BRUEGGER'S BAGEL BAKERY
<br />0
<br />1A
<br />0
<br />A2.1
<br />COLUMN LINE
<br />DOOR MARK
<br />REVISION SYMBOL
<br />CEILING FINISH CODE
<br />CEILING HEIGHT
<br />ELEVATION REFERENCE
<br />SHEET NUMBER
<br />ELEVATION NUMBER & DIRECTION
<br />SHEET NUMBER
<br />ROOM NAME
<br />ROOM NUMBER
<br />REVISION CLOUD
<br />EQUIPMENT TAG
<br />WINDOW MARK
<br />FINISH TAG
<br />NORTH ARROW
<br />ELEVATION HEIGHT TARGET
<br />LOCATION IN SPACE
<br />WALL SECTION REFERENCE
<br />SHEET NUMBER
<br />DETAIL REFERENCE
<br />SHEET NUMBER
<br />CODED NOTE
<br />PARTITION TYPE
<br />REFERENCE SHEET
<br />A4.3
<br />SECTION REFERENCE
<br />SHEET NUMBER
<br />XXXCT1
<br />1
<br />1
<br />XXX
<br />ROOM NAME
<br />123
<br />NOTE
<br />X' - X" A.F.F
<br />A7.1
<br />A
<br />B
<br />C
<br />D A7.1
<br />A
<br />2
<br />1
<br />1
<br />0
<br />A1
<br />0
<br />1A
<br />10' - 0" A.F.F.
<br />2841 W MACARTHUR BLVD, SUITE 3E
<br />SANTA ANA, CA 92704
<br />CENTERLINE
<br />ACOUSTIC CEILING TILE
<br />ADJUSTABLE
<br />ABOVE FINISH FLOOR
<br />ALUMINUM
<br />ARCHITECTURAL
<br />BOARD
<br />BUILDING
<br />BLOCKING
<br />BEAM
<br />BOTTOM
<br />CABINET
<br />CERAMIC
<br />CEILING
<br />CAULKING
<br />CLEAR
<br />COLUMN
<br />CONCRETE
<br />CONTINUOUS
<br />DOUBLE
<br />DETAIL
<br />DIAMETER
<br />DIMENSION
<br />DOOR
<br />DOWNSPOUT
<br />DRAWING
<br />EXISTING
<br />EACH
<br />ELEVATION
<br />ELECTRICAL
<br />EMERGENCY
<br />EQUAL
<br />FIRE EXTINGUISHER
<br />FACE OF
<br />FACE OF FINISH
<br />FACE OF STUDSF.O.S.
<br />F.O.F.
<br />F.O.
<br />F.E.
<br />EQ.
<br />EMER.
<br />ELEC.
<br />ELEV.
<br />EA.
<br />(E)
<br />DWG.
<br />DS.
<br />DR.
<br />DIM.
<br />DIA.
<br />DET.
<br />DBL.
<br />CONT.
<br />CONC.
<br />COL.
<br />CLR.
<br />CLKG.
<br />CLG.
<br />CER.
<br />CAB.
<br />BOT.
<br />BM.
<br />BLKG.
<br />BLDG.
<br />BD.
<br />ARCH.
<br />ALUM.
<br />A.F.F.
<br />ADJ.
<br />ACT
<br />L C
<br />FINISH TO FINISH
<br />FIRE RETARDANT
<br />FINISH
<br />FLOOR
<br />FLUORESCENT
<br />FOOT, FEET
<br />FIELD VERIFY
<br />GRAB BAR
<br />GENERAL CONTRACTOR
<br />GAUGE
<br />GLASS
<br />GYPSUMGYP.
<br />GL.
<br />GA.
<br />G.C.
<br />G.B.
<br />F.V.
<br />FT.
<br />FLUOR.
<br />FL.
<br />FIN.
<br />F.R.
<br />F/F
<br />H.M.
<br />HDWD.
<br />HORIZ.
