECTRICAL INSTALLATIONS, MAINS SERVICE AND PANEL BOARDS SHALL BE PER U.E.C.17. PROVIDE FIRE DAMPERS <br />IN ALL DUCTS PENETRATING FIRE RATED WALLS AND CEILINGS. SEE MECHANICAL SERIES DRAWINGS. <br />15. WHERE NO CONSTRUCTION DETAILS ARE SHOWN OR NOTED FOR ANY PART OF THE WORK TO BE DONE, DETAILS <br />SHOULD BE SAME AS FOR OTHER SIMILAR WORK. <br />16. APPROVED HARDWIRED SMOKE DETECTORS ARE TO BE INSTALLED IN ALL OFFICES, STORAGE ROOMS AND HALLWAYS, <br />PER 2016 CFC 105.4.2. <br />17. SITE SECURITY: PROJECT SITE SHALL BE SECURED AND MONITORED AT ALL TIMES. PROVIDE. TEMPORARY PORTABLE <br />CHAIN-LINK FENCING AS REQUIRED; MINIMUM 6 FEET HIGH. <br />18. PROVIDE AND PAY FOR ALL TEMPORARY UTILITIES, INCLUDING POWER, TELEPHONE, WATER AND TOILETS, AS REQUIRED. <br />GENERAL CONSTRUCTION <br />17. ALL STEEL FABRICATIONS TO BE PRIMED WITH BEST QUALITY RUST PROOFING PRIMER. <br />18. ALL POWER ACTUATED PINS/ANCHORS SHALL BE "RAMSET" #2330 AT 32" O.C. FOR INTERIOR, NON-LOAD BEARING <br />PARTITIONS PER ICC #ESR-1799. <br />19. ALL METAL FASTENERS SHALL BE MIN. HOT DIPPED GALVANIZED AFTER THEIR FABRICATION. ALL NAILS, SCREWS AND <br />BOLTS TO BE CORROSION RESISTANT. <br />20. ALL SUBSTRATES TO BE PAINTED OR OTHERWISE FINISHED, SHALL BE THOROUGHLY PREPARED AND CLEANED, AND <br />SHALL BE COMPATIBLE WITH PAINTS SELECTED. <br />21. DRYWALL CONTRACTOR SHALL PROVIDE ALL REQUIRED ACCESS PANELS WHERE NECESSARY TO PROVIDE ACCESS TO <br />FIRE DAMPERS, ELECTRICAL DISCONNECTS, PUMPS, VALVES, ETC. THE PAINTING CONTRACTOR WILL BE RESPONSIBLE TO <br />PAINT ALL ACCESS DOORS TO MATCH ADJACENT SURFACE. LAB AREAS: ALL ACCESS PANELS MUST HAVE AIR‐TIGHT GASKETS. <br />22. INSTALL SUPPLEMENTARY FRAMING, BLOCKING, AND BRACING AT TERMINATIONS IN GYPSUM BOARD ASSEMBLIES TO <br />SUPPORT CABINETRY, FIXTURES, EQUIPMENT SERVICES <br />DIVISION 2 <br />DIVISION 3 <br />CONCRETE FLOOR REPAIRS <br />1. CONTRACTOR SHALL DETERMINE LOCATION OF EXISTING UTILITY LINES BELOW EXISTING FLOOR SLAB AND CONDUCT <br />CORING AND/OR TRENCHING FOR CONNECTION OF NEW UTILITIES. WORK SHALL BE CARRIED OUT TO MINIMIZE <br />DISTURBANCE TO EXISTING FLOOR SLAB OR ADJACENT TENANTS. COORDINATE WITH BEAM / REINFORCEMENT <br />LOCATIONS. COORDINATE ALL SUCH WORK WITH PLUMBING AND ELECTRICAL SUBCONTRACTORS, AND FILL GAPS <br />AROUND PIPEWORK WITH FIRE RATED CAULKING / SAFING MATERIAL TO MAINTAIN 2-HOUR FIRE RATING AT 2ND FLOOR <br />CONCRETE SLAB. PROVIDE CEMENTITIOUS FLOAT / FILL TO ENSURE NEW / EXISTING FLOORING SURFACE IS SMOOTH AND <br />LEVEL AND APPLY MOISTURE SEALANT AT ALL AREAS WHERE MOISTURE PRESSURE EXCEEDS FLOORING MANUFACTURER <br />INSTALLATION RECOMMENDATIONS, AS REQUIRED. <br />2. PENETRATION THRU RATED WALLS SHALL BE SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF <br />FLAMES AND HOT GASES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC OF FIRE STOPS <br />ASTM-E-814 (U.L. SYSTEM #WL1001 FOR WALLS & #CAJ1001 FOR FLOORS). <br />DIVISION 6 <br />INTERIOR CABINETRY <br />1.INSTALL ALL ITEMIZED PREFABRICATED CABINETRY AS NOTED ON PLANS, PER MANUFACTURER'S DIRECTIONS AND <br />MAKE ALL UTILITY CONNECTIONS AS REQUIRED. <br />2.CABINET SUBCONTRACTOR TO VERIFY ALL CABINET WIDTH DIMENSIONS PRIOR TO FABRICATION. COMPLY WITH AWI <br />STANDARDS FOR CUSTOM GRADE AND PREMIUM GRADE FOR PLASTIC LAMINATE. SUBMIT SHOP DRAWINGS IN <br />CONJUNCTION WITH OTHER SUBMITTALS COVERING FABRICATION, INSTALLATION AND FINISH FOR CONFORMANCE W/ <br />DESIGN INTENT, ETC. <br />3.CUSTOM CABINET