Laserfiche WebLink
Structural Calculations <br />Charge Ready Program <br />Date: 10/27/2023 <br />Calculated by: MM <br />Checked By: DPB <br />EV SWBD-1 <br />Wx1 Gf Cfq zweq1heq1943.55 lb(Force due to Wind in X-Direction) <br />Mz1 Wx1 h g1 <br />heq1 <br />2 <br />3.54 kip ft <br />Wz1 Gf Cfq zleq1heq1521.44 lb(Force due to Wind in Z-Direction) <br />Mx1 Wz1 h g1 <br />heq1 <br />2 <br />1.96 kip ft <br />EV SWBD-2 <br />Wx2 Gf Cfq zweq2heq2282.51 lb(Force due to Wind in X-Direction) <br />Mz2 Wx2 h g2 <br />heq2 <br />2 <br />0.75 kip ft <br />Wz2 Gf Cfq zleq2heq2264.86 lb(Force due to Wind in Z-Direction) <br />Mx2 Wz2 h g2 <br />heq2 <br />2 <br />0.71 kip ft <br />150kVA Transformer <br />Wx3 Gf Cfq zweq3heq3183.18 lb(Force due to Wind in X-Direction) <br />Mz3 Wx3 h g3 <br />heq3 <br />2 <br />0.36 kip ft <br />Wz3 Gf Cfq zleq3heq3117.86 lb(Force due to Wind in Z-Direction) <br />Mx3 Wz3 h g3 <br />heq3 <br />2 <br />0.23 kip ft <br /> Seismic Load: <br />SDS 1.034(Spectral Acceleration, short period, ASCE 7-16 Section 11.4.5) <br />SD1 0.461(Spectral Acceleration,1s period, ASCE 7-16 Section 11.4.6) <br />Page: 3 of 5 <br />909 N Grand Ave - <br />101116238 & 201806132/15/2024