<br />HGT.
<br />HVAC
<br />HOLLOW METAL
<br />HARDWOOD
<br />HORIZONTAL
<br />HEIGHT
<br />HEATING, VENTILATION,
<br />AIR CONDITIONING
<br />I.D. INSIDE DIAMETER
<br />INSUL. INSULATION
<br />JT. JOINT
<br />LAM LAMINATE
<br />MAX. MAXIMUM
<br />MECHANICAL
<br />MANUFACTURER
<br />MINIMUM
<br />MISCELLANEOUS
<br />METAL
<br />MECH.
<br />MFR.
<br />MIN.
<br />MISC
<br />MTL.
<br />MGR. MANAGER
<br />N. NORTH
<br />N.I.C. NOT IN CONTRACT
<br />N.T.S. NOT TO SCALE
<br />(N) NEW
<br />NO. NUMBER
<br />NOMINALNOM.
<br />O.D. OUTSIDE DIAMETER
<br />OPNG. OPENING
<br />OPPOSITEOPP.
<br />P.LAM. PLASTIC LAMINATE
<br />PL. PLATE
<br />PLAS. PLASTER
<br />PLWD. PLYWOOD
<br />PR. PAIR
<br />PT. POINT
<br />RAD. RADIUS
<br />REG. REGISTER
<br />REQ'D. REQUIRED
<br />RM. ROOM
<br />S. SOUTH
<br />S.C. SOLID CORE
<br />S.S. STAINLESS STEEL
<br />SCHED. SCHEDULE
<br />SHT. SHEET
<br />SIM. SIMILAR
<br />SPEC. SPECIFICATION
<br />SQ. SQUARE
<br />STD. STANDARD
<br />STL. STEEL
<br />STOR. STORAGE
<br />SUSP. SUSPENDED
<br />T.C. TIME CLOCK
<br />T.O. TOP OF
<br />TEL. TELEPHONE
<br />THK. THICK
<br />TYP. TYPICAL
<br />U.N.O. UNLESS NOTED
<br />OTHERWISE
<br />VERT. VERTICAL
<br />VERIFY IN FIELD
<br />WEST
<br />WITH
<br />WATER CLOSET
<br />WITHOUT
<br />WATER RESISTANT
<br />V.I.F.
<br />W.
<br />W/
<br />W/C
<br />W/O
<br />W/R
<br />WOODWD.
<br />REF. REFERENCE
<br />LB(S). POUND(S)
<br />H. HIGH
<br />S.F. SQUARE FOOT
<br />FACE OF MASONRYF/MAS
<br />ALUMINUM COMPOSITE
<br />MATERIAL
<br />ACM
<br />ARCHITECT OF RECORDA.O.R.
<br />P.T. PRESSURE-TREATEDDND DO NOT DISTURB
<br />KED
<br />FOUNDATIONFDN.
<br />PROV'D PROVIDED
<br />WALK-IN BOX
<br />(FREEZER/COOLER)
<br />WIB
<br />P.U.W. PICK UP WINDOW
<br />V.C.T. VINYL COMPOSITE TILE
<br />CONCRETE MASONRY UNITC.M.U.
<br />KITCHEN EQUIPMENT
<br />DISTRIBUTOR
<br />ABBREVIATIONSGENERAL NOTES
<br />CODE DATA AND SQUARE FOOTAGE
<br />PROJECT TEAM DIRECTORY
<br />SCOPE OF WORK
<br />CONSTRUCTION PRODUCT WARRANTY
<br />LEGEND
<br />VICINITY MAP
<br />0
<br />1A
<br />DETAIL REFERENCE
<br />SHEET NUMBER
<br />·EXISTING GAS OVEN IS TO BE REPLACED WITH ELECTRIC OVEN.
<br />·EXISTING WALLS ARE TO BE REFINISHED AT OVEN.