INTERIORS TO BE CONSTRUCTED OF WHITE MELAMINE SURFACED HIGH DENSITY <br />PARTICLEBOARD, PER ANSI 208.1 GRADE M-2, EXCEPT AT AREAS BELOW SINKS, WHICH SHALL BE SURFACED WITH WHITE <br />HIGH DENSITY PLASTIC LAMINATE OVER 3/4" PLYWOOD. ALL EXPOSED INTERIOR EDGES TO BE COVERED WITH MELAMINE <br />UNLESS NOTED OTHERWISE. ALL CABINET BASES TO BE PLASTIC LAMINATE. <br />4.CABINET DRAWER GLIDES TO BE 100LB FULL EXTENSION GLIDES - GRANT GR 329 (OR EQUAL) GLIDE LENGTH TO BE <br />AS REQUIRED BY CABINET DEPTH (2"-4" SHORTER THAN OVERALL DEPTH OF CABINET.) CABINET STANDARDS TO BE KV FLUSH <br />SHELF STANDARDS: KV255WH72 (STEEL WHITE EPOXY COAT) WITH KV CLIPS KV256WH (STEEL WHITE EPOXY COAT), OR <br />APPROVED EQUAL SYSTEM. <br />5.CABINET DOOR HINGES TO BE BLUM MODUL FULL OVERLAY 110O FULLY CONCEALED HINGE. REFER TO MANUF. <br />SPECIFICATIONS FOR NUMBER PER DOOR AND MOUNTING STYLE APPLICATION REQUIRED. LOCKS WHERE REQUIRED, TO <br />BE BEST LOCKS 5L SERIES LATCHBOLT 3/4" UTILITY CYLINDERS, SATIN CHROME FINISH. SUPPLY TWO KEYS PER LOCK. INTERIOR <br />SURFACE HEAD AND FOOT BOLTS TO BE 4" IVES IV40-4BR. EXCEPT WHERE PUSH-CATCHES ARE REQUIRED. <br />6.FINAL SELECTION OF CABINET DOOR & DRAWER PULLS TO BE BY OWNER; ALLOW FOR 5" L.RECTANGULAR BAR <br />D-PULLS, AS SKYLIGHT# HH075328-14 BY HICKORY HARDWARE INC. IN BRUSHED NICKEL FINISH. VERIFY W/ OWNER PRIOR <br />TO INSTALLATION. <br />7. CUSTOM CABINET BODIES, DOORS, DRAWER FRONTS AND SIDE PANELS TO BE HIGH PRESSURE PLASTIC LAMINATE <br />OVER 3/4" HIGH DENSITY FIBERBOARD PER ANSI 208.2, EXCEPT AT ALL TOPS AND WET AREAS (SINK LOCATIONS, ETC.) <br />WHERE 3/4 PLYWOOD SHALL BE USED. PROVIDE PLASTIC LAMINATE OR SOLID-SURFACE TOPS AS NOTED ON CABINET <br />ELEVATIONS. TOPS AND EDGING TO BE CHEMICAL-RESISTANT PLASTIC LAMINATE MIN. .050" THK. PER NEMA LD-3. <br />VERTICAL SURFACES MAY EMPLOY .028" THK. LAMINATE. GROMMETS TO BE HAFELE - HA429.93.322 (OR EQ.) BLACK <br />ROUND PLASTIC GROMMETS.(LOUIS & CO. (214) 647-8811). FINAL LOCATION OF GROMMETS TO BE APPROVED BY <br />OWNER PRIOR TO INSTALLATION <br />8.ALL STORAGE SHELVING TO BE 6 TIER X 12" WIDE (OR AS NOTED), CONSTRUCTED OF WHITE MELAMINE SURFACED <br />HIGH DENSITY FIBERBOARD. COVER EXPOSED EDGES WITH MELAMINE UNLESS NOTED OTHERWISE. INSTALL ON STANDARD <br />METAL KNIFE-EDGE BRACKETS SET ON FLUSH VERTICAL STANDARDS @ MIN. 24" ON CENTER. <br />8. REFER TO FINISH SCHEDULE ON THIS SHEET FOR ALL LAMINATE AND COUNTERTOP FINISH SELECTIONS, ETC. <br />DIVISION 7 <br />INSULATION AND SEALANTS <br />1. PROVIDE INSULATION WITH FIRE PERFORMANCE PER TEST METHODS ASTM E 84, ASTM E 119 AND ASTM E 136. <br />2. FOR ALL INTERIOR WALLS FULL HT. TYPE I (BLANKETS WITHOUT MEMBRANE FACING), AS USG <br />"THERMAFIBER" OR EQUAL HAVING BEST SOUND DEADENING PROPERTIES (MIN. R-11). <br />3. INTERIOR PLUMBING FIXTURES; 1- PART SANITARY, MILDEW RESISTANT, AS DOW CORNING 786 OR EQ. <br />4. R-11 FOR MISSING WALL INSULATION. INSULATION TO COMPLY WITH ASTM C 665 FOR TYPE III, CLASS A : BLANKETS WITH <br />KRAFT MEMBRANE FACING. SET FACED UNITS WITH KRAFT TOWARDS OUTSIDE. <br />5. SEALANT FOR THRESHOLDS; SINGLE COMPONENT POLYSULPHIDE, BY PECORA, DAP, OR EQUAL. <br />6. INTERIOR PAINTED AREAS; ACRYLIC LATEX CAULK BY TREMCO, OR EQUAL. <br />7. INTERIOR CABINETRY AND VINYL WALL COVERING;1-PART SILICONE AS DOW CORNING 795 OR EQ. <br />8. INTERIOR PLUMBING FIXTURES;1- PART SANITARY, MILDEW RESISTANT, AS DOW CORNING 786 OR EQ. <br />ROOFING REPAIRS <br />9. LANDLORD'S NOMINATED ROOFING