Laserfiche WebLink
SUB MMSAGSUB <br />BB BBSUB <br />BB <br />BB <br />SU <br />B <br />SU <br />B <br />SITE PLAN NOTES <br />A. ALL WORK SHALL COMPLY WITH APPLICABLE, LOCAL, MUNICIPAL CODES, AND <br />TO MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS. <br />B. THE ROOF ACCESS POINT REQUIRING A LADDER SHALL NOT BE LOCATED <br />OVER A WINDOW, DOOR OR LOCATED WHERE IT CONFLICTS WITH OVERHEAD <br />OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS [R324.7.1]. <br />C. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND <br />PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED [NEC 110.26]. <br />D. THE DEPICTED CONDUIT RUN ON PLANS IS A PROPOSED CONDUIT ROUTE. <br />THE CONDUIT RUN MAY BE ALTERED AT INSTALLATION AS REQUIRED, AS LONG <br />AS ALTERATIONS ADHERE TO ALL AHJ AND HOA REQUIREMENTS. <br />E. INSTALLATION OF NEW PV SYSTEM SHALL NOT OBSTRUCT EXISTING <br />PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, OR VENTILATION INTAKE AIR <br />OPENINGS; ANY RELOCATED PLUMBING VENTS MUST BE THROUGH THE ATTIC <br />SPACE AND TERMINATED A MIN. 6 INCHES ABOVE THE ROOF LINE. <br />F. ALL EQUIPMENT SHALL BE LISTED AND ALL OUTDOOR EQUIPMENT SHALL BE <br />NEMA 3R RATED, INCLUDING ROOF MOUNTED TRANSITION BOXES AND <br />SWITCHES. <br />G. EQUIPMENT LISTINGS AND CERTIFICATIONS ARE AS FOLLOWS: <br />I. MODULES ARE LISTED UNDER UL61370-1 & UL61370-2 <br />II. INVERTER IS LISTED UNDER UL1741 <br />III. RACKING IS LISTED UNDER UL2703 <br />IV. RACKING SYSTEMS IN COMBINATION WITH TYPE 1 OR 2 MODULES, <br /> ARE CLASS A FIRE RATED. <br />FIRE PATHWAY NOTES <br />R324.6.1: PATHWAYS TO RIDGE. <br />I.NOT LESS THAN TWO MINIMUM 36-INCH WIDE (914 MM) PATHWAYS ON <br /> SEPARATE ROOF PLANES, FROM LOWEST ROOF EDGE TO RIDGE, SHALL <br /> BE PROVIDED ON ALL BUILDINGS. AT LEAST ONE PATHWAY SHALL BE <br /> PROVIDED ON THE STREET OR DRIVEWAY SIDE OF THE ROOF. <br />II. FOR EACH ROOF PLANE WITH A PHOTOVOLTAIC ARRAY, A MINIMUM <br /> 36-INCH-WIDE PATHWAY FROM THE LOWEST ROOF EDGE TO RIDGE <br /> SHALL BE PROVIDED ON THE SAME ROOF PLANE AS THE PHOTOVOLTAIC <br /> ARRAY, ON AN ADJACENT ROOF PLANE, OR STRADDLING THE SAME AND <br /> ADJACENT ROOF PLANES. <br />III.PATHWAYS SHALL BE OVER AREAS CAPABLE OF SUPPORTING FIRE <br /> FIGHTERS ACCESSING THE ROOF. PATHWAYS SHALL BE LOCATED IN <br />AREAS WITH MINIMAL OBSTRUCTIONS SUCH AS VENT PIPES, CONDUIT, <br /> OR MECHANICAL EQUIPMENT. <br />R324.6.2 SETBACKS AT RIDGE. <br />FOR PHOTOVOLTAIC ARRAYS