<br />·EXISTING CEILING AT OVEN TO BE REPAIRED AS REQUIRED
<br />·NEW HOOD & EXHAUST FANS TO BE INSTALLED AT OVEN.
<br />·ELECTRICAL CIRCUITS FOR OVENS TO BE INSTALLED.
<br />·ELECTRICAL, MECHANICAL, PLUMBING PLANS ARE UNDER SEPARATE REVIEW AND
<br />PERMIT
<br />CONSTRUCTION / PRODUCT WARRANTIES THESE CONSTRUCTION DOCUMENTS NOTE
<br />SPECIFIC PRODUCTS, DETAILS AND SPECIFICATIONS THAT WILL PROVIDE
<br />CONSTRUCTION / PRODUCT WARRANTIES FOR THE FOLLOWING AREAS OF
<br />CONSTRUCTION:
<br />SIDING (KNOTWOOD)
<br />ROOFING (DURO-LAST)
<br />INTERIOR TILE (LATICRETE)
<br />ALTERING THESE DOCUMENTS MAY ALTER THE WARRANTY GUIDELINES. DURO-LAST
<br />AND LATICRETE WILL BE REQUIRED TO APPROVE THE DRAWINGS TO MAINTAIN THE
<br />WARRANTIES. THE CONTRACTOR IS ALSO RESPONSIBLE FOR CONTACTING, DURO-LAST
<br />AND LATICRETE FOR ON-SITE INSTALLATION INSPECTIONS OF EACH OF THE AREAS OF
<br />WORK.
<br />1. REVIEW DOCUMENTS AND VERIFY DIMENSIONS AND FIELD CONDITIONS AND
<br />CONFIRM THAT WORK IS CONSTRUCTIBLE AS SHOWN. CONFLICTS OR OMISSIONS,
<br />ETC., SHALL BE IMMEDIATELY REPORTED TO THE ARCHITECT FOR CLARIFICATION
<br />PRIOR TO THE PERFORMANCE OF WORK IN QUESTION.
<br />2. DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN PARTITION LOCATIONS.
<br />IN CASE OF CONFLICT, NOTIFY THE ARCHITECT OF RECORD. FLOOR PLAN BY
<br />ARCHITECT OF RECORD SUPERSEDES OTHER PLANS. DIMENSIONS MARKED
<br />"CLEAR" SHALL BE MAINTAINED AND SHALL ALLOW FOR THICKNESS OF FINISHES
<br />INCLUDING CARPET, PAD, CERAMIC TILE, V.C.T., ETC
<br />3. INTERIOR DIMENSIONS ARE TO THE FACE OF STUD, UNLESS NOTED OTHERWISE.
<br />4. MARK LOCATIONS OF PARTITIONS AND DOORS FOR REVIEW BY THE OWNER'S
<br />REPRESENTATIVE PRIOR TO INSTALLATION. REVIEW WILL BE FOR DESIGN INTENT.
<br />COORDINATE AND VERIFY CONDITIONS TO ENSURE PROPER FIT.
<br />5. CONTRACTOR IS REQUIRED TO SCHEDULE A PRE-CONSTRUCTION MEETING WITH
<br />THE OWNER'S REPRESENTATIVE TO REVIEW SPECIFIC REQUIREMENTS.
<br />CONTRACTOR IS RESPONSIBLE TO FOLLOW LOCAL RULES AND REGULATIONS.
<br />6. WHEN CONTRACTOR ACCEPTS DELIVERY OF ALL ITEMS NOTED ON PLANS
<br />WHETHER IN CONTRACT OR NOT IN CONTRACT, HE SHALL BE RESPONSIBLE FOR
<br />LOSS AND/OR DAMAGE TO THESE ITEMS.
<br />7. THE CONTRACTOR SHALL MAINTAIN, FOR THE ENTIRE DURATION OF THE WORK, ALL
<br />EXITS, EXIT/ EGRESS LIGHTING, FIRE PROTECTION DEVICES AND ALARMS IN
<br />CONFORMANCE WITH ALL APPLICABLE CODES AND ORDINANCES.
