9. All conductor exposed to weather shall be <br />listed and identified for use in direct sunlight. <br />[NEC 690.31(B), 310.8(D)] <br />10. The module conductors must be type USE-2 <br />or listed for photovoltaic (PV) wire. (NEC <br />690.31(B)) <br />11. All conductors shall be marked on each end <br />for unique identification. <br />12. PV module negative shall be grounded. All <br />grounded conductor shall be properly color <br />identified as white. [NEC 200.6] <br />13. PV system connected on the load side of the <br />service disconnecting means of the other <br />source(s) at any distribution equipment on the <br />premises shall meet the following [NEC <br />705.12(D)]: <br />14. Each source connection shall be made at a <br />dedicated circuit breaker or fusible disconnecting <br />means. [NEC 705.12(D)(1)] <br />15. The sum of the ampere rating of the <br />overcurrent devices in circuits supplying power to <br />the busbar or conductor shall not exceed 120% <br />of the rating of busbar or conductor. [NEC <br />705.12(D)(2)] <br />16. The interconnection point shall be on the line <br />side of all ground-fault protection equipment. <br />[NEC 705.12(D)(3)] <br />17. Equipment containing overcurrent devices in <br />circuits supplying power to a bus bar or <br />conductor shall be marked to indicate the <br />presence of all sources. [NEC 705.12(D)(4)] <br />18. Circuit breaker, if backfed, shall be suitable <br />for such operation. [NEC 705.12(D)(5)] <br />19. To minimize overheating of the busbar in <br />panelboard, the panelboard main circuit breaker <br />and the PV power source circuit breaker shall be <br />physically located at the opposite end of the <br />busbar. <br />20. All the NEC required warning signs, markings, <br />and labels shall be posted on equipment and <br />disconnects prior to any inspections to be <br />performed by the Building Department inspector. <br />21. Metallic raceways or metallic enclosures are <br />required wiring method for inside a building for <br />PV system. [NEC 690.31(E)] <br />SOLAR PHOTOVOLTAIC SYSTEM NOTES: <br />22. Flexible, fine-stranded cables shall be <br />terminated only with terminals, lugs, devices or <br />connector that are identified and listed for such use. <br />[NEC 690.31(F)] <br />23. Connectors shall be of latching or locking type. <br />Connectors that are readily accessible and operating <br />at over 30 volts shall <br />24. Require tool to open and marked "Do Not <br />Disconnect Under Load" or "Not For Current <br />Interrupting". [NEC 690.33(C) & (E)(2)] <br />25. Equipment grounding conductor for PV modules <br />smaller than 6AWG shall be protected from physical <br />damage by a raceway or cable armor. [NEC 690.46 <br />& 250.120(C)] <br />26. Equipment grounding conductor for PV systems <br />without Ground Fault Protection (GFP) and installed <br />on non-dwelling unit must have ampacity of at least <br />2 times the temperature and conduit fill corrected <br />circuit conductor ampacity. [NEC 690.45(B)] <br />27. Fine stranded cables used for battery terminals, <br />devices, and connections require lugs and terminals <br />listed and marked for the use. [NEC 690.74] <br />28. Grounding bushings are required around <br />pre-punched concentric knockouts on the DC side of <br />the system (NEC 250.64 C) <br />29. Grounding electrode conductor will be <br />continuous, expect for splices or joints at busbars <br />within listed equipment. <br />(NEC 250.64 C) <br />30. All smoke alarms, Carbon monoxide alarms and <br />audible notification devices shall be listed and <br />labeled in accordance with UL 217 and UL 2034. <br />They will be installed in accordance with NFPA 72 <br />and NFPA 720. (CRC 2019 R314 & R315). <br />31. 