HEAVY-DUTY GRID <br />NOTES: <br />1. LIGHT FIXTURES OR DIFFUSERS IN EXCESS <br />OF 56 LBS REQUIRE (4) 12 GAUGE HANGER <br />WIRES. <br />2. SUSPENDED CEILING TO COMPLY WITH <br />ASCE 7-16 SECTION 13.5.6.2.2., ASTM C636, <br />CISCA DESIGN REQUIREMENTS <br />3. CEILINGS SHALL BE SPECIAL INSPECTED <br />PER SECTION 11A.1.3.9 OF ASCE 7.16 <br />(SEE ADDITIONAL NOTES ON RCP) <br />(2) 12 GAUGE HANGER <br />WIRES TO STRUCTURE <br />ABOVE - AT ALTERNATE <br />CORNERS OF ALL 2X4 <br />LIGHT FIXTURES AND <br />HVAC DIFFUSERS <br />2" OVERSIZED <br />RING ADAPTER AT <br />SPRINKLER HEAD <br />INSTALL COMPRESSION STRUT <br />EA. DIRECTION OR EVERY 144 <br />S.F. OF CEILING AREA PER CBC <br />STANDARDS 47-18 <br />12 GA. WIRES @ 12'-0" O.C. <br />SPLAYED 45° FROM CEILING <br />PLANE <br />CROSS RUNNER @ 2'-0" O.C. <br />45° - <br />TYP <br />. <br />WA <br />L <br />L <br />MAIN RUNNER @ 4'-0" O.C. <br />NOTE: <br />1. ALL INTERIOR WALL & CEILING FINISHES SHALL BE FLAME SPREAD CLASS III MIN. <br />2. SUSPENDED T-BAR SYSTEM SHALL BE 25 GA. MIN. <br />3. SUSPENDED CEILING TILE SYSTEM TO COMPLY WITH ICC-ESR #1308 <br />4. ALL 24" X 48" LIGHT FIXTURES & 24" X 24" HVAC DIFFUSERS SHALL BE <br />SUPPORTED BY A MIN. OF (2) HANGERS @ OPPOSITE CORNERS - CEILING <br />SYSTEM SHALL NOT SUPPORT OTHER ITEMS. <br />5. CEILING SYSTEM GRID TO BE HEAVY DUTY. <br />12 GA HANGER WIRE @ 4'-0" O.C. <br />ALONG EACH MAIN RUNNER <br />6'-0" MAX. <br />CEILING SYSTEM GRIDTO <br />BE HEAVY DUTY. <br />++ <br />1/2 " =.5 L=5' MAX. x 12"=60 <br />PROVIDE COMPRESSION <br />STRUTS @ 12'-0" O.C. <br />EACH DIRECTION (OR 144. <br />S.F. AND WITH 6'-0" OF <br />WALLS <br />60/.5 = 120 < 200 <br />L/R = < 200 <br />NOTE: <br />'X' CUT BOTTOM OF <br />CONDUIT (1" DEEP) AND FIT <br />SNUG TO T-BAR <br />INTERSECTION <br />(2) #8 WOOD SCREWS <br />1" DIA. RIGID CONDUIT <br />COMPRESSION POST <br />JOIST, PURLIN OR SUB-PURLIN <br />(SEE ADDITIONAL NOTES ON RCP) <br />SUSPENDED CEILING TILE SYSTEM TO COMPLY WITH ICC-ESR #1308 <br />SPLICE AS NEEDED WITH 3/4" <br />DIA.BY 6" CONDUIT AND #8 <br />MACHINE SCREWS AND NUTS <br />VA <br />R <br />I <br />E <br />S <br /> <br />( <br />V <br />. <br />I <br />. <br />F <br />. <br />) <br />B <br />A <br />HANGER WIRE - PARALLEL TO <br />WALL @ 4'-0" O.C. - TYP. <br />MAIN RUNNER - POP RIVET EACH MAIN <br />RUNNER OR CROSS TEE TO WALL <br />ANGLE - PROVIDE ADDTIONAL <br />CLOSURE ANGLES AS REQUIRED <br />ACCOUSTICAL PANEL - TYP. <br />MAIN RUNNER - DO NOT ATTACH TO <br />WALL ANGLE <br />WALL OR SOFFIT - SEE PLAN <br />CONTINUOUS 2" X 2" ANGLE WITH #10 <br />SELF-TAPPING SCREWS AT EACH <br />STUD - TYP. <br />TYP. <br /> <br />8" MAX. <br />ATTACHED <br />(2) ADJACENT WALLS <br />UNATTACHED <br />OPPOSITE WALLS <br />NOTE: <br />MAIN RUNNERS SHALL BE ATTACHED AT (2) ADJACENT WALLS AS SHOWN IN <br />CONDITION 'A' <br />MAIN RUNNERS SHALL BE UNATTACHED AT OPPOSITE WALLS AS SHOWN IN <br />CONDITION 'B' <br />SEE ADDITIONAL NOTES ON REFLECTED CEILING PLAN - SHEET I-121 <br />3/4" CLR. <br />SPREADER BAR AS REQUIRED TO <br />PREVENT SPREADING <br />TABLE FOR NON-BEARING METAL STUDS SSMA PRODUCTS <br />ICC ESR #2054 <br />5 PSI (SIZING PERTAINS TO ALL 'S' WALL TYPES) <br />STUD SIZE AND GAUGE SPACING MAX. HT. <br />3625125-18 (3 5/8" X 25 GA.) 16" O.C. 14'-4" <br />3625125-33 (3 5/8" X 20 GA.) 16" O.C. 16'-5" <br />3625125-43 (3 5/8" X 18 GA.) 16" O.C. 18'-0" <br />4005125-18 (4" X 25 GA.) 16" O.C. 15'-4" <br />4005125-33 (4" X 20 GA.) 16" O.C. 18'-4" <br />4005125-43 (4" X 18 GA.) 16" O.C. 19'-5" <br />6005125-18 (6" X 25 GA.) 16" O.C. 19'-9" <br />6005125-33 (6" X 20 GA.) 16" O.C. 24'-6" <br />6005125-43 (6" X 18 GA.) 16" O.C. 28'-3" <br />SEE DETAIL 13 AND 15 THIS SHEET FOR FULL HEIGHT WALLS. <br />FULL THICKNESS BATT <br />INSULATION - ONLY WHERE <br />INDICATED ON PLANS AND <br />SPECIFICATIONS <br />FRAMING PER PLAN <br />FINISH FLOOR1/ <br />4 <br />" <br /> <br />M <br />A <br />X <br />. <br />5/8" TYPE 'X' GYP. BD. <br />SHOT PINS - HILTI OR EQUAL <br />@ 24" O.C. <br />LARR. #25646 - ESR # 1663 <br />25 GA. FLOOR TRACK - <br />CONTINUOUS <br />4X WOOD BLOCKING <br />BETWEEN ROOF <br />TRUSSES AS REQUIRED <br />ROOF FRAMING OR OTHER <br />STRUCTURAL MEMBER <br />CONTINUOUS SLIP <br />TRACK <br />FRAMING PER PLAN- 1" <br />MINIMUM CLEAR FROM ROOF <br />STRUCTURE - TO ALLOW ROOF <br />DIAPHRAM MOVEMENT - SHOT <br />PIN - ICC ESR -1752 <br />5/8" TYPE 'X' GYP. BD. - WHERE <br />OCCURS <br />DO <br /> <br />N <br />O <br />T <br /> <br />A <br />T <br />T <br />A <br />C <br />H <br /> <br />G <br />Y <br />P <br />. <br /> <br />B <br />D <br />. <br /> <br />AB <br />O <br />V <br />E <br /> <br />T <br />H <br />I <br />S <br /> <br />P <br />O <br />I <br />N <br />T <br />(2) #10 X 2" WOOD SCREWS <br />@ 24" O.C. <br />SIMPSON TIE HANGER LU <br />FRAMING ANCHOR @ EA <br />END. USE (3) 8-d NAILS, <br />TYP <br />WEB FILLER WHEN <br />APPLICABLE <br />5/8" TYPE 'X' GYP. BD. <br />ATTACH BRACING TO <br />CONTINUOUS 20 GA. TOP <br />TRACK WITH (2) #10 S.M.S. <br />3 5/8" METAL STUD WALL <br />BRACING @ 45 DEG. @48" O.C. <br />IN ALTERNATING DIRECTIONS - <br />SAME STUD GAUGE AS WALL <br />FRAMING PER PLAN <br />I501 <br />7 <br />I501 <br />6 <br />FRAMING PER PLAN <br />5/8" TYPE 'X' GYP BD. <br />EXISTING ROOF & STRUCTURE <br />CONTINUOUS SLIP TRACK <br />ICC-ESR #2054 <br />LARR # 25631 <br />CEILING PER