Laserfiche WebLink
GENERAL NOTES <br />FRAMING LUMBER <br />1. <br />2. <br />3. <br />4. <br />6. <br />5. <br />7. <br />8. <br />9. <br />10. <br />12. <br />13. <br />14. <br />15. <br />16. <br />2. <br />3. <br />4. <br />5. <br />1. <br />1. <br />11. <br />ALL STRUCTURAL LUMBER SHALL BE (DOC PS20 OR EQUIVALENT) DOUGLAS FIR <br />LARCH OF THE FOLLOWING MINIMUM GRADES: <br /> A. 2X FRAMING INCLUDING PLATES AND STUDS NO. 2 <br /> B. 4X BEAMS AND HEADERS UP TO 4X12 NO. 2 <br /> C. LARGER THAN 4X12 AND POSTS NO. 1 <br /> D. 6X AND LARGER BEAMS NO. 1 <br />STRUCTURE PANELS SHALL BE DOUGLAS FIR CONFORMING TO U.S. PRODUCT <br />STANDARD DOC PS1 OR DOC PS2 OR ANSI/APA PRP210, AND SHALL BEAR THE <br />STAMP OF AN APPROVED FABRICATOR. <br />INSTALLATION OF VERTICAL AND HORIZONTAL SHEATHING SHALL FIRST BE <br />APPROVED BY THE INSPECTOR PRIOR TO COVERING. <br />NO STRUCTURAL MEMBER SHALL BE CUT OR NOTCHED UNLESS SPECIFICALLY <br />SHOWN ON APPROVED PLANS. <br />MAXIMUM MOISTURE CONTENT OF ALL MUMBER SHALL BE 19%. <br />BOLT HOLES TO BE NOMINAL DIAMETER OF BOLT PLUS 1/16 INCH UNLESS NOTED <br />OTHERWISE. PROVIDE WASHERS UNDER HEAD AND NUTS OF BOLTS AND LAG <br />SCREWS. <br />FRAMING CONNECTIONS SHALL BE "SIMPSON STRONG-TIE". <br />THE NUMBER OF NAILS CONNECTING LUMBER SHALL NOT BE LESS THAN THE <br />MINIMUM REQUIRED ON CRC R602.3(1). <br />ALL NAILS USED ON STRUCTURAL PANELS SHALL BE COMMON NAILS. <br />PROVIDE CONTINUOUS EDGE SUPPORT ALONG TOP AND BOTTOM OF 2X14 JOISTS. <br />BUILT-UP FRAMING MEMBERS SHALL BE CONNECTED AS FOLLOWS: <br /> A. 2-2X 16D AT 12" O.C. STAGGERED TOP AND BOTTOM. <br /> B. 3-2X 5/8" DIA. M.B. AT 18" O.C. STAGGERED TOP AND BOTTOM. <br /> C. 4-2X 5/8" DIA. M.B. AT 18" O.C. STAGGERED TOP AND BOTTOM. <br />PROVIDE DOUBLE JOISTS UNDER PARALLEL PARTITIONS. <br />PROVIDE SOLID BLOCKING UNDER ALL NON-PARALLEL PARTITIONS. <br />INSTALL LAG BOLTS BY DRILLING LEAD HOLE 65% TO 75% OF SHANK DIAMETER <br />AND FULL DIAMETER FOR SHANK PORTION. USE SOAP OR OTHER APPROVED <br />LUBRICANT ON THREADS. INSTALLATION SHALL BE BY TIGHTENING OF SCREW NOT <br />BY HAMMERING. <br />TRUSS JOISTS SHOP DRAWINGS SHALL BE PROVIDED BY THE SUPPLIER AND <br />SUBMITTED TO THE BULIDING DEPARTMENT FOR APPROVAL PRIOR TO <br />FABRICATION. <br />SHOP DRAWINGS SHALL BE STAMPED AND WET SIGNED BY A LICENSED ENGINEER. <br />DOUBLE TOP PLATES WITH END JOINTS OFFSET BY 48" MIN. FOR STUD WALL <br />GLULAM/PARALLAM/MICROLAM BEAMS <br />GLUE LAMINATED BEAMS