PROJECT NAME
<br />SHEET TITLE
<br />SHEET NUMBER
<br />PROJECT TITLE
<br />JOBSITE ADDRESS
<br />JIMENEZ
<br />RESIDENCE
<br />4.400 DC kW
<br />4.048 KW CEC-AC RATING
<br />STRING INVERTER SYSTEM
<br />1919
<br />N SPURGEON ST,
<br />SANTA ANA, CA
<br />92706
<br />CONTRACTOR
<br />TITAN SOLAR POWER CA INC
<br />525 W BASELINE ROAD
<br />MESA, AZ 85210
<br />(855) 729-7652
<br />WWW.TITANSOLARPOWER.COM
<br />PROJECT ID# TSP157692
<br />DATE DESCRIPTION
<br />REVISION
<br />DATE
<br />DRAWN04-20-23 REVISION
<br />DESIGN BY: RD
<br />CAD
<br />F O R C A L I I N C .
<br />SHELLEY V CALUAG
<br />cadforcali@gmail.com
<br />323-698-4207
<br />SP: Ascend Energy
<br />CRCR106 & Business and
<br />Professions Code 5536.2
<br />A0
<br />PROJECT INFO
<br />VICINITY MAP
<br />PV NOTES
<br />VICINITY MAP
<br />AERIAL VIEW
<br />PROJECT SITE INFORMATION
<br />NAME: JESUS JIMENEZ
<br />ADDRESS:1919 N SPURGEON ST,
<br />SANTA ANA, CA 92706
<br />PHONE: (714) 651-1532
<br />EMAIL: Jrjimenez190466@gmail.com
<br />APN:
<br />00315357
<br />(ORANGE COUNTY)
<br />UTILITY: SCE
<br />AHJ: SANTA ANA CITY (CA)
<br />BUILDING INFO
<br />OCCUPANCY: R3-SFD CONSTRUCTION TYPE: VB
<br /># OF STORIES: 2 BLDG AREA (SQFT): 1138
<br />SPRINKLERS: NONE ROOF AREA (SQFT): 1348
<br />ENGINEERING CRITERIA FOR RACKING
<br />DESIGN WIND SPEED: 110 MPH
<br />WIND EXPOSURE CATEGORY: B
<br />GROUND SNOW LOAD: O PSF
<br />PROJECT SCOPE
<br />INSTALLATION OF ROOF MOUNT SOLAR PV SYSTEM
<br />PV EQUIPMENT QTY MODEL NO AND MANUFACTURER
<br />MODULES:11 MODEL#: HY-DH108P8-400
<br />400W HYPERION MODULES
<br />OPTIMIZERS:11 S440 SOLAREDGE OPTIMIZERS
<br />AC COMBINER:1 SE3800H-US (240V)
<br />SOLAREDGE HD INVERTER
<br />SYSTEM SIZE:4.400 DC kW RATING
<br />4.048 CEC AC RATING
<br />ARRAY AREA:20.35 SQFT x 11 = 223.90 SQFT
<br />MAIN SERVICE PANEL INFORMATION
<br />UTILITY: SCE
<br />EXISTING: YES UPGRADE: NO
<br />BUS RATING: (E)200A MAIN BREAKER: (E)200A
<br />PHASE: 1PH MB POSITION: END
<br /># OF WIRES: 3 DERATE?: NO
<br />VOLTAGE: 240V DERATE SIZE: N/A
<br />UTILITY FED: OH
<br />METER#: 222010-109642
<br />SHEET INDEX
<br />A0 PROJECT INFO, VICINITY MAP, NOTES
<br />A1 SITE PLAN
<br />A2 MOUNTING ROOF PLAN
<br />E1 SINGLE LINE DIAGRAM
<br />E2 ELECTRICAL CALCULATIONS
<br />E3 - E3.1 REQUIRED SIGNAGE & DIRECTORY
<br />E4 - E4.1 MODULE DATA SHEET & CERTIFICATION
<br />E5 - E5.1 INVERTER DATA SHEET & CERTIFICATION
<br />E6 OPTIMIZER DATA SHEET
<br />S1 - S1.1 STANCHION DATA SHEET
<br />S2 RACKING DATA SHEET
<br />S3 - S3.3 RACKING ENGINEERING
<br />S4 RACKING GROUNDING
<br />S5 RACKING CERTIFICATION
<br />APPLICABLE CODES
<br />ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL COMPLY
<br />WITH THE FOLLOWING 2022 APPLICABLE CODES
<br />2022 CA BUILDING CODES (CBC)
<br />2022 CA RESIDENTIAL CODES (CRC)
<br />2022 CA MECHANICAL CODES (CMC)
<br />2022 CA PLUMBING CODES (CPC)
<br />2022 CA FIRE CODES (CFC)
<br />2022 CA ELECTRICAL CODES (CEC)
<br />2022 CA ENERGY CODES (CEnC)
<br />2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGreen)
<br />4.400 DC kW SOLAR PV STRING INVERTER SYSTEM - ROOF MOUNT
<br />1919 N SPURGEON ST, SANTA ANA, CA 92706
<br />JIMENEZ RESIDENCE
<br />SOLAR PHOTOVOLTAIC SYSTEM NOTES
<br />2022 CODE REFERENCE
<br />CEC 110.2
<br />CEC 110.3
<br />ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED TESTING LABORATORY AND INSTALLED PER
<br />THE LISTING REQUIREMENTS AND THE MANUFACTURER'S INSTRUCTIONS
<br />ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF MOUNTED TRANSITION BOXES AND
<br />SWITCHES.