CONTRACTOR SHALL BE EMPLOYED FOR ALL ROOFING PATCH AND REPAIR WORK. <br />10.MAKE ALL REQUIRED REPAIRS AT NEW PENETRATIONS, EQUIPMENT-MOUNTINGS, ETC. OR ESTABLISHED LEAKS OR <br />DETERIORATED AREAS, USING 4-PLY CLASS A / I-60 BUILT-UP ASPHALT/ PLY SYSTEM WITH WHITE (GRANULAR) CAP SHEET TO <br />MATCH EXISTING SYSTEM. FIELD VERIFY AND REPORT TO ARCHITECT ON ALL PRE-EXISTING NEGATIVE ROOFING <br />CONDITIONS: ACCOUNT FOR THIS WORK AS A PART OF YOUR BID. CONTRACTOR MAY SLIT MEMBRANES IF PROPER <br />PATCHES ARE PROVIDED. DURING ROOFING REPAIR OPERATIONS PROVIDE PROTECTIONS TO ENSURE AGAINST BITUMEN <br />SPILLS ON SIDING OR PAVING BELOW. CLEAN UP ANY SPILLS OR SPATTERS IMMEDIATELY. <br />11. EXTEND ALL NEW VENT PIPES TO 12" ABOVE SHEATHING. ADD METAL FLASHING COLLARS TO ALL NEW PIPES AFTER <br />COMPLETION OF BUILT UP ROOFING REPAIRS. <br />12. PROVIDE 22 GAGE GALVANIZED SHEET METAL FLASHINGS, WITH PAINT FINISH AT ROOF EDGES, ETC. <br />DIVISION 8 <br />INTERIOR WINDOWS / VISION PANELS <br />1. SUBMIT SHOP DRAWINGS IN CONJUNCTION WITH OTHER SUBMITTALS COVERING FABRICATION, INSTALLATION AND <br />FINISH FOR CONFORMANCE W/ DESIGN INTENT, ETC. VERIFY QUANTITIES AND SIZES PRIOR TO ORDERING. <br />2. INTERIOR WINDOWS SHALL BE SINGLE GLAZED WITH 1/4" THICK, CLEAR TEMPERED PANES WITH TINTS, FILMS, ETC. OR <br />OTHER SPECIAL GLAZING PRODUCTS AS SPECIFIED AND NOTED ON THE PLANS. NON-RATED GLAZING SHALL BE SET IN <br />HIDDEN C-CHANNEL ALUMINUM FRAMES AND STOPS. <br />INTERIOR DOORS <br />4. CONTRACTOR TO COORDINATE AND REVIEW DOOR SUBMITTALS (INCL. HARDWARE SCHEDULES) FOR CONFORMANCE <br />WITH DESIGN INTENT, ETC. VERIFY QUANTITIES/ SIZES PRIOR TO ORDERING. <br />5a. INTERIOR DOORS TO BE 'WESTERN INTEGRATED' FLUSH SLAB SOLID CORE, WOOD DOORS, WITH PLASTIC LAMINATE <br />FINISH (AS DIRECTED IN THE OWNER'S COLOR SCHEDULE). INTERIOR FRAMES SHALL BE 'WESTERN INTEGRATED' <br />KNOCK-DOWN METAL FRAME, COLOR: CLEAR ANNOD. INCLUDING CLEAR ALUM SNAP-ON TRIM. <br />5b. INTERIOR VISION PANELS IN DOORS TO BE GLAZED W/ 1/4" THICK, CLEAR TEMPERED GLASS (OR LEADED) PER <br />SCHEDULE. ALL FRAMES AND STOPS TO BE PAINTED STEEL. <br />5c. DOOR FRAMES WITH INTEGRAL SIDELITES SHALL BE BY WESTERN INTEGRATED (562-634-2823) - GC TO COORD. WITH <br />WESTERN INTEGRATED PRIOR TO ORDERING AND INSTALLATION. <br />6. WINDOWS AND ENTRY / EXIT DOORS TO REMAIN WHERE EXISTING. ANY REPLACEMENTS SHALL MATCH EXISTING: <br />PROVIDE BUILDING STANDARD DOORS, PRE-FINISHED CLEAR, OR COLOR AS DIRECTED BY LANDLORD. ENTRY DOOR <br />FRAMES SHALL BE PROFILE, STYLE AND FINISH AS DIRECTED BY LANDLORD. <br />7. MOUNT HARDWARE UNITS AT HEIGHTS INDICATED IN FOLLOWING APPLICABLE PUBLICATIONS, EXCEPT AS SPECIFICALLY <br />INDICATED OR REQUIRED TO COMPLY WITH CBC GUIDELINES AND CBC 1008.1.8 AND HANDICAP ACCESSIBILITY <br />REGULATIONS <br /> 1. "RECOMMENDED LOCATIONS FOR BUILDERS HARDWARE FOR STANDARD STEEL DOORS AND FRAMES" BY THE DOOR <br />AND HARDWARE INSTITUTE. <br />8. WHERE CLOSERS ARE INDICATED FOR DOORS REQUIRED TO BE ACCESSIBLE TO THE PHYSICALLY HANDICAPPED, <br />PROVIDE ADJUSTABLE UNITS COMPLYING WITH ANSI A117.1 PROVISIONS FOR DOOR OPENING FORCE AND DELAYED <br />ACTION CLOSING. FINISH TO MATCH SPRAYED LAQUER US26D. ADJUST UNITS TO COMPLY WITH CBC PROVISIONS FOR <br />DOOR OPENING FORCE AND DELAYED ACTION CLOSING. <br />9. PROVIDE CBC APPROVED ALUM. / VINYL TRANSITION STRIPS AT DOORWAYS BETWEEN FLOORING OF <br />DIFFERENT TYPES. SEE ARCHITECT'S DETAIL. <br />10. AS REQUIRED BY MECHANICAL