Laserfiche WebLink
Step 1: Mounting and Grounding the Power <br />Optimizers <br />For each of the power optimizers1: <br /> 1. Determine the power optimizer mounting location and use the power optimizer <br />mounting brackets to attach the power optimizer to the support structure (See <br />Figure 5). It is recommended to mount the poweroptimizer in a location protected <br />from direct sunlight. For frame-mounted power optimizers follow the instructions <br />supplied with the optimizers, or refer to <br />https://www.solaredge.com/sites/default/files/installing_frame_mounted_power_ <br />optimizers.pdf. <br /> 2. If required, mark the mounting hole locations and drill the hole. <br />CAUTION! <br />Do not drill through the power optimizer or through the mounting holes. The drilling vibrations can <br />damage the power optimizer and will void the warranty. <br /> <br />ATTENTION! <br />Ne pas percer à travers la optimiseur de puissance ou ses trous de fixation. Les vibrations qui en <br />résulteraient peuvent endommager la optimiseur de puissance. <br /> 3. Attach each power optimizer to the rack using M6 (1/4'') stainless steel bolts, nuts and washers or <br />other appropriate mounting hardware.  Apply torque of 9.5 N*m / 7 lb*ft. <br />For 3NA  series power optimizes, SolarEdge recommends mounting the power optimizer on a rail with <br />the smooth side facing out, so that the power optimizer body will prevent its rotation. <br /> 4. Use the following methods2 to ground the power optimizer: <br />WARNING! <br />The metallic enclosure of the power optimizer must be grounded in accordance with the <br />requirements of the local and national codes. <br /> <br />AVERTISSEMENT! <br />L'enceinte métallique de l’optimiseur de puissance doit être mise à la terre en accord avec les <br />régulations locales et nationales. <br /> l For mounting on a grounded metal rail: Use the provided 5/16'' stainless steel grounding star <br />washer between the railing and the flat side of the mounting bracket.  The grounding washer <br />should break through the anodize coating of the railing to ensure low resistive connection. Apply <br />torque of 9.5 N*m / 7 lb*ft. See Figure 5. <br />1Not applicable to smart modules. <br />2These methods have been evaluated by a nationally recognized testing laboratory as part of the optimizer evaluation. <br />The SolarEdge-supplied grounding lug kit has been evaluated only for use with SolarEdge power optimizers. It is not <br />intended or listed to be used as a general purpose grounding lug with other electrical equipment. <br />Chapter 2:InstallingthePower Optimizers <br />SinglePhaseInverter with HD-WaveTechnologyInstallation MAN-01-00306-1.1 19 <br />Figure 5: Power optimizer installation and grounding using a star washer <br /> l For mounting on rails with sliding nut fasteners: If the star washer cannot be used, use the <br />SolarEdge grounding plate (purchased separately) between the railing and the flat side of the <br />mounting bracket. Use mounting specific hardware as needed. Apply torque of 9.5 N*m / 7 lb*ft. <br />See Figure 6 <br />Figure 6: Power optimizer installation and grounding using a grounding plate <br /> l For mounting on un-grounded structures (such as a wooden structure): If the star washer or <br />the plate cannot be used, use the SolarEdge grounding lug (purchased separately) with an <br />equipment-grounding conductor  according to the supplied instructions. The grounding terminal <br />accepts a wire size of 6-14 AWG, and must be sized for equipment grounding per NEC 250.122 <br />requirements. Tighten the screws connecting the power optimizer to the frame and the <br />grounding terminal screw. Apply torque of 9.5 N*m / 7 lb*ft. See Figure 7 <br />Figure 7: Power optimizer grounding terminal <br /> 5. Verify that each power optimizer is securely attached to the module support structure. <br />SinglePhaseInverter with HD-WaveTechnologyInstallation MAN-01-00306-1.120 <br />Step1:MountingandGroundingthePower Optimizers <br />2110 W 7th St - <br />2017778512/28/22