SHALL BE PER CBC (AITC A190.1 & ASTM 3737) AND <br />AMERICAN INSTITUTE OF TIMBER <br />CONSTRUCTION 117. CONBINATION SYMBOLS SHALL BE AS FOLLOWS: <br /> A) 24F-V4 DF/DF FOR SIMPLE BEAMS <br /> B) 24F-V8 DF/DF FOR CANTILEVERED BEAMS <br />PARALLAM BEAMS SHALL BE 2.0E PSL I LEVEL, ICC ESR- 1387 <br />MICROLAM BEAMS SHALL BE 2.0E LVL <br />LAMINATED BEAMS SHALL BE FABRICATED BY A LICENSED FABRICATOR AND <br />SHALL BE ACCOMPANIED TO <br />THE JOB SITE WITH CERTIFICATE OF FABRICATION. <br />SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT OR ENGINEER FOR <br />REVIEW PRIOR TO FABRICATION. <br />STRUCTURAL AND MISCELLANEOUS STEEL <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />8. <br />9. <br />ALL STRUCTURAL AND MISCELLANEOUS STEEL SHALL CONFORM TO <br />A.S.T.M. A-36 AND SHALL BE FABRICATED AND ERECTED IN ACCORDANCE <br />WITH THE A.I.S.C. SPECIFICATIONS FOR THE DESIGN, FABRICATION AND <br />ERECTION OF STRUCTURAL STEEL FOR BUILDING, LATEST EDITION. <br />PIPE COLUMNS SHALL CONFORM TO A.S.T.M. A-53 GRADE B. <br />TUBULAR STEEL SHALL CONFORM TO A.S.T.M. A500 GRADE B. <br />BOLTS SHALL CONFORM TO A.S.T.M. A-307 UNLESS NOTED OTHERWISE. <br />SHOP DRAWING SHALL BE SUBMITTED TO THE ARCHITECT AND ENGINEER <br />AND BUILDING DEPARTMENT FOR <br />REVIEW PRIOR TO FABRICATION. <br />FABRICATION SHALL BE DONE IN THE SHOP OF LICENSED FABRICATORS. <br />USE ELECTRIC ARC PROCESS WELDING WITH E70XX ELECTRODES. <br />ALL WELDING SHALL BE DONE IN THE SHOP OF LICENSED FABRICATOR OR <br />PROVIDE CONTINUOUS SPECIAL INSPECTION BY A RESGISTERED DEPUTY <br />INSPECTOR. <br />WHERE A FILLET WELD SYMBOL IS USED IN THE PLANS WITHOUT <br />INDICATION OF SIZE, THE MINIMUM WELD SIZE AS SPECIFIED IN THE A.I.S.C. <br />MANUAL OF STEEL CONSTRUCTION SHALL BE USED. <br />9.ENCLOSED USABLE SPACE UNDER STAIRWAY REQUIRES ONE HOUR <br />CONSTRUCTION ON ENCLOSED SIDE <br />17. <br />1. <br />2. <br />PROVIDE HOSE BIBB WITH NON-REMOVABLE BACK FLOW PREVENTED @ DWELLING. <br />PLUMBING REQUIREMENT: <br /> NOTES <br />CONTROL VALVER FOR SHOWER(TUB- SHOWER SHALL BE OF PRESSURE BALANCE <br />OR THERMOSTATIC MIXING VALVE <br />MAX. FLOW RATE <br />WC. = 1.28 GPM. <br />SHOWER HEAD =1.8 GPM <br />USE 2- 15 # FEET WHEN STUCCO IS APPLIED OVER PLYWOOD <br />1. <br />2. <br />3. <br />4. <br />SHOWERS SHALL BE FINISHED 72" ABOVE DRAIN W/ SURFACE MATERIAL NOT <br />ADVERSELY EFFECTED BY MOISTURE <br />5.WATER HEATER MUST HAVE A PRESSURE AND A TEMPERATURE RELIEF VALVE <br />PLUMBED TO THE OUTSIDE OF THE BUILDING <br />12" MIN. ACCESS PANEL IS REQUIRED FOR THE BATHTUB TRAP SLIP JOINT. <br />CLEANOUT IN UNDERFLOOR PIPING SHALL BE EXTENDED TO OR ABOVE THE FLOOR <br />OR EXTENDED TO THE EXTERIOR OF THE BUILDING UNLESS: AN 18" X30" <br />CLEARANCE IS PROVIDED FROM THE MEANS OF ACCESS. IN ADDTION, NO CLEAN <br />OUT SHALL BE MORE THAN 20'-0" FROM THE ACCESS OPENING. <br />WATER HEATER WILL HAVE AN R-16 BLANKET OR BE RATED FOR R-16 <br />8. <br />6. <br />7. <br />SHOWER AND BATHTUB DOORS AND THE ENCLOSURES TEMPERED GLASS <br />AT COUNTER SPACE IN KITCHEN AND DINING AREA, RECEPTACLE SHALL BE <br />PROVIDED AS FOLLOWS: <br />RECEPTACLE SHALL BE PROVIDED SO THAT NO POINT ALONG THE WALL IS MORE <br />THAN 24" FROM A RECEPTACLE <br />RECEPTACLES OUTLETS SHALL BE PLACED @12'-0" MAXIMUM AND SHALL BE <br />LOCATED WITH 6'-0" OF DOOR OPENINGS. <br />DETECTORS MUST RECEIVE POWER FROM THE BUILDING WIRING, WITH BATTERY <br />BACKUP WITHOUT A DISCONNECTING SWITCH, OTHER THAN FOR OVER OVER <br />CURRENT PROTECTION, EXCEPT THAT IN THE EXISTING PORTION OF AN EXISTING <br />BUILDING (NOT IN AN ADDITION), THEY MAY BE BATTERY OPERATED (CRC SEC. R314). <br />3. <br />RECEPTACLE/OUTLET: <br />2. <br />1. <br />PROVIDE HEATING TO PRODUCE REQUIRED ROOM TEMPERATURE OF 70 <br />DEGREE @ 3 FEET ABOVE FLOOR. <br />1. <br />MECHANICAL REQUIREMENT: <br />SERVICE: <br />DOORS & WINDOWS <br />IN ALL BEDROOMS, PROVIDE ON OPENABLE ESCAPE WINDOW MEETING ALL OF THE <br />FOLLOWING: AN OPENABLE AREA OF NOT LESS THAN 5.7 SQ. FT., A MINIMUN CLEAR 24 <br />INCHES HEIGHT AND 20 INCHES WIDTH AN A SILL HEIGHT NOT OVER 44 INCHES ABOVE <br />THE FLOOR. <br />GLAZING ADJACENT TO DOORS, SHALL MEET WITH CRC308.4.2. <br />STRUCTURE NOTES: <br />CONCRETE: <br />REINFORCING STEEL: ASTM A615, GRADE #60. #4 AND SMALLER, GRADE #40.A. <br />CONCRETE NORMAL WEIGHT WITH COMPRESSIVE STRENGTH OF 3,000 PSI AT 28 <br />DAYS. WATER-CEMENT RATIO 0.45 AND CEMENT TYPE V OR PER SOILS REPORT. <br />B. <br />FOR STEM WALLS LONGER THAN 24", PROVIDE #4 VERTICAL BARS @ 24" O.C.C. <br />LANDING 3 1/2" CONC W/ 6X6 10X10 MESH.STEEL:D. <br />SHAPED AND PLATE: ASTM A36; TUBE: ASTM A500, GRADE B.1. <br />BOLTS: ASTM A307.2. <br />WOOD: <br />FRAMING MEMBERS : DOUGLAS FIR LARCH (DOC PS20)A. <br />COLUMNS, BEAMS, HEADERS, AND PLATES : NO 1B. <br />STUDS, JOISTS, RAFTERS, BLOCKINGS: NO 2C. <br />WALL SILLS, NAILERS, AND LEDGERS IN CONTACT WITH CONCRETE: PRESERVATIVE <br />TREATED