Laserfiche WebLink
Base Plate Analysis: Typical <br />The base plate will be analyzed with the rectangular stress resulting from the vertical load P, combined with the triangular <br />stresses resulting from the moment Mb (if any). Three criteria are used in determining Mb: <br />1. Moment capacity of the base plate <br />2. Moment capacity of the anchor bolts <br />3. Vcol <br /> . h/2 (full fixity) <br />Mb is the smallest value obtained from these three criteria. <br />Fy = 36000 psi <br />Pcol = 20024 lbs <br />MBase = 5833 in-lbs <br />P/A = Pcol/(D . B) = 20024 / (8 . 8) = 313 psi <br />fb = MBase / (D . B2 / 6) = 5833 / (8 . 82 / 6) = 68.36 psi <br />fb2 = fb <br /> . (2 . b1 / B) = 68.36 . (2 . 2/8) = 34.18 psi <br />fb1 = fb - fb2 = 68.36 - 34.18 = 34.18 psi <br />Mb = wb1 <br />2 / 2 = (b1 <br />2 / 2) . (fa + fb1 + 0.67 . fb2) <br /> = (22 / 2) . (313 + 34.18 + 0.67 . 34.18) = 739.68 in-lbs <br />SBase = (B . t2) / 6 = 0.08sq.in. <br />FBase = 0.9 . Fy = 32,400 psi <br />fb / Fb = Mb / (SBase <br /> . FBase) = 739.68 / (0.08 . 32,400) = 0.27 <br />Plate width B =8 in. <br />Plate depth D =8 in. <br />Plate thickness t =0.25 in. <br />Column width b =4 in. <br />Column depth d =3 in. <br />b1 =2 in. <br />PROJECT: <br />FOR: <br />ADDRESS: <br />SHEET#: <br />CALCULATED BY: <br />DATE: <br />Power Distribution Inc <br />Aztec_steve peterson <br />4011 W. CARRAIGE D <br />SANTA ANA, CA <br />41 <br />kelvira <br />6/19/2024 <br /> TEL:(909)869-0989 <br /> 1130 E. CYPRESS ST, COVINA, CA 91724 <br />PN:20240103_2 <br />4011 W Carriage Dr <br />9/11/2024