ENGINEER, UNDERCUT RESTROOM DOOR 1-1/2 FOR AIR CONDITIONING TRANSFER. <br />11. EQUIP LOCKS WITH INTERCHANGABLE CORE PIN TUMBLER INSERTS. PROVIDE 6-PIN CYLINDER HDWR. WITH 2 KEYS FOR <br />EACH LOCK. PROVIDE 2 MASTER KEYS. <br />12. PROVIDE SUBMITTAL DOCUMENTS FOR ALL HARDWARE REFERENCED TO EACH DOOR. HINGES TO BE 4-1/2" X 4-1/2" <br />HINGE CO.; LOCKS SHALL BE SCHLAGE AL / SPARTA D SERIES. MATCH EXISTING WHERE NECESSARY. PROVIDE MANUF. <br />CATALOGUE CUTS FOR OWNER SELECTION. <br />13. INTERIOR STOREFRONT GLASS DOORS (AND DOOR SIDELIGHT) TO BE 1/4" THICK SINGLE GLAZED, CLEAR TEMPERED. <br />14. SPECIALTY HARDWARE TYPES TO BE AS FOLLOWS: <br />STOREFRONT ENTRIES: <br />STOREFRONT HINGES / PIVOTS, <br />12" 'D' PULLS, <br />O/H DOOR CLOSER, <br />DEADLOCK: ADAMS RITE D.R. MS 1850, MS 4043, OR MS 4002, OR EQ. <br />WEATHER-STRIPPING, THRESHOLD AND STOPS <br />INTERIOR UTILITY / ELECTRICAL / MACHINE ROOM CLOSET: <br />1-1/2 PR X 4" BUTT HINGES, <br />LEVER CYL. LOCK, <br />WEATHER-STRIPPING, THRESHOLD AND STOPS <br />OPERATING ROOM DOORS: <br />2 PR X 4" BUTT HINGES, <br />GLYNN JOHNSON HL-6 PUSH-PULL LATCH, <br />SOUND-STRIPPING, THRESHOLD AND STOPS <br />12" STAINLESS STEEL KICK PLATES <br />15.FINISH: PROVIDE BRUSHED ALUMINUM FINISH FOR ALL HARDWARE. HINGES TO BE MIN. 4" X 4" AS HAGER HINGE CO. <br />OR EQUAL. LOCKSETS TO BE SCHLAGE TRE-PLY DESIGN. STOPS, GASKETS (S88D), AND WEATHER -STRIPPING TO BE PEMKO <br />MANUF. INC. PROVIDE 3 RUBBER SILENCERS PER SINGLE DOOR. <br />DIVISION 10 CONT.): <br />WINDOW COVERINGS <br />6.PROVIDE VERTICAL WINDOW COVERINGS AT EACH EXISTING EXTERIOR WINDOW AS SPECIFIED BELOW. CONFIRM <br />STYLE, ETC. W/ OWNER PRIOR TO ORDERING: <br />MECHOSHADE THERMOVEIL 1300 SERIES DENSE BASKET WEAVE SHADECLOTH, COLOR: 1320 SHADOW GREY <br />DIVISION 15 <br />PLUMBING NOTES: <br />1. READ W/ MECHANICAL PLUMBING SPECIFICATION DRAWINGS. <br />2. ALL PLUMBING SHALL BE IN ACCORDANCE WITH CPC AND ALL LOCAL CODES AND ORDINANCES. <br />3. CONTRACTOR TO COORDINATE EQUIPMENT CONNECTIONS WITH ALL OTHER TRADES AND <br />SUPPLIERS. INSTALL AND MAKE FINAL CONNECTIONS, FURNISHING CUT-OFF VALVES, P-TRAPS, P.R.V.'S AND PIPING AS <br />REQUIRED. <br />3A. INSTALL SHOCK ABSORBERS IN COLD WATER LINES, AS REQUIRED <br />4. CONNECT TO EXISTING VENT AND WASTE STACKS WHERE POSSIBLE. CAREFULLY COODINATE WORK IN FLOOR WITH <br />LOCATION OF EXISTING UTILITIES. DO NOT DISTURB ADJACENT BUILDINGS DURING WORKING HOURS. <br />5. HOT WATER SUPPLY TO BE CONNECTION TO NEW ELECTRICAL WATER HEATER, OR AS NOTED ON PLUMBING PLANS. <br />6. ALL PIPEWORK SHALL BE CONCEALED IN STUD WALLS ETC. STUB-OUTS SHALL BE MIN. 6" AFF. <br />7. HOT AND COLD WATER PIPING SHALL BE 1/2" DIA. COPPER TYPE "L" PER ASTM B88, INSULATED WITH 1" FIBERGLASS, WITH <br />VAPOUR SEAL ON COLD WATER PIPING. SLEEVE ALL NEW UNDERGROUND PIPING. <br />8. CONDENSATE DRAIN PIPING SHALL BE TYPE "L" COPPER WITH 1" FIBERGLASS INSULATION. <br />9. DRAIN LINES TO BE NO SMALLER THAN STUB-OUT OF FIXTURE ITSELF, OR MIN. 1 1/2" DIA. <br />10. SCREWED PIPE SHALL BE MADE UP WITH PIPE COMPOUND APPLIED TO MALE THREAD, WITH NOT MORE THAN 2 <br />THREADS LEFT EXPOSED. PIPES SHALL BE REAMED AFTER THREADING. <br />11. COPPER JOINTS SHALL BE MADE UP WITH 95-5 SOLDER. <br />12. CLEAN-OUTS SHALL BE AS MANUF. JOSAM ZURN MANUF. CO., OR EQUAL, AND SHALL BE INSTALLED AT ALL BENDS <br />ANGLES AND ENDS OF WASTE AND SEWER LINES. ALL CLEAN-OUTS SHALL BE BROUGHT TO FINISHED FLOOR LEVEL AND <br />SHALL BE PROVIDED WITH