www.hilti.com <br />Hilti PROFIS Engineering 3.0.88 <br />Input data and results must be checked for conformity with the existing conditions and for plausibility! <br />PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan <br />3 <br />Company: <br />Address: <br />Phone I Fax: <br />Design: <br />Fastening point: <br /> | <br />EV SWBD-1 Anchor Design <br />Page: <br />Specifier: <br />E-Mail: <br />Date: <br />3 <br />10/27/2023 <br />2 Proof I Utilization (Governing Cases) <br />Design values [kip] Utilization <br />Loading Proof Load Capacity bN / b V [%]Status <br /> Tension Concrete Breakout Failure 4.959 9.812 51 / - OK <br /> Shear Concrete edge failure in direction x- 2.050 17.844 - / 12 OK <br />Loading bN bV z Utilization bN,V [%]Status <br /> Combined tension and shear loads 0.505 0.115 5/3 35 OK <br />3 Warnings <br />• Please consider all details and hints/warnings given in the detailed report! <br />Fastening meets the design criteria! <br />909 N Grand Ave - <br />101116238 & 201806132/15/2024