OCCUPYING 33 PERCENT OR LESS OF THE <br />PLAN VIEW TOTAL ROOF AREA, A MINIMUM 18 IN. SETBACK IS REQUIRED ON <br />BOTH SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS <br />OCCUPYING MORE THAN 33 PERCENT OF THE PLANVIEW TOTAL ROOF AREA, <br />A MINIMUM 36 IN. WIDE SETBACK IS REQUIRED ON BOTH SIDES OF A <br />HORIZONTAL RIDGE. <br />R324.7.2.6 EMERGENCY ESCAPE AND RESCUE OPENING. <br /> PANELS AND MODULES INSTALLED ON DWELLINGS SHALL NOT BE PLACED <br />ON THE PORTION OF A ROOF THAT IS BELOW AN EMERGENCY ESCAPE AND <br />RESCUE OPENING. A 36 IN. WIDE PATHWAY SHALL BE PROVIDED TO THE <br />EMERGENCY ESCAPE AND RESCUE OPENING. <br />FIRE PATHWAY REQUIREMENT EXCEPTIONS. <br />I.DETACHED, NONHABITABLE STRUCTURES SHALL NOT BE REQUIRED TO <br /> PROVIDE ROOF ACCESS. <br />II.FIRE ACCESS PATHWAYS NOT REQUIRED FOR ROOFS WITH SLOPES OF 2:12 <br /> (11 DEGREE PITCH) OR LESS. <br />ADDITIONAL FIRE NOTES. <br />I. FIRE PATHWAYS TO RIDGE ARE PROPOSED PATHWAYS AND ARE NOT <br /> INTENDED TO LIMIT ALTERNATIVE PATHWAYS TO ROOF AT INSTALLATION IF <br /> SITE CONDITIONS REQUIRE. ALTERNATIVE PATHWAYS MUST COMPLY WITH <br /> ALL AHJ AND CODE REQUIREMENTS FOR FIRE PATHWAYS. <br />II. SEE ADDITIONAL NOTES SECTION FOR ROOF COVERAGE CALCULATIONS <br />INSTALLER NOTES SITE PLAN <br />INFINITY SOLAR, INC. <br />749 N MAIN ST. <br />ORANGE, CA 92868 <br />PHONE: (714) 880-8089 <br />LIC NO.: C10 - 824287 <br />TIM POLUJANCEWICZ <br />COMBO METER/MAINMM <br />IN <br />V <br />SU <br />B <br />FIRE SETBACKS & PATHWAYS <br />3' FIRE CODE PATHWAY <br />18" RIDGE FIRE SETBACK <br />SCALE: 1/16" = 1' <br />ROOF & FIRE PLAN <br />ROOF AREA PV COVERAGE <br />ROOF SURFACE:2757 SQ. FT. <br />PV COVERAGE:902.96 SQ. FT <br />ROOF AREA COVERED:32.75% <br />A/C ROOFTOP A/C UNIT <br />ADDITIONAL NOTES <br />LEGEND KEY <br />INVERTER <br />SUB PANEL <br />SKY LIGHT <br />CHIMNEY <br />ATTIC VENT <br />PLUMBING VENT <br />SATELLITE DISH <br />ELECTRICAL MASTSAC DISCONNECT <br />PROPOSED CONDUIT <br />PROPOSED STRINGING <br />OPTIMIZER/RSD/ <br />MICROINVERTER <br />AC <br />L AC LOADCENTER <br />IQ COMBINER <br />NEMA 3R JBOX <br />BB BATTERY BANK <br />EV EV CHARGER <br />IQ <br />C <br />PV MODULE DETAILS <br />FIRE SETBACKS AND PATHWAYS DESIGNED <br />IN COMPLIANCE WITH R324.6.2 AND <br />ASSUMES NO AUTOMATIC FIRE <br />SPRINKLERS ARE ON THE PROPERTY <br />UNLESS CONFIRMED BY THE INSTALLER. <br />HANWHA QCELLS <br />Q.TRON BLK M-G2+ 425 <br />425 WATTS <br />67.8" H X 44.6" L X 