<br />CEC 110.26 WORKING CLEARANCES TO BE PROVIDED AT NEW AND EXISTING ELECTRICAL EQUIPMENT
<br />CEC ARTICLE 250 ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED
<br />ALL PV CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL HAVE PROTECTION AGAINST OVERCURRENT
<br />CEC 690.13
<br />CEC 690.15
<br />DISCONNECTING MEANS OF THE PV SYSTEM (INCLUDING RAPID SHUTDOWN INITIATION) SHALL BE LOCATED IN
<br />READILY ACCESSIBLE LOCATION NEAR THE EQUIPMENT
<br />CEC 690.12 RAPID SHUTDOWN EQUIPMENT TO COMPLY WITH CEC 690.12.
<br />CEC 705.40
<br />THE UTILITY-INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED
<br />ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND SHALL
<br />REMAIN IN THAT STATE UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN
<br />RESTORED
<br />CEC 310.10(D)
<br />CEC 690.31(A) TO (F)
<br />ALL CONDUCTORS IN EXPOSED OUTDOOR LOCATIONS SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT
<br />SUNLIGHT AND FOR THE APPLICATION.
<br />CEC 690.31(C INSULATION OF EXPOSED CONDUCTORS UNDER THE MODULES SHALL BE USE-2 OR PV-WIRE TYPE FOR PV
<br />SYSTEMS
<br />CEC 110.14 FINE-STRANDED CABLE CONNECTIONS MUST BE MADE IN LUGS AND TERMINALS LISTED AND MARKED FOR THE
<br />USE,
<br />CEC 690.31(B) ALL PV CIRCUIT CONDUCTORS SHALL BE MARKED ON EACH END AND GROUPED FOR UNIQUE IDENTIFICATION
<br />CEC 200.6, CEC
<br />200.7 CEC 400.22
<br />CEC 250.119
<br />CEC 400.23
<br />CEC 310.110(C)
<br />ALL GROUNDED, (NEUTRAL), CONDUCTORS' INSULATION SHALL BE SOLID WHITE, GRAY, OR WITH 3-WHITE
<br />STRIPES, CEC 200.6, 200.7, & 400.22; AND ALL GROUNDING CONDUCTORS SHALL BE OF BARE WIRE WITHOUT
<br />COVERING, OR WITH INSULATION OF GREEN OR GREEN WITH YELLOW STRIPES, CEC 250.119 & 400.23. THE
<br />COLOR OF UNGROUNDED CONDUCTORS SHALL BE OTHER THAN FOR GROUNDED, (NEUTRAL), AND
<br />GROUNDING CONDUCTORS, CEC 310.110(C).
<br />CEC 711.11(C)MAXIMUM CONDUCTOR LENGTH BETWEEN SUPPLY SIDE CONNECTION AND OVERCURRENT PROTECTION IS 10
<br />FEET
<br />CEC 705.12(B)CONNECTIONS ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER SOURCE(S) AT ANY
<br />DISTRIBUTION EQUIPMENT ON THE PREMISES
<br />CFC 605.11.2 DC WIRING INSIDE A BUILDING MUST BE IN METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, OR CABLE
<br />SHEATHINGS
<br />CEC 250.97 METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, AND CABLE SHEATHS CONTAINING CIRCUITS OVER
<br />250-VOLTS TO GROUND MUST BE BONDED
<br />CEC 314.15 ALL EXTERIOR CONDUIT, FITTINGS AND BOXES SHALL BE RAIN TIGHT AND APPROVED FOR USE IN WET LOCATIONS
<br />CEC 690.31(C)(5)
<br />CEC 110.14.