<br />8. SAW CUTTING AND CORING LOCATIONS SHALL BE REVIEWED IN FIELD AND
<br />COORDINATED WITH THE OWNER'S REPRESENTATIVE PRIOR TO CUTTING/CORING.
<br />9. DURING ALL PHASES OF WORK, DO NOT DISTURB THE DELIVERIES AND FUNCTIONS
<br />OF ADJACENT AND NEIGHBORING TENANTS.
<br />10. 'TYP.' MEANS THAT THE CONDITION IS REPRESENTATIVE FOR SIMILAR CONDITIONS
<br />THROUGHOUT, UNLESS OTHERWISE NOTED.
<br />11. PROVIDE PORTABLE FIRE EXTINGUISHER(S) IN ACCORDANCE WITH NFPA 10, WITH
<br />U.L. LABEL AND A RATING OF NOT LESS THAN 2-A WITH 75 FT. TRAVEL DISTANCE TO
<br />ALL POSITIONS OF RESTAURANT OR AS DIRECTED BY THE FIRE DEPARTMENT FIELD
<br />INSPECTOR. PROVIDE CLASS K FIRE EXTINGUISHER WITHIN 20 FT. OF COMMERCIAL
<br />FOOD HEAT-PROCESSING EQUIPMENT.
<br />12. EXTERIOR BUILDING SIGNS SHALL BE SUBMITTED UNDER SEPARATE PERMIT
<br />APPLICATION FOR REVIEW AND APPROVAL AS REQUIRED BY LOCAL AUTHORITIES.
<br />EXTERIOR SIGNS ARE NOT WITHIN THE SCOPE OF BUILDING DEPARTMENT
<br />APPROVAL.
<br />13. PRIOR TO COMMENCEMENT OF WORK - OBTAIN A COPY OF THE BUILDING
<br />CONSTRUCTION PERMIT FROM THE AUTHORITY HAVING JURISDICTION (AHJ) AND A
<br />COPY OF THE SET OF CONSTRUCTION DOCUMENTS SIGNED AND SEALED BY A
<br />LICENSED DESIGN PROFESSIONAL FOR ALL DISCIPLINES AS REQUIRED AND USED
<br />TO OBTAIN THE BUILDING PERMIT.
<br />14. IF REQUIRED BY LOCAL JURISDICTION - SPRINKLER, LIFE SAFETY, AND FIRE ALARM
<br />SYSTEMS ARE TO BE DESIGNED AND SUBMITTED FOR REVIEW AND APPROVAL BY
<br />LOCALLY LICENSED DESIGN PROFESSIONAL. THE DESIGN OF SYSTEM(S) MUST
<br />COMPLY TO LOCAL, STATE, AND NATIONAL CODES.
<br />15. BIDDERS REFER TO WENDY'S APPROVED SUPPLIER LIST TO OBTAIN NATIONAL
<br />ACCOUNT PHONE NUMBERS AND CONTACTS.
<br />16. GC IS RESPONSIBLE FOR FINDING AND LOCATING ALL UNDERGROUND UTILITIES IN
<br />AREAS OF EXCAVATION PRIOR TO DIGGING. ACCIDENTAL INTERRUPTION OF THESE
<br />SERVICES DURING CONSTRUCTION WILL BE THE RESPONSIBILITY OF THE GC.
<br />PRIOR TO DIGGING, GC TO CALL LOCAL UTILITY LOCATION SERVICE.
<br />17. IF THERE IS ARE CONFLICTING DETAILS ON PLANS THE MORE COSTLY METHOD IS
<br />TO BE COMPLETED
<br />18. CONTRACTOR IS RESPONSIBLE TO PROVIDE AND INCLUDE ACCESS PATH AS
<br />REQUIRED FOR ACCESS TO PLUMBING, MECHANICAL, ELECTRIC, OR FIRE LINES.