SUFFICIENT SPACE FOR RODDING. <br />13. ALL VALVES SHALL BE BRASS, MANUF. BY CRANE, NIBCO, STOCKHAM, LUNKENHEMER, NORDSTRON, GRINNELL OR <br />EQUAL. <br />14. PROVIDE GATE VALVES ON ALL WATER LINES. <br />FIRE SPRINKLER SYSTEM: <br />1. PLANS FOR MODIFICATIONS TO FIXED FIRE PROTECTION EQUIPMENT SHALL BE PREPARED AND SUBMITTED TO THE <br />OWNER & ARCHITECT BY INSTALLING CONTRACTOR AND SHALL BE APPROVED BY COSTA MESA FIRE DEPARTMENT, <br />OWNER'S INSURANCE ORGANIZATION AND ARCHITECT PRIOR TO INSTALLATION. SPRINKLER CONTRACTOR SHALL BE <br />NOMINATED BY LANDLORD (ONLY). <br />2. COMPLY WITH NFPA 13 AND 24 "STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS." THE BUILDING'S <br />AUTOMATIC SPRINKLER SYSTEM SHALL COMPLY WITH 2022 CFC 105.4.2. <br />3. COMPLY WITH NFPA 70 "NATIONAL ELECTRICAL CODE" FOR ELECTRICAL CONNECTIONS BETWEEN WIRING AND <br />ELECTRICALLY OPERATED DEVICES. <br />4. VERIFY EXISTING UTILITY LOCATIONS. INSTALL DETECTOR CHECK VALVES AS REQUIRED. COMPLY WITH NFPA 26 FOR <br />DEVICES AND METHODS OF VALVE SUPERVISION. <br />5. INSTALL FULLY CONCEALED HEADS IN ALL AREAS, EXCEPT SEMI-RECESSED CHROME FINISH HEAD WITH WHITE FINISHED <br />ESCUTCHEON MAY BE USED IN ELECTR. UTILITY ROOMS ONLY. <br />DIVISION 16 <br />SEE ELECTRICAL SPECIFICATIONS. ON SEPARATE DRAWINGS <br />1. COORDINATE WITH LANDLORD'S FIRE ALARM SUB-CONTRACTOR. THE FIRE ALARM SYSTEM SHALL CONFORM TO <br />ARTICLE 760 2022CALIFORNIA ELECTRICAL CODE. <br />2.ALL DEVICES OF THE FIRE ALARM SYSTEM SHALL BE APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE <br />MARSHALL. A CERTIFICATE OF COMPLIANCE SHALL BE PREPARED BY THE INSTALLER. INSTALLER TO PROVIDE CSFM LISTING <br />NUMBERS FOR ALL APPLICABLE DEVICES PER 2022 CFC 907.1.3. <br />3.PROVIDE HARD-WIRED SMOKE DETECTORS IN QUANTITIES AND LOCATIONS AS REQUIRED BY THE COSTA MESA FIRE <br />DEPARTMENT. <br />NURSE CALL SYSTEM <br />4.COORDINATE INSTALLATION OF OWNER'S NURSE CALL ALARM SYSTEM; TO BE LINKED WITH PULL CORD STATIONS IN <br />EACH OF THE PATIENT EXAM AREAS AND AND RESTROOMS, TO RECESSED ILLUMINATED ANNUNCIATOR AT CENTRAL <br />NURSE STATION CABINETRY. PROVIDE CONNECTIONS PER E-SERIES PLANS . VERIFY ALL PRE- INSTALLATIONS AND SYSTEM <br />REQUIREMENTS WITH OWNER. <br />FIRE ALARM <br />1.COORDINATE INTEGRATION OF NEW SUITE FIRE ALARM SYSTEM WITH LANDLORD'S EXISTING CENTRAL BUILDING <br />ALARM SYSTEM. EMPLOY LANDLORD'S NOMINATED FIRE ALARM COMPANY FOR ALL FIRE ALARM WORK. PROVIDE <br />DOCUMENTATION OF DEVICE COMPATIBILITY PER 2016 CFC 907.1.3. <br />2.PROVIDE CONDUITS TO PULL STATIONS WITHIN 5 FEET EACH EXIT AND NURSE STATION / CENTRAL HALLWAY. <br />INCLUDE CONNECTIONS TO ILLUMINATED STROBE/HORN ANNUNCIATORS PER CEILING PLAN. PROVIDE CONNECTIONS <br />PER E-SERIES PLANS . VERIFY ALL PRE- INSTALLATIONS AND SYSTEM REQUIREMENTS WITH OWNER. <br />LIGHT FIXTURES: <br />UNLESS DIRECTED OTHERISE; 2' X 4' INDIRECT LUMINAIRE, PERFORATED LIGHT SHIELD, CENTERMOUNT CONFIGURATION, <br />STANDARD WHITE - SEE E-SERIES PLAN / SPECS <br />LIGHT SWITCH: LEVITON #5501, WHITE <br />ELECTRICAL WALL OUTLET: <br />25.LEVITON DUPLEX OUTLET #5242, 20A, 120V, WHITE OR RED FOR EMERGENCY POWER OUTLETS <br />ELECTRICAL WALL OUTLET - DEDICATED: <br />1.LEVITON DUPLEX OUTLET #5242, 20A, 120V, WHITE <br />TELEPHONE BACKBOARD: <br />1.4'-0" X 4'-0" ¾" CDX PLYWOOD BACKBOARD <br />2.TELEPHONE FEEDER <br />3.ONE DEDICATED 110V DUPLEX OUTLET <br />PROVIDE CEILING SPEAKERS IN LOCATIONS SHOWN, W/ WALL-MOUNTED VOLUME CONTROLS IN