DOUGLAS FIR. <br />D. <br />FRAMING CONNECTION HARDWARE: AS MANUFACTURED BY SIMPSON STRONGTIE <br />CO. OR APPROVED EQUIVALENTS. SIMPSON DESIGNATIONS USED. USE NAILS PER <br />ICC APPROVAL AND AS RECOMMENDED BY SIMPSON FOR EACH DEVICE. <br />E. <br />COMMON NAILS, UNLESS OTHERWISE NOTED, ALL NAILING TO BE PER CRC TABLE <br />R602.3(1), UNLESS OTHERWISE NOTED. <br />F. <br />EXPOSED TO WEATHER: <br />ALL EXPOSED STEEL MEMBERS SHALL BE COATED WITH A ZINC RICH PRIMER.A. <br />ALL EXTERIOR HANGERS AND OTHER SIMPSON TYPE PRODUCTS SHALL BE GALVANIZED.B. <br />ALL PLYWOOD SHALL BE OF AN EXP. 1 GRADE.C. <br />FRAMING: <br />DOUBLE FLOOR JOISTS REQUIRED UNDER PARALLEL BEARING WALLS.A. <br />APPLY CONT. LINE OF GLUE TO FLOOR PANELS AT ALL JOIST.B. <br />BLOCKING ARE REQUIRED AT ALL SHEAR WALL PANEL EDGES.C. <br />CONSTRUCT OF PLYWOOD SHEAR WALL SHALL BE WITH COMMON NAILS ONLY.D. <br />HOLD DOWN BOLT HOLES AT EACH END OF THE PLYWOOD SHEAR WALL SHALL <br />HAVE TOLERANCE OF NO MORE THAN 1/16". <br />E. <br />ALL POSTS WITH HOLD DOWNS OR UPLIFT STRAPS SHALL HAVE CONTINUOUS <br />EDGE NAILING. <br />F. <br />ALL ANCHOR BOLTS SHALL BE ATTACHED TO THE SILL PLATE WITH 3"X3"X.229" <br />STEEL PLATE WASHERS. <br />G. <br />HORIZONTAL PLYWOOD SHEARTHING: <br />VERTICAL PLYWOOD SHEATHING: (DOC PS1 OR PS2) (SEE SCHEDULE).A. <br />EXTERIOR STUCCO NOTES: CRC SECTION R703 <br />STUCCO LATH AND DRYWALL SHALL BE NAILED TO ALL STUDS AND TO <br />TOP AND BOTTOM PLATES <br />A. <br />7.FOUNDATION PLATES OR SILLS BOLTED WITH 5/8" DIA. X 12" ANCHOR BOLTS W/ 7" <br />MIN. EMBEDMENT AT NOT MORE THAN 4'-0" O.C. ONE BOLT IS REQUIRED WITHIN 12" <br />OF EACH END OF EACH MEMBER AND A MIN. OF 2 BOLTS ARE REQUIRED PER <br />MEMBER (SEC. 2304.3.4 CBC). <br />FASTENERS SHALL BE HOT- DIPPED ZINC- COATED GALVANIZED STEEL. <br />CONCRETE: f'c=4500 PSI, w/c=0.45 AND TYPE V CEMENT <br />8. <br />1. <br />2. <br />FOUNDATION <br />4. <br />5. <br />6. <br />IN LIEU OF A SOIL REPORT, FOUNDATION HAVE BEEN DESIGNED USING MAX ALLOWABLE <br />SOIL BEARING CAPACITY OF 1,500 PSI. <br />FOUNDATION DESIGN IS BASED ON NON-EXPANSIVE SOIL. <br />EXISTING FOUNDATIONS ARE ASSUMED TO BE IN GOOD CONDITION. CONTRACTOR SHALL <br />NOTIFY THE ENGINEER OF ANY FOUNDATION WITH SIGNIFICANT SETTLEMENT, SEVERE <br />CRACKING OR ANY INDICATION OF STRUCTURAL FAILURE OR DISTRESS OR DEFECT. <br />THE CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING, FENCE ENCLOSURES AND <br />PROTECTION LIFE AND PROPERTY