Laserfiche WebLink
Wind Load Cont. <br />110 mph ASCE 7‐16 Figure 26.5‐1B <br />C <br />1.0 ASCE 7‐16 Sec 26.8.2 <br />0.85 ASCE 7‐16 Table 26.10‐1 <br />0.85 ASCE 7‐16 Table 26.6‐1 <br />1.00 ASCE 7‐16 Table 26.9‐1 <br />22.31 psf <br />23.0 Degrees <br />1.5 Conservatively assuming all exposed <br />0.8 conservatively assuming 10 ft2 effective area <br />Uplift (W)Zone(1,2e) Zone(2r, 2n) Zone(3e) Zone(3r) <br />Fig. 30‐3‐2 GCp=‐1.3 ‐1.7 ‐1.7 ‐1.8 <br />Eq. 29.4‐7 P=qh(GCp)(γE)(γa)=‐34.80 ‐45.51 ‐45.51 ‐48.18 <br />GCp=0.6 Figure 30.3‐2 <br />P=qh(GCp)(γE)(γa)=8.83 Equation 29.4‐7 <br />Rafter Attachments: 0.6D+0.6W (CD=1.6)  <br />Connection Check <br />Attachment max. spacing= 6 ft <br />5/16" Lag Screw Withdrawal Value= 266 lbs/in Table 12.2A ‐ NDS <br />2.5 in DFL Assumed <br />Prying Coefficient 1.4 <br />Allowable Capacity= 760 lbs <br />Zone Trib Width Area (ft) Uplift (lbs) Down (lbs) <br />Zone(1,2e)6 16.5 205.8 195.3 <br />Zone(2r, 2n)6 16.5 264.1 195.3 <br />Zone(3e)6 16.5 264.1 195.3 <br />Zone(3r)6 16.5 278.7 195.3 <br />Conservative Max=278.7 < 760 <br />CONNECTION IS OK <br />Risk Category = <br />KZ = <br />Kd = <br />Ke = <br />2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw.  <br />Embedment in sheading or other material does not count. <br />II <br />V= <br />Exposure = <br />1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift  <br />governs  <br />γE= <br />γa= <br /> KZt = <br />qh= 0.00256KzKztKdKeV2= <br />Pitch = <br />Lag Screw Penetration <br />projects@evengineersnet.com <br />http://www.evengineersnet.com <br />1012 N King St- <br />101118433, 201822213/13/2024