EA. ROOM: 6 OR 8 INCH <br />2-WAY LOUDSPEAKER, 60W RMS POWER, WITH A WHITE ALUMINUM GRILLE, 6DB HIGH - LOW PASSFREQ. POWER <br />HANDLING: 130 WATTS (60 RMS)IMPEDANCE: 8 OHM NOMINAL. PROVIDE 18 GA. CO-AX SPKR. CABLE HOMERUN FROM <br />EA. SPKR. TO SERVER ROOM. <br />DIVISION 9 9CONT.): <br />3. STUD WALLS SHALL HAVE CONT. 20 GA. SHEET METAL BACKING AND HORIZONTAL BLOCKING WHERE WALL-HUNG <br />CABINETS / EQUIMENT INDICATED. PROVIDE DOUBLE 20 GA. STUDS AT ALL DOOR JAMBS. <br />4. ALL VERTICAL DRYWALL CORNERS / EDGES SHALL BE CONSTRUCTED WITH SQUARE METAL DRYWALL TRIM BEADS, TO BE <br />COORDINATED WITH PLANT-ON CORNER PROTECTION AS REQUIRED. <br />5. INTERIOR PARTITIONS: 1 LAYER 5/8" GYPSUM BOARD EACH SIDE 3 5/8" X 20 GAUGE METAL STUDS AT 16" ON CENTER, <br />EXCEPT THAT WATER-RESISTANT GYP. BD. IS REQUIRED AT PLUMBING WALLS. REPAIRS TO DEMISING WALLS SHALL INCLUDE <br />R-11 INSULATION. AT LAB AREAS: ALL ACCESS PANELS MUST HAVE AIR-TIGHT GASKETS. <br />6. ALL DRYWALL SHALL BE FINISHED WITH A LEVEL-4 SMOOTH TEXTURE. <br />SUSPENDED CEILING (NON-RATED OPEN PLENUM)/ T-BAR CEILINGS <br />7. APPLY ACOUSTICAL SEALANT IN A CONTINUOUS RIBBON CONCEALED ON BACK OF VERTICAL LEGS OF EDGE MEMBERS, <br />AT PRIVATE OFFICE ONLY. <br />8. PROVIDE CLIPS ETC. FOR ATTACHING HANGERS WITH CAPABILITY TO SUSTAIN A LOAD 10 TIMES THAT OF CEILING <br />CONSTRUCTION, PER ASTM E 1190. WIRE FOR HANGERS AND TIES: ASTM A 641, CLASS 1 ZINC COATING, SOFT TEMPER. DO <br />NOT ATTACH HANGERS TO CONC. FLOOR DECK OR STEEL DECK TABS. ATTACH HANGERS TO STRUCTURAL MEMBERS. <br />SPACE HANGERS MAX. 48" O.C. AND NOT MORE THAN 8" FROM ENDS OF EACH MEMBER. <br />9. SUSPENSION SYSTEM FOR INTERIOR CEILINGS: ARMSTRONG SEISMIC RX HEAVY DUTY SUSPENDED T-BAR CEILING SYSTEM <br />SET AT HEIGHTS SHOWN ON CEILING PLAN, PER ASTM C 645 (MANUFACTURER'S STANDARD DIRECT-HUNG SUSPENSION <br />SYSTEM FOR SUSPENDED GYPSUM BOARD CEILINGS). MAIN BEAMS AND CROSS FURRING MEMBERS INCLUDING SEISMIC <br />SPLAY-BRACING AND VERTICAL STRUTS THAT ARE CROSS CONNECTED TO FORM A MODULAR SUPPORTING NETWORK. <br />10. CEILING TILES: WHITE 1/2" X 24" X 24" NON-FIRE-RESISTANCE-RATED, WATER-FELTED, MINERAL-BASE TILE: TYPE III, FORM 2 <br />ACOUSTICAL TILES PER ASTM E 1264 IN ALL T-BAR LOCATIONS, AS 'ASTRO-CLIMA PLUS' W/ RABBETED EDGE, OR <br />EQUIVALENT. MATCH EXISTING WHERE POSSIBLE. <br />13. STANDARD FOR CEILING SUSPENSION SYSTEM INSTALLATIONS: COMPLY WITH ASTM C 636 AND CBC. CONFORM TO THE <br />LAYOUT SHOWN ON REFLECTED CEILING PLANS. SCREW EDGE SUPPORTS TO SUBSTRATE AT 16" O.C. AND AT 3" FROM <br />ENDS, LEVELING WITH CEILING SUSPENSION SYSTEM TO A TOLERANCE OF 1/8" IN 12 FEET. MITER CORNERS ACCURATELY <br />AND CONNECT SECURELY. DO NOT USE EXPOSED FASTENERS. <br />PAINTING / FINISHING <br />14. CONTRACTOR TO ENSURE ALL FINISH MATERIALS WILL BE FLUSH AND WASHABLE. INTERIOR FINISH TO CONFORM TO <br />REQUIREMENTS OF CBC 803.5 FLAME SPREAD INDEX 200 MAX. SMOKE DENSITY RATING 450 MAX. ALL DECORATIVE <br />MATERIALS SHALL BE MAINTAINED IN A FLAME RETARDANT CONDITION. ALLOW FOR 3-COLOR INTERIOR PAINT SCHEME, <br />PER IPS #11 ENAMEL AND IPS #9 EPOXY PAINT IN PROCEDURE ROOM, RE-USE ROOM, JANITOR AND MED WASTE ROOMS. <br />15. ALL FINISHED SURFACES SCHEDULED FOR PAINTING TO BE CLEAN AND FREE OF SURFACE DEFECTS AND READY FOR <br />PAINTING. ALL DRYWALL TO BE TAPED, FLOATED, SANDED AND FINISHED WITH A SMOOTH TEXTURE. INTERIOR PAINTING <br />MAY BE APPLIED BY BRUSH, ROLLER, OR SPRAY RIG METHOD ACCORDING TO MANUFACTURER'S