2019 California Residential Code (CRC) requires <br />that Smoke alarms and Carbon Monoxide Alarms be <br />retrofitted into the existing dwelling. These Smoke <br />alarms are required to be in all bedrooms, outside <br />each bedroom, and at least one on each floor of the <br />house. Carbon Monoxide alarms are required to be <br />retrofitted outside each bedroom and at least one <br />on each floor of the house. These alarms may be <br />solely battery operated if the Photovoltaic project <br />does not involve the removal of interior wall and <br />ceiling finishes inside the home, otherwise, the <br />alarms must be hard wired and interconnected. <br />ABBREVIATIONS <br />PR <br />O <br />J <br />E <br />C <br />T <br />: <br />DRAWN BY: <br />DATE: <br />SOLAR MAX RENEWABLE <br />ENERGY PROVIDER INC <br />3080 12TH STREET, <br />RIVERSIDE, CA 92507 <br />TEL: (951) 300-0788 <br />FAX: (951) 213-3099 <br />CLASS: C-46 LIC# 972048 <br />CLASS: C-10 LIC# 999740 <br />E1.1 <br />SHEET NUMBER: <br />APN#: <br />MODULES: <br />INVERTER: <br />AHJ: <br />SYSTEM kW: <br />PR <br />O <br />P <br />O <br />S <br />E <br />D <br /> <br />S <br />Y <br />S <br />T <br />E <br />M <br /> <br />S <br />I <br />Z <br />E <br /> <br />I <br />S <br /> <br /> <br />11 <br />. <br />6 <br />K <br />W <br />SO <br />L <br />A <br />R <br /> <br />P <br />H <br />O <br />T <br />O <br />V <br />O <br />L <br />T <br />A <br />I <br />C <br /> <br />S <br />Y <br />S <br />T <br />E <br />M <br /> <br />F <br />O <br />R <br />: <br />AL <br />E <br />X <br /> <br />W <br />O <br />N <br />G <br /> <br />& <br /> <br />N <br />G <br />A <br />N <br /> <br />D <br />O <br />A <br />N <br />(7 <br />1 <br />4 <br />) <br /> <br />6 <br />8 <br />4 <br />- <br />4 <br />4 <br />8 <br />2 <br /> 2 <br />2 <br />6 <br />2 <br /> <br />N <br /> <br />L <br />Y <br />O <br />N <br /> <br />S <br />T <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />BUILDING HT: <br />MOUNTING <br />HARDWARE: <br />C.BE <br />1/4/2023 <br />39605622 <br />2 STORY <br />Q.PEAK DUO <br />BLK-ML-G10+ 400 <br />11.6KW <br />QUICK MOUNT <br />IQ8A-72-2-US <br />CITY OF SANTA ANA <br />All materials, equipment, installation and work <br />shall comply with the following applicable codes: <br />x 2022 CA Building Code <br />x 2022 CA Residential Code <br />x 2022 CA Electrical Code <br />x 2022 CA Mechanical Code <br />x 2022 CA Plumbing Code <br />x 2022 CA Fire Code <br />x 2022 Building Energy Efficiency Standards <br />x Local Authority Having Jurisdiction <br />x Local Fire Authority Having Jurisdiction <br />1. Existing plumbing vents, skylights, exhaust <br />outlets, ventilations intake air openings shall not <br />be covered by the solar photovoltaic system. <br />2. Equipment. Inverters, motor generators, <br />photovoltaic modules, photovoltaic panels, ac <br />photovoltaic modules, source-circuit combiners, <br />and charge controllers intended for use in <br />photovoltaic power systems shall be identified <br />and listed for the application. (NEC 690.4(D)) <br />3. All outdoor equipment shall be NEMA 3R rated, <br />including all roof mounted transition boxes and <br />switches. <br />4. All equipment shall be properly grounded and <br />bonded in accordance with NEC article 250. <br />5. All circuits connected to more than one source <br />shall have overcurrent devices located so as to <br />provide overcurrent protection from all sources. <br />[NEC 690.9(A)] <br />6. All photovoltaic (PV) modules shall be mounted <br />on the roof. Additional equipment of the PV <br />system shall be located outside the building near <br />the main electrical services. [NEC 690.14(C)] <br />7. The utility interactive inverters shall <br />automatically de-energize its output to the <br />connected electrical production and distribution <br />network upon loss of voltage in the system and <br />shall remain in that state until the electrical <br />production and distribution network voltage has <br />been restored.[NEC 690.61] <br />8. Due to the fact that PV modules are energized <br />whenever exposed to light, PV contractor shall <br />disable the array during installation and service <br />by short circuiting, open circuiting, or covering <br />the array with opaque covering. [NEC 690.18] <br />2262 N Lyon St - <br />2017948205/30/23