<br />SHEET INDEX
<br />RESTAURANT DESIGN
<br />STRUCTURAL ENGINEER
<br />CLIENT
<br />ARCHITECT
<br />1330 OLYMPIC BLVD.
<br />SANTA MONICA, CA 90404
<br />CONTACT: JOHN DODSON
<br />TEL: 310-452-5533 X204
<br />EMAIL: DODSON@ADNARCH.COM
<br />ARMET DAVIS NEWLOVE ARCHITECTS
<br />CONTACT:
<br />TEL:
<br />FAX:
<br />ELECTRICAL ENGINEER
<br />T.B.DSOILS ENGINEER
<br />CIVIL ENGINEER
<br />TRAFFIC CONSULTANT
<br />M/P ENGINEER
<br />PROPERTY OWNER
<br />FIRE DEPARTMENT NOTES
<br />1. FIRE EXTINGUISHERS:
<br />LOCATIONS AND CLASSIFICATIONS OF EXTINGUISHERS TO BE DETERMINED
<br />2. STREET ADDRESS MUST BE PROVIDED ON THE FRONT OF THE BUILDING, PLAINLY
<br />VISIBLE FROM ROADWAY WHICH BUILDING IS ADDRESSED. NUMBERS MUST BE OF A
<br />COLOR WHICH CONTRASTS WITH THEIR BACKGROUND.
<br />3. PROVIDE IDENTIFICATION FOR ALL UNITS OR SUITES. SUCH IDENTIFICATION SHALL
<br />ALSO BE PROVIDED ON ALL UTILITY SHUT OFF DEVICES.
<br />4. NATIONAL FIRE PROTECTION ASSOCIATION, STANDARD 25, CHAPTER 4 REQUIRES
<br />ALL PRIVATE HYDRANT SYSTEMS TO BE SERVICED ANNUALLY TO ENSURE PROPER
<br />OPERATING FUNCTIONING. SERVICE SHALL INCLUDE LUBRICATING HYDRANTS
<br />ANNUALLY TO KEEP ALL STEMS, CAPS, PLUGS, ANT THREADS IN PROPER
<br />OPERATING CONDITION. HYDRANTS SHALL BE KEPT FREE OF MATERIALS AND
<br />PROTECTED AGAINST MECHANICAL DAMAGE SO THAT FREE ACCESS IS ENSURED.
<br />THE SERVICE, AND ANY NECESSARY REPAIRS, ARE THE RESPONSIBILITY OF THE
<br />PROPERTY OWNER.
<br />5. PRIVATE FIRE HYDRANTS, SPRINKLER CONTROL AND POST INDICATOR VALVES,
<br />RISERS AND FIRE DEPARTMENT CONNECTIONS SHALL BE PAINTED OSHA SAFETY
<br />RED
<br />6. MAIN EXIT DOORS SHALL BE PROVIDED WITH A DURABLE SIGN OF ONE INCH (1")
<br />LETTERS ON CONTRASTING BACKGROUND INDICATING, "THIS DOOR IS TO REMAIN
<br />UNLOCKED WHEN BUILDING IS OCCUPIED NOTE: ONLY ONE DOOR OR SET OF
<br />DOORS MAY BE DESIGNATED AS THE MAIN EXIT.
<br />7. ADDITIONAL EXIT DOORS SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE
<br />OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT (SINGLE ACTION).
<br />8. AN AUTOMATIC FIRE SPRINKLER SYSTEM IS REQUIRED BY CITY ORDINANCE. UNDER
<br />SEPARATE COVER, SUBMIT PLANS FOR THE AUTOMATIC FIRE SPRINKLER SYSTEM(S)
<br />AND OBTAIN APPROVAL FROM THE FIRE DEPARTMENT PRIOR TO INSTALLATION.
<br />SYSTEMS EXCEEDING 99SPRINKLER HEADS SHALL BE PROVIDED WITH
<br />SUPERVISORY SERVICE AND SHALL BE MONITORED BY AN APPROVED FACILITY.