SPECIFICATIONS. PAINT <br />SPECS ARE BASED ON BENJAMIN MOORE PAINTS, BUT EQUALS ARE ACCEPTABLE (ALL PAINT COLORS TO BE AS SELECTED <br />BY ARCHITECT/ OWNER) AS FOLLOWS: <br />INTERIOR PAINTS & CLEAR WOOD FINISH: <br />DRYWALL <br /> PRIMER- PVA (USG DRYWALL PRIMER) <br /> FINISH- 2 COATS BENJAMIN MOORE - LATEX ACRYLIC EGGSHELL ENAMEL (PROD. NO. 319) <br />PAINTED WOODWORK <br /> PRIMER - BENJAMIN MOORE - LATEX ENAMEL UNDERBODY (PROD. NO. 345) <br /> FINISH- 2 COATS BENJAMIN MOORE - SEMI GLOSS LATEX ACRYLIC ENAMEL (PROD. NO. 333) <br />CLEAR WOOD FINISH <br /> STAIN - 1 COAT, BENJAMIN MOORE - BENWOOD INTERIOR STAIN (PROD. NO. 237) <br /> FINISH - 2 COATS BENJAMIN MOORE - BENWOOD SATIN FINISH VARNISH (PROD. NO. 404) <br /> SAND LIGHTLY BETWEEN COATS <br />NOTE PAINT FOR CLEANROOM LAB AREAS 228, 279, 280, 281, 282 & 283 AND EXAM ROOMS 111, 231, 232 & 233: <br />LOW/NO VOLATILE ORGANIC COMPOUND (VOC) RELEASE, I.E. A WATERBASED “LOW ODOUR” ACRYLIC OR <br />LATEXPAINT, E.G. DULUX/GLIDDEN LIFEMASTER, BENJAMIN MOORE NATURA OR ULTRA SPEC 500, & BEHR PREMIUM PLUS <br />PAINTS. <br />VINYL WALL COVERING <br />16. WHERE INDICATED, PROVIDE VINYL WALLCOVERING AT SELECTED FOR ACCENT WALLS, ETC. COMPLY WITH FS <br />CCC-W-408, CLASS A, MEDIUM DUTY MIN. 19 OZ: TYPE II 54" WIDTH. REFER TO FINISH SCHEDULE AND VERIFY SELECTION <br />WITH OWNER. USE MILDEW RESISTANT, NON-STAINING, STRIPPABLE ADHESIVE COMPATIBLE WITH COVERING SELECTED. <br />FLOORING <br />17. COORDINATE DELIVERY AND INSTALLATION OF OWNER-SUPPLIED GLUE-DOWN COMMERCIAL CARPET AS SPECIFIED IN <br />THE MATERIALS AND COLOR SCHEDULE. ALLOW SUFFICIENT TIME FOR VERIFICATION THAT ACTUAL SELECTION IS <br />AVAILABLE. CONTRACTOR SHALL INSTALL SCHEDULE BASE MATERIAL AFTER CARPET INSTALLATION. <br />18. SHEET VINYL FLOORING SHALL BE COMMERCIAL GRADE PRODUCT, AS SPECIFIED ON THE FINISH SCHEDULE: ALLOW <br />OWNER TO CONFIRM SELECTION PRIOR TO ORDERING. <br />19. PROVIDE MIN. 3 COATS MANUFACTURER-RECOMMENDED FINISH WAX TO ALL NEW SHEET VINYL FLOORS. CLEAN AND <br />BUFF FINISHED INSTALLATIONS. <br />20. TILE WHERE REQUIRED SHALL BE PORCELAIN CERAMIC TILE,, THINSET OVER LEVELLING COMPOUND. ALLOW FOR <br />SETTING OF INDIVIDUAL TILE ACCENTS & LINERS PER ELEVS. <br />21. SUB-CONTRACTORS SHOULD FULLY INFORM THEMSELF WITH THE WORK INVOLVED AND FIELD CONDITIONS. ALL <br />SUBSTRATE PREPARATION AND ANY REQUIRED CEMENTITIOUS FEATHERING / FLOATING SHALL BE INCLUDED. TEST <br />CONCRETE SLAB SUB-STRATES FOR MOISTURE OFF-GASSING PRIOR TO INSTALLATION OF FLOORING AND PROVIDE MANUF. <br />RECOMMENDED SEALANTS WHERE EXCEEDING INDUSTRY AND MANUF. MAX. RECOMMENDED MOISTURE LEVELS. <br />22.WHERE SHEET VINYL INDICATED PROVIDE INTEGRAL COVED BASE. ENSURE TIGHT FIT AT JUNCTION OF FLOOR AND <br />WALLS. PROVIDE 4" RUBBER BASE FOR OTHER TOP-SET INSTALLATIONS AT ALL AREAS SCHEDULED FOR CARPET (WAITING <br />ROOM, HALLWAYS ETC.). <br />23.NOTE AS A MINIMUM: CLEANROOM LAB AREAS 228, 279, 280, 281, 282 & 283 AND EXAM ROOMS 111, 231, 232 & <br />233: WELDED SHEET VINYL WITH A BONDED SURFACE COATING MUST BE USED. COORDINATE WITH FINISH SCHEDULE. <br />DIVISION 10 <br />SPECIALTY PRODUCTS <br />1.SCHEDULE OF BATHROOM SPECIALTIES: <br />A.TOILET GRAB BAR 36"x42"x1 1/2" DIA. S/STEEL:BOBRICK B-6897, OR EQUAL (QTY: 3) <br />C.TOILET PAPER HOLDER/SEAT DISPENSER:BOBRICK B-2840, OR EQUAL (QTY: 3) <br />D.LIQUID SOAP DISPENSER:BOBRICK B-306, OR EQUAL (QTY:3) <br />E.FRAMELESS LED PERIM. MIRROR :CUSTOM MIRROR (VERIFY SIZE/DESIGN INTERIOR