Laserfiche WebLink
6.0 Design Loads - Downward (Cont.): <br />6.2 Racking Dimensions for Point Loads (Cont.): <br />Fig. 6.2 Section A-A <br />6.3 Point Load Summary:Notes: <br />DLsys = 98 lbs./module -Base 2 repeat for larger width arrays. <br />Total DL = (Varies on location and ballast quantity) <br />SLm = 0 lbs./module <br />WLin (no snow) = 723 lbs./module <br />WLin (with snow) = 192 lbs./module <br /> <br /> <br />Max Total Load Per Base (lbs.) <br />load combinations (ASD) <br />Location Base <br />DL + Snow DL + 0.6 X Wlin DL + 0.75 X SLm + 0.75(0.6 X WLin) <br />South 1 41 150 63 <br />Interior 2 91 308 134 <br />2nd From North 3 71 288 115 <br />North 4 51 159 72 <br />Table 6.1-A Max Total Load per Base (lbs.) <br /> <br />Max Contact Pressure Table Per Base (psi) <br />load combinations (ASD)# of <br />Pads Location Base <br />DL + Snow DL + 0.6 X Wlin DL + 0.75 X SLm + 0.75(0.6 X WLin) <br />South 1 2 8 3 <br />Interior 2 5 17 7 <br />2nd From North 3 4 16 6 <br />2 <br />North 4 3 9 4 <br />South 1 1 4 2 <br />Interior 2 2 8 4 <br />2nd From North 3 2 8 3 <br />4 <br />North 4 1 4 2 <br />Table 6.1-B Max Point Load Summary (psi) <br />02/01/2024 <br />APPROVED FOR CONSTRUCTION <br />12 <br />PanelClaw, Inc., 1600 Osgood Street, Suite 2023, North Andover, MA 01845 <br />(978) 688.4900 - www.panelclaw.com <br />2130 N Grand Ave <br />10/1/2024