<br />POST INDICATOR VALVES, DETECTOR CHECK CONTROL VALVES AND WATER FLOW
<br />SWITCHES ARE REQUIRED TO BE CENTRAL STATION MONITORED. HAVE ALARM
<br />CONTRACTOR SUBMIT PLANS AND OBTAIN APPROVALS PRIOR TO INSTALLATION.
<br />ALARM CONTRACTOR SHALL PROVIDE A COPY OF A MAINTENANCE CONTRACT
<br />COMPLYING WITH N.F.P.A. 72.
<br />9. THE NAMES, ADDRESSES AND TELEPHONE NUMBERS OF THE BUILDING OWNERS(S),
<br />MANAGEMENT COMPANY, EMERGENCY CONTACTS AND MANAGER(S) MUST BE
<br />PROVIDED TO THE FIRE INSPECTOR NO LATER THAN THE FINAL FIRE INSPECTION.
<br />10. AN INSPECTION BY THE FIRE DEPARTMENT IS REQUIRED PRIOR TO OCCUPANCY.
<br />CONTACT INSPECTOR TO SCHEDULE THE INSPECTION. NOTE: FAILURE TO CALL FOR
<br />YOUR INSPECTION IS A VIOLATION OF THE CALIFORNIA FIRE CODE AND MAY RESULT
<br />IN CRIMINAL PROSECUTION.
<br />11. FIRE SAFETY DURING CONSTRUCTION, ALTERATION OR DEMOLITION OF A BUILDING
<br />SHALL BE IN ACCORDANCE WITH 1994 UFC ARTICLE 87.
<br />12. THE ACCESS DOOR TO THE FIRE SPRINKLER RISER ROOM SHALL HAVE A
<br />PERMANENT SIGN ON IT INDICATING " FIRE RISER ROOM ".
<br />SAFEGUARDS DURING CONSTRUCTION
<br />3302.3 FIRE SAFETY DURING CONSTRUCTION
<br />FIRE SAFETY DURING CONSTRUCTION SHALL COMPLY WITH THE APPLICABLE
<br />REQUIREMENTS OF THIS CODE AND THE APPLICABLE PROVISIONS OF CHAPTER 33 OF THE
<br />CALIFORNIA FIRE CODE.
<br />3305.1 FACILITIES REQUIRED
<br />SANITARY FACILITIES SHALL BE PROVIDED DURING CONSTRUCTION, REMODELING OR
<br />DEMOLITION ACTIVITIES IN ACCORDANCE WITH THE CALIFORNIA PLUMBING CODE.
<br />SECTION 3312 AUTOMATIC SPRINKLER SYSTEM
<br />3312.1 COMPLETION BEFORE OCCUPANCY
<br />IN BUILDINGS WHERE AN AUTOMATIC SPRINKLER SYSTEM IS REQUIRED BY THIS CODE, IT
<br />SHALL BE UNLAWFUL TO OCCUPY ANY PORTION OF A BUILDING OR STRUCTURE UNTIL
<br />THE AUTOMATIC SPRINKLER SYSTEM INSTALLATION HAS BEEN TESTED AND APPROVED,
<br />EXCEPT AS PROVIDED IN SECTION 111.3.
<br />3312.2 OPERATION OF VALVES
<br />OPERATION OF SPRINKLER CONTROL VALVES SHALL BE PERMITTED ONLY BY PROPERLY
<br />AUTHORIZED PERSONNEL AND SHALL BE ACCOMPANIED BY NOTIFICATION OF DULY
<br />DESIGNATED PARTIES. WHEN THE SPRINKLER PROTECTION IS BEING REGULARLY TURNED
<br />OFF AND ON TO FACILITATE CONNECTION OF NEWLY COMPLETED SEGMENTS, THE
<br />SPRINKLER CONTROL VALVES SHALL BE CHECKED AT THE END OF EACH WORK PERIOD
<br />TO ASCERTAIN THAT PROTECTION IS IN SERVICE.