<br />FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES OR
<br />CONNECTOR THAT ARE IDENTIFIED AND LISTED FOR SUCH USE
<br />CEC 690.33 (D)(2)
<br />CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY ACCESSIBLE AND
<br />OPERATING AT OVER 30 VOLTS SHALL REQUIRE TOOL TO OPEN AND MARKED “DO NOT DISCONNECT UNDER
<br />LOAD” OR “NOT FOR CURRENT INTERRUPTING”
<br />CEC 690.45
<br />CEC 250.122
<br />EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES SMALLER THAN 6 AWG SHALL BE PROTECTED FROM
<br />PHYSICAL DAMAGE BY A RACEWAY OR CABLE ARMOR, CEC 690.46 & 250.120(C).
<br />CEC 705.32 WHERE PROTECTION IS INSTALLED IN ACCORDANCE WITH 230.95, THE OUTPUT OF AN INTERACTIVE SYSTEM
<br />SHALL BE CONNECTED TO THE SUPPLY SIDE OF THE GROUND-FAULT PROTECTION.
<br /> CEC 690.31(G)(4)THE MARKINGS, "WARNING: PHOTOVOLTAIC POWER SOURCE", FOR DC RACEWAYS AND CABLE ASSEMBLIES
<br />MUST BE AT 10' O.C.; AND BENDS, ABOVE OR BELOW PENETRATIONS OF ROOFS, CEILINGS, WALLS, OR BARRIERS
<br />CEC 300.4 CABLES/WIRES THAT ARE SUBJECT TO PHYSICAL DAMAGE, SUCH AS THOSE NOT LOCATED UNDER THE MODULES,
<br />MUST BE PROTECTED
<br />CEC 310.15
<br />WHERE RACEWAYS OR CABLES ARE EXPOSED TO DIRECT SUNLIGHT ON OR ABOVE ROOFTOPS, RACEWAYS OR
<br />CABLES SHALL BE INSTALLED A MINIMUM DISTANCE ABOVE THE ROOF TO THE BOTTOM OF THE RACEWAY OR
<br />CABLE OF 7∕8 IN. WHERE THE DISTANCE ABOVE THE ROOF TO THE BOTTOM OF THE RACEWAY IS LESS THAN 7∕8
<br />IN., A TEMPERATURE ADDER OF 60°F SHALL BE ADDED TO THE OUTDOOR TEMPERATURE TO DETERMINE THE
<br />APPLICABLE AMBIENT TEMPERATURE FOR APPLICATION OF THE CORRECTION FACTORS IN TABLE 310.15(B)(2)(A)
<br />OR TABLE 310.15(B)(2)(B).
<br />CEC 690.56(C)IDENTIFICATION OF POWER SOURCE RAPID SHUTDOWN AND LABELING SHALL BE IN ACCORDANCE WITH CEC
<br />690.56(C).
<br />CEC 690.31(G)(4)LABELS SHALL BE REFLECTIVE, AND ALL LETTERS SHALL BE CAPITALIZED AND SHALL BE A MINIMUM HEIGHT OF 3/8''
<br />IN WHITE ON A RED BACKGROUND. CEC 690.31(G)(4)
<br />690.56(C)IDENTIFICATION OF POWER SOURCE RAPID SHUTDOWN AND LABELING SHALL BE IN ACCORDANCE WITH CEC
<br />690.56(C).
<br />WHEN THE MAIN CIRCUIT BREAKER IS DERATED, A PERMANENT MARKING MUST BE PROVIDED ON THE
<br />PANELBOARD TO INDICATE THAT THE MAIN CIRCUIT BREAKER HAS BEEN DOWNSIZED TO _______ AMPS, DO NOT
<br />UPSIZE IT.
<br />CRC R324.7
<br />CRC R302.1.
<br />GROUND-MOUNTED PV SYSTEMS MUST HAVE A CLEAR, BRUSH-FREE AREA OF 10-FEET AND A FIRE SEPARATION
<br />DISTANCE OF 5-FEET MINIMUM TO OTHER STRUCTURES AND PROPERTY LINES
<br />EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, & VENTILATIONS INTAKE AIR OPENINGS SHALL NOT BE
<br />COVERED OR BLOCKED BY THE SOLAR PHOTOVOLTAIC SYSTEM.