PLAN <br />6" <br /> <br />M <br />I <br />N <br />. <br />5/8" TYPE 'X' GYP <br />BD. - EXTEND TO <br />UNDERSIDE OF ROOF <br />STRUCTURE WHERE <br />NO CEILING OCCURS <br />NOTES: <br />1. ALL INTERIOR WALLS TO HAVE GYPSUM BOARD EXTEND TO PROVIDE TIGHT <br />BUTT JOINT TO FLOOR SLAB. NO GAP IN EXCESS OF 1/4" WILL BE ALLOWED. <br />2. PROVIDE WATER RESISTANT GYPSUM BOARD AT THE INTERIORS OF ALL <br />TOILET ROOMS AND WET WALLS. <br />3. USE 5/8" TYPE 'X' GYP. BD. THROUGHOUT - U.N.O. <br />4. PROVIDE SOUND BATT INSULATION AT ALL OFFICE AREAS & RESTROOMS <br />WALLS <br />AND CEILINGS. <br />SIM. <br />NOTES: <br />1. ALL INTERIOR WALLS TO HAVE GYPSUM BOARD EXTEND TO PROVIDE TIGHT <br />BUTT JOINT TO FLOOR SLAB. NO GAP IN EXCESS OF 1/4" WILL BE ALLOWED. <br />2. PROVIDE WATER RESISTANT GYPSUM BOARD AT THE INTERIORS OF ALL <br />TOILET ROOMS AND WET WALLS. <br />3. USE 5/8" TYPE 'X' GYP. BD. THROUGHOUT - U.N.O. <br />4. PROVIDE SOUND BATT INSULATION AT ALL OFFICE AREAS & RESTROOMS <br />WALLS <br />AND CEILINGS. <br />FRAMING PER PLAN - <br />ATTACH BRACING TO <br />CONTINUOUS TOP TRACK <br />WITH (2) #10 S.M.S. <br />3 5/8" METAL STUD WALL <br />BRACING @ 48" O.C. IN <br />ALTERNATING DIRECTIONS - <br />GA. TO MATCH WALL <br />ATTACH BRACING TO <br />BOTTOM CHORD OR <br />BLOCKING WITH (2) #10 x 1" <br />SCREWS <br />BATT INSULATION AT <br />UNDERSIDE OF ROOF <br />DECK AS REQUIRED - <br />REFER TO T-24 FOR R <br />VALUE <br />ADD WEB JOIST STIFFENER <br />X 12" LONG EACH JOIST <br />PROVIDE 2X6 BLOCKING AS <br />REQUIRED AT PARALLEL AND <br />PERPENDICULAR TRUSS <br />CONDITIONS WITH LUS26 <br />EACH END TO WEB <br />STIFFENER <br />CEILING PER PLAN - REFER <br />TO I103 FOR CEILING TYPE <br />AND HEIGHT. <br />5/8" TYPE 'X' GYP. BD. <br />6" <br /> <br />M <br />A <br />X <br />. <br />TYP.45° <br />ICC-ESR #2054 <br />LARR # 25631 <br />FLOOR FINISH PER PLAN <br />EXISTING TOP OF SLABI501 <br />6 <br />12 <br />' <br />- <br />0 <br />" <br /> <br />M <br />A <br />X <br />. <br />I501 <br />8 <br />FINISH FLOOR <br />5/8" TYPE 'X' GYP. BD. <br />CONTINUES 12" ABOVE <br />ACOUS. <br />CEILING <br />SEE PLAN FOR STUD <br />SIZE AND TRACK - <br />ICC-ESR #2054 <br />5/8" WATER RESISTANT GYP. <br />BOARD <br />(E) DEMISING WALL <br />EXISTING CONCRETE SLAB <br />TYPICAL INTERIOR WALL ASSEMBLY <br />WALL & CEILING ASSEMBLY NOTES <br />1. ALL INTERIOR WALLS TO HAVE GYPSUM BOARD EXTEND TO PROVIDE TIGHT <br />BUTT JOINT TO FLOOR SLAB. NO GAP IN EXCESS OF 1/4" WILL BE ALLOWED. <br />2. PROVIDE WATER RESISTANT GYPSUM BOARD AT THE INTERIORS OF ALL <br />TOILET ROOMS. <br />3. USE 5/8" THICK GYPSUM BOARD THROUGHOUT EITHER TYPE "X" OR UN-RATED <br />AS NOTED ON SHEET <br />4. PROVIDE SOUND BATT INSULATION OVER ALL OFFICE AREAS & RESTROOMS. <br />25 GAUGE FLOOR <br />TRACK <br />ANCHOR W/ 5/32" SHOT <br />PINS AT 36" ON <br />CENTER <br />ATTACH BRACING TO <br />CONTINUOUS TOP TRACK <br />WITH <br />(2) #10 S.M.S. <br />3 5/8" METAL STUD WALL <br />BRACING AT 45 DEG. SPACED <br />AT 48" O.C. IN ALTERNATING <br />DIRECTIONS, SAME STUD <br />GAUGE AS WALL <br />PROVIDE 2X6 BLOCKING AS REQUIRED AT PARALLEL AND <br />PERPENDICULAR TRUSS CONDITIONS W/LUS26 EA. END TO <br />WEB STIFFENER <br />ATTACH BRACING TO BOTTOM CHORD OR BLOCKING <br />WITH (2) #10 x 1" SCREWS <br />ADD WEB JOIST STIFFENER X 12" LONG EACH JOIST <br />REFER TO PLAN A101 AND <br />METAL STUD TABLE - SEE <br />5/I500 <br />(E) GYP BD <br />CEILING <br />I501 <br />6 <br />FINISH FLOOR <br />5/8" TYPE 'X' GYP. BD. <br />CONTINUES 12" ABOVE <br />ACOUS. <br />CEILING <br />SEE PLAN FOR STUD <br />SIZE AND TRACK - <br />ICC-ESR #2054 <br />5/8" WATER RESISTANT GYP. <br />BOARD <br />(E) DEMISING WALL <br />EXISTING CONCRETE SLAB <br />TYPICAL INTERIOR WALL ASSEMBLY <br />WALL & CEILING ASSEMBLY NOTES <br />1. ALL INTERIOR WALLS TO HAVE GYPSUM BOARD EXTEND TO PROVIDE TIGHT <br />BUTT JOINT TO FLOOR SLAB. NO GAP IN EXCESS OF 1/4" WILL BE ALLOWED. <br />2. PROVIDE WATER RESISTANT GYPSUM BOARD AT THE INTERIORS OF ALL <br />TOILET ROOMS. <br />3. USE 5/8" THICK GYPSUM BOARD THROUGHOUT EITHER TYPE "X" OR UN-RATED <br />AS NOTED ON SHEET <br />4. PROVIDE SOUND BATT INSULATION OVER ALL OFFICE AREAS & RESTROOMS. <br />25 GAUGE FLOOR <br />TRACK <br />ANCHOR W/ 5/32" SHOT <br />PINS AT 36" ON <br />CENTER <br />PROVIDE 2X6 BLOCKING AS REQUIRED AT PARALLEL AND <br />PERPENDICULAR TRUSS CONDITIONS W/LUS26 EA. END TO <br />WEB STIFFENER <br />ATTACH BRACING TO BOTTOM CHORD OR BLOCKING <br />WITH (2) #10 x 1" SCREWS <br />ADD WEB JOIST STIFFENER X 12" LONG EACH JOIST <br />REFER TO PLAN A101 AND <br />METAL STUD TABLE - SEE <br />5/I500 <br />(E) GYP BD <br />CEILING <br />I501 <br />6 <br />2 PROVIDE 1X NAILER AS NEEDED <br />5 PROVIDE SEALANT AND BACKER ROD (CONT.) <br />1 <br />2 <br />3 <br />4 <br />5 <br />5 <br />4 5/8" GWB FINISHED PER SCHEDULES <br />6 <br />3 STOREFRONT HEAD. USE BLACK ADONIZED MULLION. <br />7 <br />1 PATCH AND REPAIR STUCCO EXTERIOR PLASTER OVER METAL <br />LATHE. <br />6 CONT. VAPOR BARRIER. PATCH AND REPAIR AS NEEDED. <br />7 EXISTING R-19 BATT INSULATION <br />8 20GA GALVANIZED DRIP EDGE <br />8 <br />2 PROVIDE 1X NAILER AS NEEDED <br />4 5/8" GWB FINISHED PER SCHEDULES <br />5 PROVIDE SEALANT AND BACKER ROD (CONT.) <br />1 <br />2 <br />3 <br />4 5 <br />5 <br />3 STOREFRONT JAMB. USE BLACK ANODIZED MULLIONS <br />6 <br />7 <br />1 PATCH AND