UNTIL THE PROJECT IS COMPLETE. <br />3. <br />THE ARCHITECTURAL FLOOR PLAN AND NOTIFY THE PROJECT DESIGNER OF ANY <br />DISCREPANCIES PRIOR TO STARTING WORK. <br />TREATED LUMBER CONFORMING TO (CRC) FOR FOUNDATION PLATES AND SILL <br />1. <br />2. <br />3. <br />5. <br />7. <br />8. <br />6. <br />ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE 2022 CALIFORNIA <br />RESIDENTIAL CODES AND ALL AMENDMENTS AND LOCAL, COUNTY, STATE AND <br />FEDERAL REGULATIONS. <br />THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE WORK OF ALL <br />TRADES AND SHALL CHECK ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO <br />BID AND SIGNING OF CONTRACT. ALL DISCREPANCIES SHALL BE CALLED TO THE <br />ATTENTION OF THE ARCHITECT AND ENGINEER AND BE RESOLVED IN WRITING <br />BEFORE PROCCEDING WITH THE WORK. <br />GENERAL NOTES AND TYPICAL DETAILS SHALL APPLY TO ALL PARTS OF THE JOB <br />EXCEPT WHERE THEY ARE IN CONFLICT WITH DETAILS AND NOTES ON OTHER <br />DOCUMENTS; THE MORE STRICT CONDITION APPLIES SUBJECT TO REVIEW BY THE <br />ENGINEER. <br />ALL INFORMATION SHOWN ON THE PLANS RELATIVE TO EXISTING CONDITION WERE <br />CAREFULLY TAKEN IN THE FIELD BUT WITHOUT GUARANTEE OF ACCURACY. WHERE <br />ACTUAL CONDITIONS ARE IN CONFLICT WITH THE PLANS, THEY SHALL BE <br />REPORTED TO THE ENGINEER SO THAT PROPER CHANGES CAN BE MADE. <br />REQUIRED SHOP DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER AND THE <br />BUILDING DEPARTMENT FOR REVIEW. <br />MODIFICATION OF STRUCTURAL PLANS AND MATERIAL SUBSTITUTIONS SHALL NOT <br />BE DONE WITHOUT WRITTEN APPROVAL OF THE ENGINEER. <br />THE APPROVED PLANS AND SPECIFICATIONS REPRESENT THE FINISH STRUCTURE <br />AND DO NOT INCLUDE THE METHODS OF CONSTRUCTION. THE CONTRACTOR <br />SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE SOLELY RESPONSIBLE <br />FOR CONSTRUCTION METHODS, MEANS, TECHINQUES, SEQUENCES AND <br />PROCEDURES INCLUDING BUT NOT LIMITED TO SHORING, INSURANCE, FENCING, <br />CONSTRUCTION CANOPY, SCAFFOLDING ETC. FIELD OBSERVATIONS BY THE <br />ENGINEER SHALL NOT BE CONSIDERD AS INSPECTIONS AS REQUIRED BY THE <br />CODE. <br />REFER TO THE ARCHITECTURAL PLANS FOR DIMENSIONS, OPENINGS, LAYOUT ETC. <br />4. <br />REINFORCING STEEL <br />1. <br />2. <br />3. <br />4. <br />5. <br />6. <br />7. <br />9. <br />8. <br />REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO THE REQUIREMENTS OF <br />A.S.T.M. A-615 <br />GRADE 60 FOR BARS LARGER THAN #4, GR.40 FOR #4 OR