MARKING IS REQUIRED ON ALL INTERIOR AND <br />EXTERIOR DC PV CONDUIT, RACEWAYS, ENCLOSURES, <br />CABLE ASSEMBLIES, AND JUNCTION BOXES TO ALERT <br />THE FIRE SERVICE TO AVOID CUTTING THEM. MARKING <br />SHALL BE PLACED EVERY 10 FEET, AT TURNS AND <br />ABOVE AND/OR BELOW PENETRATIONS, AND AT ALL PV <br />COMBINER AND JUNCTION BOXES. [CEC 690.31(D)(2)] <br />REFLECTIVE WEATHER RESISTANT MATERIAL SUITABLE <br />FOR THE ENVIRONMENT (DURABLE ADHESIVE <br />MATERIALS MUST MEET THIS REQUIREMENT) <br />MARKING CONTENT AND FORMAT <br />PER [ CEC 110.21(B)] WITH REFERENCE <br />TO ANSI Z535.4-2011 <br />-BACKGROUND PER ANSI Z535.4-2011 <br />-LETTERING PER ANSI Z535.4-2011 <br />-MINIMUM 3/8” LETTER HEIGHT <br />-ALL CAPITAL LETTERS <br />-ARIAL OR SIMILAR FONT, NON BOLD <br />MARKING PV CIRCUIT <br />E9 <br />SHEET NUMBER: <br />SE <br />M <br />P <br />E <br />R <br /> <br />S <br />O <br />L <br />A <br />R <br />I <br />S <br />18 <br />0 <br />5 <br /> <br />J <br />O <br />H <br />N <br /> <br />T <br />O <br />W <br />E <br />R <br />S <br /> <br />A <br />V <br />E <br />EL <br /> <br />C <br />A <br />J <br />O <br />N <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />0 <br />2 <br />0 <br />C- <br />1 <br />0 <br /> <br />L <br />I <br />C <br /> <br /># <br /> <br />9 <br />7 <br />8 <br />1 <br />5 <br />2 <br />Li <br />c <br />. <br /> <br />H <br />o <br />l <br />d <br />e <br />r <br /> <br />D <br />i <br />g <br />i <br />t <br />a <br />l <br />l <br />y <br /> <br />S <br />t <br />a <br />m <br />p <br />e <br />d <br />PR <br />O <br />J <br />E <br />C <br />T <br /> <br />F <br />O <br />R <br />: <br /> <br />PR <br />O <br />P <br />O <br />S <br />E <br />D <br /> <br />DRAWN BY: <br />DATE: <br />(DC) kW: <br />PROJECT #: <br />Jo <br />h <br />n <br /> <br />A <br />l <br />m <br />o <br />n <br />d <br />FIN-S <br />11-09-2023 <br />79664 <br />10.800 <br />GA <br />B <br />R <br />I <br />E <br />L <br />L <br />A <br /> <br />C <br />A <br />R <br />D <br />O <br />Z <br />A <br />- <br />F <br />A <br />V <br />A <br />R <br />A <br />T <br />O <br /> <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />4 <br /> <br />31 <br />1 <br />4 <br /> <br />S <br /> <br />R <br />I <br />T <br />A <br /> <br />W <br />A <br />Y <br />(2 <br />1 <br />0 <br />) <br /> <br />5 <br />4 <br />2 <br />- <br />2 <br />5 <br />0 <br />2 <br />AP <br />N <br />- <br />4 <br />1 <br />2 <br />0 <br />1 <br />3 <br />1 <br />9 <br />SO <br />L <br />A <br />R <br /> <br />P <br />H <br />O <br />T <br />O <br />V <br />O <br />L <br />T <br />A <br />I <br />C <br /> <br />SY <br />S <br />T <br />E <br />M <br /> <br />S <br />I <br />Z <br />E <br />: <br /> <br />10 <br />. <br />8 <br />0 <br />0 <br /> <br />k <br />W <br /> <br />D <br />C <br /> <br />P <br />V <br />MA <br />I <br />N <br /> <br />L <br />I <br />N <br />E <br />: <br /> <br />6 <br />1 <br />9 <br />- <br />3 <br />5 <br />7 <br />- <br />4 <br />1 <br />4 <br />2 <br />1 <br />13 144 <br />8 <br />3 <br />2 <br />13 <br />12 <br />11 <br />9 <br />5 <br />PV COMBINER <br />(IF USED) <br />FOR ILLUSTRATION ONLY (NOT ACTUAL MSP) <br />MAIN SERVICE PANEL <br />AC DISCONNECT <br />(IF USED) <br />PV METER <br />(IF USED) <br />LABEL LEGEND <br />9 <br />1 <br />1 <br />2 <br />3 <br />4 <br />4 <br />5 8 <br />9 <br />13 <br />13 <br />14 <br />5 <br />3 <br />5 <br />15 <br />15 <br />CEC 690.56(C) <br />CEC 705.12(C) & CEC 690.59 <br />CEC 690.13(B) <br />CEC 690.13(B) <br />CEC 690.54 <br />CEC 705.12(B)(3)(2) <br />CEC 110.27(C)CEC 706.15(C)(4) <br />CEC 690.13(B) <br />CEC 705.12(B)(3)(3) <br />CEC 705.12(D) <br />CEC 690.56(C)(2) <br />3114 S Rita Way - <br />2017890209/14/23