Laserfiche WebLink
Structural Calculations <br />Charge Ready Program <br />Date: 10/27/2023 <br />Calculated by: MM <br />Checked By: DPB <br />100A SW - Structural Calculation <br />_________________________________________________________________________ <br />I. References <br />1. ASCE 7-16 <br />2. Schneider Electric Single Throw Safety Switch, 100A, 600V <br />II. Equipment Information <br />weq 6.38in(Width of Equipment) <br />leq 10.25in(Length of Equipment) <br />h eq 21.25in(Height of Equipment) <br />Weq 17.46lb(Weight of Equipment) <br />h g 18in(Height above Ground; Assumed) <br />n 2(Number of Posts) <br />s 1ft(Spacing of Posts; Assumed) <br />III. Equipment Loading <br /> Dead Load: <br />SF 1.5(Safety Factor to Account for Misc Parts) <br />DL <br />Weq SF <br />n 13.10 lb(Dead Load at Base of Post) <br /> Wind Load: <br />V 95mph(Basic Wind Speed: Risk Category II) <br />Exposure Category C <br />k d 0.85(ASCE Table 26.6-1) <br />k zt 1.0(ASCE 7-16 Section 26.8.1) <br />k e 1.0(ASCE Table 26.9-1) <br />k z 0.85(ASCE Table 26.10-1) <br />Gf 0.85(ASCE Equation 26.10-1) <br />Page: 1 of 4 <br />909 N Grand Ave - <br />101116238 & 201806132/15/2024