SMALLER. <br />WELDED WIRE FABRIC SHALL CONFORM TO A.S.T.M. A-82 AND A-185 . LAP 12 INCHES MINIMUM. <br />DELTAILING,FABRICATION AND ERECTION OF REINFORCING BARS SHALL CONFORM TO THE <br />LATEST EDITION OF A.C.I. <br />MANUAL OF STANDARD PRACTICE FOR DETAILING AND REINFORCED CONCRETE <br />STRUCTURES. <br />MINIMUM COVER FORCAST IN PLACE CONCRETE SHALL BE AS FOLLOWS: <br /> A. POURED AGAIN EARTH 3 INCHES <br /> B. POURED AGAIN FORM BELOW GRADE 2 INCHES <br /> C. FORMED SLABS 3/4 INCH <br /> D. SLAB ON GRADE, TOP COVER 1 INCH <br /> E. COLUMN AND BEAM MAIN BARS 1-1/2 INCHES <br /> F. WALLS EXPOSED TO WEATHER # 6 AND LARGER 2 INCHES <br /> # 5 AND SMALLER 1-1/2 INCHES <br />BARS SHALL BE CLEAN OF RUST, GREASE AND OTHER DELETERIOUS MATERIAL THAT MAY <br />AFFECT BOND. <br />ALL BEND SHALL BE MADE COLD. <br />LAP SPLICE LENGTH SHALL BE 40 BARS DIAMETERS MINIMUM AND SHALL BE STAGGERED. <br />ALL REINFORCING BARS, EMBEDS, ANCHOR BOLTS, HOLDOWNS ETC. SHALL BE SECURED IN <br />PLACE PRIOR TO PLACEMENT OF CONCRETE. <br />CODE REQUIRED INSPECTIONS BY JURISTDICTION AUTHORITY SHALL BE MADE AN SIGNED <br />OFF PRIOR TO PLACEMENT OF CONCRETE. <br />3.5.0 SQ. FT. AT GRADE LEVEL. <br />USE GRADE "D" PAPER BACKING WHEN STUCCO IS APPLIED OVER PLYWOOD (CRC).B. <br />ELECTRICAL REQUIREMENT: <br />A, B, C <br />BLOCKING BETWEEN CEILING JOISTS, RAFTERS OR TRUSSES TO <br />TOP PLATE OR OTHER FRAMING BELOW <br />1 TOE NAIL <br />EACH END TOE NAIL <br />6" O.C. FACE NAIL <br />PER JOIST, TOE NAIL2 <br />3 <br />STUD TO STUD (NOT AT BRACED WALL PANELS)8 <br />24" O.C. FACE NAIL <br />16" O.C. FACE NAIL <br />STUD TO STUD AND ABUTTING STUDS AT INTERSECTING <br />WALL CORNERS (AT BRACED WALL PANELS) <br />9 12" O.C. FACE NAIL <br />16" O.C. FACE NAIL <br />BUILT-UP HEADER (2" TO 2" HEADER WITH 1/2" SPACER)10 16" O.C. EACH EDGE FACE NAIL <br />12" O.C. EACH EDGE FACE NAIL <br />CONTINUOUS HEADER TO STUD11 TOE NAIL <br />TOP PLATE TO TOP PLATE13 <br />DOUBLE TOP PLATE SPLICE FACE NAIL ON EACH SIDE <br />OF END JOINT (MINIMUM <br />24" LAP SPLICE LENGTH <br />EACH SIDE OF END JOINT) <br />BOTTOM PLATE TO JOIST, RIM JOIST, BAND JOIST OR <br />BLOCKING (NOT AT BRACED WALL PANELS) <br />15 <br />BOTTOM PLATE TO JOIST, RIM JOIST, BAND JOIST OR <br />BLOCKING (AT BRACED WALL PANEL) <br />16 16" O.C. FACE NAIL <br />TOP OR BOTTOM PLATE TO STUD17 <br />TOE NAIL <br />END NAIL <br />TOP PLATES, LAPS AT CORNERS AND INTERSECTIONS18 FACE NAIL <br />1" BRACE TO EACH STUD AND