Laserfiche WebLink
By: T.S. <br />Date: 9/18/23 <br />Existing Loads: <br />Roof Design Loads: <br />Roofing = 4.0 p.s.f.Composition roofing <br />Sheathing = 1.5 p.s.f.1/2" Plywood <br />Framing = 1.5 p.s.f.2x6 Rafters <br />Misc = 1.0 p.s.f. <br />DLr1 =8.0 p.s.f.Roofing Dead Load (applied to top of rafters/trusses only) <br />Ceiling = 2.0 p.s.f.Drywall and framing <br />DLr2 =10.0 p.s.f.Total Existing Roof Dead Load <br />LLr = 20.0 p.s.f.Roof Live Load (Per C.B.C, Table 1607.1) <br />SL = 0.0 p.s.f.Snow Load <br />Floor Design Loads: (if applicable) <br />Flooring = 10.0 p.s.f.Weight of floor finish <br />Sheathing = 2.2 p.s.f.3/4" plywood <br />Framing = 2.0 p.s.f.2x framing or manufactured floor truss <br />Interior Partitions = 15.0 p.s.f.2x framed walls with drywall finish each side <br />Ceiling = 5.0 p.s.f.Drywall ceiling finish below <br />Misc. = 0.8 p.s.f. <br />DLf = 35.0 p.s.f.Total Existing Floor Dead Load <br />Proposed Loads: <br />Panels = 2.7 p.s.f.weight of panels including rack system <br />DLr1_proposed =10.7 p.s.f.Proposed Roof Dead Load (applied to top only) <br />DLr2_proposed =12.7 p.s.f.Total Proposed Roof Dead Load <br />LLr_proposed = 0.0 p.s.f. <br />Check Proposed Gravity Loads: <br />Total Existing Roof Load <br />Wex = (DLr1 + LLr) (Aroof) =25.2 kips <br />Total Proposed Roof Load <br />Wprop = (DLr1 + LLr) (Aroof - Aarray) + (DLr1_proposed + LLr_proposed) (Aarray) =23.2 kips <br />Proposed Load Demand <br />Gravity Loads <br />Roof Live Loads need not be applied to the area covered with by PV panel where the <br />clear space between the panels and the roof sureface is 24in or less, 1607.13.5.1 item 1 <br />Exception <br />Wprop - W ex =-8.10% TOTAL DECREASE IN GRAVITY LOADS, PANELS OK!Wex <br />9/18/2023 4:08 PM <br />4 of 7 <br />©McPherson Engineering <br />2530 S Pacific Ave <br />10/3/2023