<br /> <br />To: City of Palmdale <br />Project name: Anthony Garcia <br />Project Address: 38962 Edgemont Drive <br /> <br /> <br /> <br />RESPONSE SHEET <br /> <br /> <br />1. Added note: All work done in a neat and workmanlike manner. (CEC 110.12) PV-2 <br />2. Specified AC disconnect is rapid shutdown. PV-2 <br />3. Specified green line is conduit run. No expansion fittings will be installed. PV-3 <br />4. Corrected size of main breaker. Interconnection to be load side breaker. MPU to 150A busbar <br />with 100A main breaker. PV-6 <br />5. Added note: Main panel will be installed at the opposite end of the busbar from the main <br />breaker PV-6 <br />6. Added note: Warning inverter output connection. Do not relocate this overcurrent device. (CEC <br />705.12 D7) PV-6 <br />7. Provided photo of existing panel PV-9 <br />Thank you <br /> <br />Complete Solar <br />3000 Executive Pkwy <br />Suite #504 <br />San Ramon, CA 94583 <br />Phone Number: <br /> (877) 299-4943 <br />Signature: <br />Email: <br />Roberto Lopez (May 9, 2023 20:15 PDT) <br />2826 N Ridgewood St- <br />101118523 & 201823013/11/2024