<br />CPC 906.1
<br />EXISTING DWV PLUMBING VENT TERMINATIONS THAT ARE HORIZONTALLY LOCATED CLOSER THAN 12" FROM THE
<br />PROPOSED MODULES, MUST BE REROUTED, OR MUST BE EXTENDED A MINIMUM OF 6" ABOVE THE SURFACE OF
<br />THE MODULES
<br />CMC 802.6.1(1)
<br />CPC 509.6.1(1)
<br />EXISTING B-VENT TERMINATIONS, FOR FUEL BURNING APPLIANCES, WHERE ADJACENT TO THE PROPOSED
<br />MODULES, MUST BE EXTENDED 12" ABOVE THE MODULES' TOP SURFACE, CMC 802.6.1(1) & CPC 509.6.1(1).
<br />CEC 250.52(A)(5)
<br />CEC 250.53(G)
<br />GROUNDING ROD ELECTRODES SHALL BE MINIMUM 5/8’’ IN DIAMETER AND INSTALLED 8’ MINIMUM IN
<br />CONTACT WITH SOIL
<br />CEC 250.104 FOR ELECTRICAL SERVICE REPLACEMENTS, BONDING TO THE METAL PIPES OF NATURAL GAS, HOT WATER, AND
<br />COLD WATER MUST BE PROVIDED
<br />PROPOSED LOCATIONS OF ELECTRICAL SERVICE REPLACEMENTS MUST ALSO BE APPROVED BY THE ELECTRICAL
<br />UTILITY COMPANY.
<br />CRC R314.1
<br />CRC R315.1
<br />APPROVED SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN THE DWELLING UNIT AND SHALL
<br />BE FIELD VERIFIED EITHER THROUGH FINAL BUILDING INSPECTION. SMOKE ALARMS ARE REQUIRED TO BE
<br />INSTALLED IN ALL BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE.
<br />CARBON MONOXIDE ALARMS ARE REQUIRED OUTSIDE EACH BEDROOM AND AT LEAST ONE ON EACH FLOOR
<br />OF THE HOUSE.
<br />CRC R324.3
<br />PHOTOVOLTAIC (PV) SYSTEMS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH SECTIONS R324.3.1
<br />THROUGH R324.7.1 AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE ELECTRICAL PORTION OF
<br />SOLAR PV SYSTEMS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL
<br />CODE.
<br />CRC R324.6
<br />ROOF ACCESS, PATHWAYS AND SETBACK REQUIREMENTS SHALL BE PROVIDED IN ACCORDANCE WITH
<br />SECTIONS R324.6.1 THROUGH R324.6.2.1. ACCESS AND MINIMUM SPACING SHALL BE REQUIRED TO PROVIDE
<br />EMERGENCY ACCESS TO THE ROOF, TO PROVIDE PATHWAYS TO SPECIFIC AREAS OF THE ROOF, PROVIDE FOR
<br />SMOKE VENTILATION OPPORTUNITY AREAS, AND TO PROVIDE EMERGENCY EGRESS FROM THE ROOF.
<br />A LADDER MUST BE PROVIDED FOR INSPECTIONS IN ACCORDANCE WITH CAL-OSHA REGULATIONS, SECURED
<br />AND EXTENDING 3' ABOVE THE ROOF. LADDERS SHALL BE OSHA APPROVED AND SECURED TO THE STRUCTURE
<br />FOR INSPECTION PURPOSES.
<br />CONTRACTORS ARE REQUIRED TO BE PRESENT FOR THE FIRST AND/OR FINAL INSPECTIONS.
<br />ALL OF THE REQUIRED MARKINGS, SIGNS, AND LABELS MUST BE INSTALLED ON ALL EQUIPMENT PRIOR TO ANY
<br />INSPECTIONS.
<br />PLAN CHECK AND PERMIT FOR PV SYSTEM AND ASSOCIATED EQUIPMENT ONLY.
<br />ALL PROJECTS SUBJECT TO FIELD VERIFICATION FOR CODE COMPLIANCE.
<br />NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM.
<br />PROJECT SITE
<br />STRUCTURAL ONLY
<br />www.vincise.com
<br />S T R U C T U R A L E N G I N E E R S
<br />4.28.2023
<br />The scope of the plans is for the installation of the solar
<br />photovoltaic system only and the approval is subject to
<br />compliance with all applicable city and state codes and
<br />regulations regarding construction. The approval of the
<br />plans does not constitute any certification of the accuracy,
<br />completeness, or building permit status of the existing
<br />buildings and structures as shown.
<br />Bldg# 101115455
<br />Elec# 20179904
<br />Issued 06/14/23
<br />1919 N Spurgeon St
<br />06/15/23
|