DESIGNER/OWNER) <br />E.COMBO TRASH / TOWEL RECEPTACLE:BOBRICK B-36903 (QTY: 3) <br />F.TOWEL DISPENSER:BOBRICK B-4262 (QTY: 6)(CONFIRM LOCN. W/ OWNER) <br />G.LAVATORY TRAPS/ PIPE INSULATION:TRUEBRO INC. PRE-MOULDED PIPE WRAP (WHITE) HANDI <br />LAV-GUARD" #102 (QTY. 4) <br />1.PROVIDE AND INSTALL BUMPER RAIL AND CORNER GUARDS AS MANUFACTURED BY ACROVYN DOOR AND WALL <br />PROTECTIONS SYSTEMS, IN LOCATIONS INDICATED ON PLANS. <br />2.BUMPER RAIL: MODEL SCR-64, 8" HIGH WITH PERFORMED RETURN TO WALL END CAPS. STANDARD PEBBLETTE PATTERN <br />TEXTURE, COLOR : CG-1. <br />3.CORNER GUARD: MODEL SM-20 SURFACED MOUNTED 3' X 3" X 48" HIGH, STANDARD PEBBLETTE PATTERN TEXTURE, <br />COLOR : CG-1. <br />4.FIRE EXTINGUISHERS / CABINETS: 10 LBS TYPE ABC DRY CHEMICAL, WITH 16 GA. SEMI-RECESSED CABINET WITH WHITE <br />BAKED ENAMEL FINISH, GLASS DOOR AND LOCK, AS STRIKEFIRST CORP. OF AMERICA EL-ELITE ARCHITECTURAL SERIES FIRE <br />EXTINGUISHER CABINET (FIRE-RATED) OR EQUAL. <br />5.CUBICLE CURTAINS AND TRACK: SERIES 6063-T5 TRACK SERIES 7900 BY KIRSH CO. AND TREVIRA POLYESTER <br />FLAME-RETARDANT / PROOFED 12OZ AS UNICUBE CO. SIZED 20% WIDER THAN TRACK LENGTH. INCLUDE CARRIERS, MESH <br />TOP 18" AND TERMINATE 15" ABOVE FLOOR. SEE PLAN FOR LOCATIONS. SEE FINISH SCHEDULE FOR STYLE AND COLOR-WAY <br />. <br />DIVISION 9 <br />METAL STUD FRAMING AND GYPSUM BOARD <br />1. PROVIDE FRAMING COMPONENTS OF SIZES INDICATED TO COMPLY WITH ASTM C 754 . ALL METAL COMPONENTS TO <br />HAVE G40 HOT-DIP GALVANIZED COATING PER ASTM A 525. PROVIDE SIZES AND GRADES INDICATED. ALL METAL <br />FASTENERS TO BE CORROSION RESISTANT. <br />2. ALL METAL WALL STUDS, INCLUDING SMOKE SEALED WALLS SHALL BE 16" ON CENTER, EXTENDING TO UNDERSIDE OF <br />EXISTING GYP. BD. PLENUM CEILING. WHERE PAINTED GYP. BD. FINISH IS INDICATED, INSTALL 5/8" GYPSUM WALLBOARD <br />(LEAD-LINED AS REQ.) SCREWED TO 1/2" RESILIENT CHANNEL FURRING AT 16" O.C., WITH MAXIMUM SCREW SPACING OF <br />7". PARTITIONS INDICATED FULL HT. ARE APPROX. 8'-0" HT. PROVIDE FIRE-RATED SEALANT CONT. AT TOP OF RATED WALLS. <br />ISOLATE STEEL FRAMING FROM BUILDING STRUCTURE TO PREVENT TRANSFER OF LOADING IMPOSED BY STRUCTURAL <br />MOVEMENT. WALLS INDICATED SMOKE / SOUND SEALED SHALL BE SET ON DOUBLE CONTINUOUS BED SEALANT. <br />SHEET NO. <br />2402 <br />REVISIONS: <br />4/12/2024DATE: <br />PROJECT NO. <br />PERMIT NO. <br />Dr <br />. <br /> <br />B <br />e <br />s <br />h <br />a <br />i <br /> <br />A <br />S <br />C <br />20 <br />1 <br />0 <br /> <br />E <br />. <br /> <br />1 <br />s <br />t <br /> <br />S <br />t <br />r <br />e <br />e <br />t <br />, <br /> <br />S <br />t <br />e <br />. <br /> <br />2 <br />0 <br />0 <br /> <br />& <br /> <br />2 <br />1 <br />0 <br />, <br /> <br />S <br />a <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />Ne <br />w <br /> <br />A <br />m <br />b <br />u <br />l <br />a <br />t <br />o <br />r <br />y <br /> <br />C <br />a <br />r <br />e <br /> <br />F <br />a <br />c <br />i <br />l <br />i <br />t <br />y <br /> <br />T <br />e <br />n <br />a <br />n <br />t <br /> <br />I <br />m <br />p <br />r <br />o <br />v <br />e <br />m <br />e <br />n <br />t <br />10/31/25 <br />REN. DATE <br /> C-26955 <br />OIF <br />NRI <br />LOFCA <br />SAUNDERS <br />TATS <br />E <br />CETIHCADESRCILEN <br />NIALL F. <br />A <br />T <br />1 <br />A5.0 <br />SPECIFICATIONS <br />SCALE: NTS <br />A-5.0 <br />SPECIFICATIONS <br />2010 E First St Units #200 <br />& 2102/19/2025