REPAIR STUCCO EXTERIOR PLASTER OVER METAL <br />LATHE. <br />6 CONT. VAPOR BARRIER. PATCH AND REPAIR AS NEEDED. <br />7 EXISTING R-19 BATT INSULATION <br />1 <br />2 <br />3 <br />4 <br />1 PATCH AND REPAIR STUCCO EXTERIOR PLASTER OVER METAL <br />LATHE. <br />2 PROVIDE 1X NAILER AS NEEDED <br />4 5/8" GWB FINISHED PER SCHEDULES <br />5 PROVIDE SEALANT AND BACKER ROD (CONT.) <br />3 DRIVE-THRU WINDOW SILL. USE BLACK ADONIZED MULLION. <br />6 CONT. VAPOR BARRIER. PATCH AND REPAIR AS NEEDED. <br />5 <br />7 EXISTING R-19 BATT INSULATION <br />6 <br />7 <br />8 20GA GALVANIZED DRIP EDGE <br />8 <br />WOOD BLOCKING <br />BETWEEN ROOF <br />TRUSSES/JOISTS AS <br />REQUIRED <br />ROOF FRAMING OR OTHER <br />STRUCTURAL MEMBER <br />SIMPSON TIE HANGER LU <br />FRAMING ANCHOR @ EA <br />END. USE (3) 8-d NAILS, <br />TYP <br />WEB FILLER WHEN <br />APPLICABLE <br />COMPRESSION STRUT <br />TOP CLIP MECHANICALLY <br />FASTENED W/(2) #8 WOOD SCREWS <br />SUSPENDED <br />CEILING 12GA <br />HANGING WIRE <br />MIN. 3" EYE LAG SCREW, <br />TYP. <br />SPRING CLIP <br />3" = 1'-0"1FIXTURE BRACING <br />12" = 1'-0"2SUSPENDED CEILING DETAIL <br />12" = 1'-0"4COMPRESSION STRUT <br />1 1/2" = 1'-0"3T-BAR CEILING <br />12" = 1'-0"5METAL STUD WALL TABLE <br />1 1/2" = 1'-0"6BOTTOM TRACK DETAIL <br />1 1/2" = 1'-0"7TOP TRACK DETAIL <br />1 1/2" = 1'-0"8TOP TRACK DETAIL <br />3/8" = 1'-0"9FULL HEIGHT WALL <br />STATE OF CALIF RNIA <br />O <br />REN.09/30/25 <br />S <br />LICEN <br />D ARCHITECT <br />E <br />H <br />I <br />DENO R I I WAGAM <br />I <br />C-34970 <br />3 PETERS CANYON RD. STE 110 <br />IRVINE, CA 92606 <br />D <br />G <br />ESI <br />N <br />| <br />ARCHITECTURE <br />H E S T I A A T E L I E R <br />SHEET NUMBER: <br />SHEET TITLE: <br />SCALE: AS SHOWN <br />STORE #: <br />PROJECT #: <br />PR <br />O <br />J <br />E <br />C <br />T <br /> <br />N <br />A <br />M <br />E <br />: <br />PR <br />O <br />J <br />E <br />C <br />T <br /> <br />A <br />D <br />D <br />R <br />E <br />S <br />S <br />: <br />C 2020 STARBUCKS COFFEE COMPANY <br />R <br />ISSUE DATE: <br />2401 UTAH AVENUE SOUTH <br />SEATTLE, WASHINGTON 98134 <br />(206) 318-1575 <br />THESE DRAWINGS AND THE PROJECT MANUAL <br />ARE CONFIDENTIAL AND SHALL REMAIN THE <br />SOLE PROPERTY OF STARBUCKS <br />CORPORATION, WHICH IS THE OWNER OF THE <br />COPYRIGHT IN THIS WORK. THEY SHALL NOT <br />BE REPRODUCED (IN WHOLE OR IN PART), <br />SHARED WITH THIRD PARTIES OR USED IN ANY <br />MANNER ON OTHER PROJECTS OR <br />EXTENSIONS TO THIS PROJECT WITHOUT THE <br />PRIOR WRITTEN CONSENT OF STARBUCKS <br />CORPORATION. THESE DRAWINGS AND <br />SPECIFICATIONS ARE INTENDED TO EXPRESS <br />DESIGN INTENT FOR A