1.18" D <br />WEIGHT: 47.2 LBS <br />N <br />ELECTRICAL & FIRE PLAN PV.02 <br />JB <br />DRAWN BY: <br />PAPER: 11X17 (ANSI B)DATE: <br />DESIGN LEAD: <br />DESIGNED BY SOLAR DEPLOYED, LLC. <br />931 10TH ST #114, MODESTO, CA 95354 <br />209-671-2001 | HELLO@SOLARDEPLOYED.COM <br />SIGNATURE: <br />CHECKED BY: <br />7/23/2024 <br />T.M. <br />C.B.T.M. <br />SHEET NAME: <br />NEW PV SYSTEM <br /> 18.275 kW DC (STC-DC) | 16.642 kW (CEC-AC) <br />SARAH HAMMARSTROM <br />403 N SUSAN ST BLDG #E, <br />SANTA ANA, CA 92703 <br />APN: 198-261-34 <br />SHEET NO.: <br />ENGINEER OF RECORD <br />3' <br />3' <br />3' <br />ARRAY 3 - 1.275 kW <br />[x3] (N) MODULES <br />TILT:18 DEGREES <br />AZIMUTH: 273 DEGREES <br />ARRAY 4 - 2.550 kW <br />[x6] (N) MODULES <br />TILT: 18 DEGREES <br />AZIMUTH: 13 DEGREES <br />ARRAY 5 - 1.275 kW <br />[x3] (N) MODULES <br />TILT: 18 DEGREES <br />AZIMUTH: 93 DEGREES <br />ARRAY 6 - 0.850 kW <br />[x2] (N) MODULES <br />TILT: 0 DEGREES <br />AZIMUTH: 183 DEGREES <br />ARRAY 1 - 3.400 kW <br />[x8] (N) MODULES <br />TILT:18 DEGREES <br />AZIMUTH: 183 DEGREES <br />(E) 200A MAIN SERVICE PANEL <br />(N) 200A CRITICAL LOAD SUB PANEL <br />(N) FRANKLIN AGATE <br />(N) 100A PV AC DISCONNECT <br />(N) 125A SOLAR SUB PANEL <br />ARRAY 2 - 0.850 kW <br />[x2] (N) MODULES <br />TILT: 18 DEGREES <br />AZIMUTH: 183 DEGREES <br />(N) ESS SUB PANEL 2 <br />(N) FRANKLIN BATTERY 4 <br />(N) FRANKLIN BATTERY 3 <br />ARRAY 7 - 8.075 kW <br />[x19] (N) MODULES <br />TILT: 0 DEGREES <br />AZIMUTH: 183 DEGREES <br />(N) ESS SUB PANEL 1 <br />(N) FRANKLIN BATTERY 2 <br />(N) FRANKLIN BATTERY 1 <br />JB <br />TRENCHING <br />GRADE <br />24 <br />" <br />TRENCHING DETAIL <br />(N) ELECTRICAL WARNING RIBBON <br />BURIED 24" BELOW GRADE. <br />(N) 1" PVC CONDUIT FULLY BURIED <br />MINIMUM 24" BELOW GRADE. <br />(N) 1" PVC CONDUIT FULLY BURIED <br />MINIMUM 24" BELOW GRADE. <br />TRENCHED AND BACKFILLED. <br />(APPROX 29') <br />JB <br />THIS DETACHED PATIO IS PART OF <br />THE OCCUPANCY OF BUILDING E <br />(BUILDING PERMIT NO.: 101104927) <br />A GEC SYSTEM WILL <br />BE PROVIDED FOR <br />THIS DETACHED PATIO <br />SEE LINE DIAGRAM <br />FOR DETAILS <br />(E) DETACHED PATIO <br />OF BUILDING E <br />(N) PV COMBINER <br />(WILL ACT AS A MEANS <br />OF DISCONNECT) <br />A <br />A <br />26 <br />This item has been digitally signed <br />and sealed on Aug 26, 2024 <br />*STRUCTURAL ONLY <br />403 N Susan St Bldg# E - <br />101119805 & 201832129/23/2024