Laserfiche WebLink
7.0 Design Loads - Seismic (Cont.): <br />7.4 Vertical Seismic Force Check: <br />Mechanical attachments may be required for several reasons including building code, roof load limits and array shape. The table <br />below provides the mechanical attachment requirements for each sub-array within this project. <br /> <br />Nomenclature: <br />WP = Sub-Array Weight <br />FPV = Vertical Seismic Force <br />FRV = Vertical Seismic Resisting Force <br /> <br />Array Information Vertical Force Verification Results <br />Sub- <br />Array <br />Name <br />WP <br />(lbs.) <br />FPV <br />(lbs.) <br />FRV <br />(lbs.) <br />0.7 FPV - <br />FRV (lbs.) <br />MA's <br />Required <br />Total MA <br />Capacity <br />(lbs.) <br />Total <br />MA's <br />Provided <br />Acceptable <br />1.1 3,677 774 2,206 -1,665 0 5,880 19 Yes <br />1.2 3,234 680 1,940 -1,464 0 5,098 17 Yes <br />1.3 3,563 750 2,138 -1,613 0 6,092 19 Yes <br />1.4 3,196 672 1,918 -1,447 0 4,815 16 Yes <br />Total:13,670 lbs.2,876 lbs.8,202 lbs.-6,189 lbs.0 21,885 71 <br /> <br />Table7.2 - Summary of Mechanical Attachment Requirements <br />* MA's Required = 0.7 FPV - FRV/MA strength <br />07/16/2024 <br />APPROVED FOR CONSTRUCTION <br />15 <br />PanelClaw, Inc., 1600 Osgood Street, Suite 2023, North Andover, MA 01845 <br />(978) 688.4900 - www.panelclaw.com <br />2130 N Grand Ave <br />10/1/2024