Laserfiche WebLink
Structural Analysis Report <br />December 11, 2024 <br />Page | 4 <br />4. SUPPORTING DOCUMENTATION <br />Construction Drawings Prodiconn Solutions dated April 4, 2024 <br />AT&T Mobility Proposed Loading RFDS ID: 4350690 dated May 4, 2022 <br />Previous Analysis Report Prodiconn Solutions dated April 4, 2024 <br /> <br />5. RESULTS <br />Components Capacity Pass/Fail <br />FRP Structure (Alpha, Beta, Gamma) 44.0% Pass <br />Roof Structure (Alpha, Beta, Gamma) See Note Acceptable <br />Roof Girder (Equipment Area) 73.3% Pass <br />Roof Joists (Equipment Area) 44.1% Pass <br />RATING = 73.3% Pass <br /> <br />Note: Looking at this installation from a structural prospective, it is an engineering judgment of this office that <br />the installation will have no appreciable impact on either the vertical or horizontal loads imposed on the <br />existing roof structure, and the existing roof structure is capable of supporting the existing and proposed <br />equipment. <br /> <br />6. RECOMMENDATIONS <br /> <br />Infinigy recommends installing AT&T Mobility’s proposed equipment loading configuration on the existing <br />rooftop at 24.5 ft & 24.0 ft. The installation shall be performed in accordance with the construction documents <br />issued for this site. <br /> <br />If you have any questions, require additional information, or believe the actual conditions differ from those <br />detailed in this report, please contact us immediately. <br /> <br /> <br /> <br />Christopher H. Lee, MS, PE <br />Engineering Manager | INFINIGY <br /> <br />3925 3%4 S Bristol St <br />Unit# WCC015/8/2025