<br />SECTION 3313 WATER SUPPLY FOR FIRE PROTECTION
<br />3313.1 WHERE REQUIRED
<br />AN APPROVED WATER SUPPLY FOR FIRE PROTECTION, EITHER TEMPORARY OR
<br />PERMANENT, SHALL BE MADE AVAILABLE AS SOON AS COMBUSTIBLE MATERIAL ARRIVES
<br />ON THE SITE.
<br />1. ADMINISTRATION
<br />A. ALL WORK SHALL BE IN CONFORMANCE WITH THE CODES IDENTIFIED IN THE
<br />GOVERNING CODES SECTION LISTED BELOW.
<br />2022 CALIFORNIA BUILDING CODE AND JURISDICTIONAL AMENDMENTS (CBC)
<br />2022 CALIFORNIA MECHANICAL CODE AND JURISDICTIONAL AMENDMENTS (CMC)
<br />2022 CALIFORNIA PLUMBING CODE AND JURISDICTIONAL AMENDMENTS (CPC)
<br />2022 CALIFORNIA ELECTRICAL CODE AND JURISDICTIONAL AMENDMENTS (CEC)
<br />2022 CALIFORNIA GREEN BUILDING STANDARDS CODE AND JURISDICTIONAL
<br />AMENDMENTS
<br />2022 CALIFORNIA FIRE CODE AND JURISDICTIONAL AMENDMENTS (CFC)
<br />2022 CALIFORNIA ENERGY CODE AND JURISDICTIONAL AMENDMENTS
<br />CITY CODES AND ORDINANCES
<br />B. CITY OF ONTARIO BUILDING DIVISION ENFORCES CHAPTER 11.B FOR DISABLED
<br />ACCESS COMPLIANCE AND DOES NOT REVIEW OR APPROVE PLANS FOR ADA
<br />COMPLIANCE. SEE CHAPTER 11.B OF 2022 CALIFORNIA BUILDING CODE
<br />2. OCCUPANCY
<br />A. PRIMARY OCCUPANCY (CHAPTER 3)B
<br /> 3. BUILDING AREA
<br />A. CONSTRUCTION TYPE (CHAPTER 5):V-B
<br />B. FULLY SPRINKLERED PER CHAPTER 9:YES
<br /> FIRE ALARM SYSTEM:YES
<br />C. ALLOWABLE (FOR GROUP "M & A-2" MORE RESTRICTIVE WHERE APPLICABLE):
<br />1. MAXIMUM ALLOWABLE STORIES (TABLE 504.4): 2 STORIES
<br />2. MAXIMUM ALLOWABLE HEIGHT FOR SPRINKLERED BUILDING (TABLE 504.3): 60 FT.