PROTOTYPICAL <br />STARBUCKS STORE (WHICH IS SUBJECT TO <br />CHANGE AT ANYTIME) AND DO NOT REFLECT <br />ACTUAL SITE CONDITIONS. NEITHER PARTY <br />SHALL HAVE ANY OBLIGATION NOR LIABILITY TO <br />THE OTHER (EXCEPT STATED ABOVE) UNTIL A <br />WRITTEN AGREEMENT IS FULLY EXECUTED BY <br />BOTH PARTIES. <br />STARBUCKS R <br />DESIGN MANAGER: <br />PRODUCTION DESIGNER: <br />CHECKED BY: <br />STARBUCKS TEMPLATE VERSION: i2021.04.23 <br />7/ <br />5 <br />/ <br />2 <br />0 <br />2 <br />4 <br /> <br />1 <br />0 <br />: <br />2 <br />2 <br />: <br />5 <br />1 <br /> <br />A <br />M <br />W: <br />\ <br />P <br />r <br />o <br />j <br />e <br />c <br />t <br />s <br />\ <br />S <br />t <br />a <br />r <br />b <br />u <br />c <br />k <br />s <br />\ <br />T <br />u <br />s <br />t <br />i <br />n <br /> <br />& <br /> <br />S <br />a <br />n <br />t <br />a <br /> <br />C <br />l <br />a <br />r <br />a <br /> <br />5 <br />1 <br />9 <br />6 <br />9 <br />\ <br />C <br />D <br />\T <br />u <br />s <br />t <br />i <br />n <br /> <br />a <br />n <br />d <br /> <br />S <br />a <br />n <br />t <br />a <br /> <br />C <br />l <br />a <br />r <br />a <br /> <br />- <br /> <br />R <br />e <br />v <br />i <br />t <br /> <br />M <br />o <br />d <br />e <br />l <br />. <br />r <br />v <br />t <br />I501 <br />76085-018 <br />07-02-2024 <br />TU <br />S <br />T <br />I <br />N <br /> <br />& <br /> <br />S <br />A <br />N <br />T <br />A <br />CL <br />A <br />R <br />A <br />23 <br />0 <br />1 <br /> <br />N <br /> <br />T <br />U <br />S <br />T <br />I <br />N <br /> <br />A <br />V <br />E <br />, <br /> <br />S <br />U <br />I <br />T <br />E <br /> <br />A <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br />, <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />51969 <br />CHARLIE CHANG <br />SEPIDEH SHARIFI <br />MAGED GERGES <br />INTERIOR DETAILS <br />2N <br />D <br /> <br />P <br />E <br />R <br />M <br />I <br />T <br /> <br />S <br />U <br />B <br />M <br />I <br />T <br />T <br />A <br />L <br /> <br />0 <br />7 <br />/ <br />0 <br />2 <br />/ <br />2 <br />0 <br />2 <br />4 <br />3/8" = 1'-0"13TYPICAL INTERIOR WALL3/8" = 1'-0"16TYPICAL INTERIOR FURRED WALL AND <br />CEILING FRAMING <br />3/8" = 1'-0"19TYPICAL INTERIOR FURRED WALL AND <br />CEILING FRAMING - 2 3" = 1'-0"15STOREFRONT HEAD DETAIL <br />3" = 1'-0"12STOREFRONT JAMB DETAIL <br />3" = 1'-0"11STOREFRONT SILL DETAIL <br />Revision Schedule <br />Rev Date By Description <br />A 06-13-24 SS 1st Round Comments <br />1 1/2" = 1'-0"20T-BAR HANGING WIRE/ COMPRESSION POST <br />TO STRUCTURE CONNECTION DETAIL <br />A <br />A <br />A <br />A <br />A <br />A <br />A <br />2301 N Tustin Ave <br />#A8/22/2024