<br />MAXIMUM ALLOWABLE FLOOR AREA FOR SPRINKLERED BLDG. (TABLE 506.2): 24,000
<br />INCREASE FOR YARDS (NONE -NOT USED): 0 SF
<br />TOTAL ALLOWABLE FLOOR AREA PER STORY: 24,000 SF
<br />D. ACTUAL:
<br />1) ACTUAL STORIES: 1 STORY
<br />2) ACTUAL HEIGHT (FROM GRADE PLANE) 26'-00"
<br />3) ACTUAL FLOOR AREA: 1,302.08 SF
<br /> FLOOR AREA UNDER HORIZONTAL SOLID PROJECTIONS/ ROOF: 467 SF
<br />TOTAL GROSS FLOOR AREA: 1,769 SF
<br />FLOOR AREA OF TENANT SPACE: 2841 SF
<br />FLOOR AREA IS ACCEPTABLE BECAUSE 12,500 S.F. < 24,000 S.F. (FULL BUILDING)
<br />3. OCCUPANCY SEPARATIONS
<br />A. BUILDING IS CLASSIFIED AS NON-SEPARATED PER SECTION 508.3
<br />NO OCCUPANCY SEPARATIONS REQUIRED
<br /> 5. TYPE OF CONSTRUCTION
<br />A. CONSTRUCTION TYPE (SEC. 602.5): TYPE V-B, FULLY SPRINKLERED PER NFPA
<br />B. FIRE RESTITIVE CONSTRUCTION REQUIREMENTS (TABLE 601):
<br />a. PRIMARY STRUCTURE 0 HR
<br />b. EXTERIOR BEARING WALL 0 HR
<br />c. INTERIOR BEARING WALL 0 HR
<br />d. EXTERIOR WALLS (< 10-FEET FIRE SEPARATION -TABLE 602) 1 HR
<br />e. EXTERIOR WALLS ( 10-FEET OR MORE FIRE SEPARATION TABLE 602) 0 HR
<br />f. INTERIOR NON-BEARING WALL 0 HR
<br />g. FLOOR CONSTRUCTION & ASSOC. SECONDARY MEMBERS 0 HR
<br />h. ROOF CONSTRUCTION & ASSOC. SECONDARY MEMBERS 0 HR
<br /> 6. OCCUPANT LOAD
<br />DINING ROOM: 18 FIXED SEATS
<br />CONCENTRATED LOAD: 40 SQ. FT. / 5 = 8
<br />KITCHEN LOAD: 535 SQ. FT. / 200 = 2
<br />TOTAL: 28
<br />LEGAL DESCRIPTION
<br />SHEET # SHEET NAME REVISION
<br />A0 TITLE SHEET
<br />AS1.0 SITE PLAN
<br />A.1 FLOOR PLAN
<br />A.2 FINISH PLAN
<br />A.3 REFLECTED CEILING PLAN
<br />A.4 FRONT ELEVATION
<br />A.5 WALL & CEILING DETAILS
<br />R.1 ROOF PLAN
<br />MP0.1 HVAC FLOOR PLAN (FOR REFERENCE ONLY)
<br />M.1 HVAC MECHANICAL PLAN (FOR REFERENCE ONLY)
<br />M2.1 CAPTIVE AIRE (FOR REFERENCE ONLY)
<br />M2.2 CAPTIVE AIRE (FOR REFERENCE ONLY)
<br />M2.3 CAPTIVE AIRE (FOR REFERENCE ONLY)
<br />T24 ENERGY FORMS (FOR REFERENCE ONLY)
<br />E10 GENERAL NOTES, ELECTRICAL NOTES, AND SYMBOL
<br />LIST (FOR REFERENCE ONLY)
<br />E20 SINGLE LINE DIAGRAM & PANEL SCHEDULES
<br />(FOR REFERENCE ONLY)
<br />E30 PANEL SCHEDULES (FOR REFERENCE ONLY)
<br />E40 POWER PLAN (FOR REFERENCE ONLY)
<br />1330 OLYMPIC BLVD.
<br />SANTA MONICA, CA 90404
<br />CONTACT: KAVEH DOLATABADY
<br />TEL: 310-452-0575
<br />L&D ENGINEERING
<br />SITE LOCATION
<br />HOSPITALITY REST. SUPPORT CENTER
<br />CONTACT: RICK LESAGE
<br />EMAIL: rick.lesage@hospitalityrsc.com
<br />TEL: 949-633-5512
<br />ARMET DAVIS NEWLOVE &
<br />ASSOCIATES, AIA ARCHITECTS
<br />1330 OLYMPIC BLVD.
<br />SANTA MONICA, CALIFORNIA 90404
<br />PH 310 452-5533 FAX 310 450-4742
<br />REN. 5/31/25
<br />A.0
<br />I
<br />I
<br />Bldg #101120150
<br />
<br />APPROVALS:
<br />PLNG - C. Santana
<br />BLDG - CSG
<br />2841 W MacArthur Blvd
<br />Unit# E12/11/2024
|