PLATE19 FACE NAIL <br />1" X 6" SHEATHING TO EACH BEARING20 FACE NAIL <br />1" X 8" AND WIDER SHEATHING TO EACH BEARING21 FACE NAIL <br />JOIST TO SILL, TOP PLATE OR GIRDER22 TOE NAIL <br />RIM JOIST, BAND JOIST OR BLOCKING TO SILL OR TOP <br />PLATE (ROOF APPLICATIONS ALSO) <br />23 <br />4" O.C. TOE NAIL <br />6" O.C. TOE NAIL <br />1" X 6" SUBFLOOR OR LESS TO EACH JOIST24 FACE NAIL <br />14 <br />2" SUBFLOOR TO JOIST OR GIRDER25 BLIND AND FACE NAIL <br />2" PLANKS (PLANK & BEAM — FLOOR & ROOF)26 AT EACH BEARING, <br />FACE NAIL <br />BAND OR RIM JOIST TO JOIST27 END NAIL <br />BUILT-UP GIRDERS AND BEAMS, 2-INCH LUMBER <br />LAYERS <br />28 <br />FACE NAIL AT ENDS <br />AND AT EACH SPLICE <br />NAIL EACH LAYER AS <br />FOLLOWS: 32" O.C. AT TOP <br />& BOTTOM & STAGGERED. <br />24" O.C. FACE NAIL AT TOP <br />& BOTTOM STAGGERED <br />ON OPPOSITE SIDES <br />LEDGER STRIP SUPPORTING JOISTS OR RAFTERS29 AT EACH JOIST OR <br />RAFTER, FACE NAIL <br />BRIDGING TO JOIST30 EACH END, TOE NAIL <br />A, B, C <br />H C, E <br />3/8" – 1/2"31 <br />6D COMMON OR DEFORMED (2" x 0.113" x 0.266" HEAD); OR <br />2 3/8" x 0.113" x 0.266" HEAD NAIL (SUBFLOOR, WALL) <br />8D COMMON (2 1/2" X 0.131") NAIL (ROOF)' OR <br />RSRS-01 (2 3/8" x 0.113") NAIL (ROOF) <br />8D COMMON (2 1/2" X 0.131") NAIL (SUBFLOOR, WALL) <br />10D COMMON (3" X 0.148") NAIL; OR <br />8D (2 1/2" X 0.131") DEFORMED NAIL <br />1 1/2" x 0.120" GALVANIZED ROOFING NAIL, 7/16" HEAD DIAMETER; OR <br />1 1/4" LONG 16 GA. STAPLE WITH 7/16" OR 1" CROWN <br />1 3/4" x 0.120" GALVANIZED ROOFING NAIL, 7/16" HEAD DIAMETER; OR <br />1 1/4" LONG 16 GA. STAPLE WITH 7/16" OR 1" CROWN <br />1 1/2" x 0.120" GALVANIZED ROOFING NAIL, 7/16" HEAD DIAMETER; OR <br />1 1/4" LONG 16 GA.; <br />8D COMMON (2 1/2" X 0.131") NAIL <br />8D DEFORMED (2 1/2" X 0.131") NAIL; OR <br />10D COMMON (3" X 0.148" ) NAIL; OR <br />DEFORMED (2" X 0.113"); OR <br />I 6 6 F <br />6 12 <br />9/32" – 3/4"32 <br />7/8" – 1 1/4"33 <br />G <br />1/2" STRUCTURAL CELLULOSIC <br />FIBERBOARD SHEATHING <br />34 <br />3 6 <br />3 6 <br />7 7 <br />7 7 <br />25/32" STRUCTURAL CELLULOSIC <br />FIBERBOARD SHEATHING <br />35 <br />1/2" GYPSUM SHEATHING36 <br />5/8" GYPSUM SHEATHING37 <br />D <br />D <br />6 12 <br />6 12 <br />6 12 <br />3/4" AND LESS38 <br />7/8" – 1"39 <br />1 1/8" – 1 1/4"40 <br />FOR SI: 1 INCH = 25.4 MM, 1 FOOT = 304.8 MM, 1 MILE PER HOUR = 0.447 M/S; 1 KSI = 6.895 MPa. <br />A. NAILS ARE SMOOTH-COMMON, BOX OR DEFORMED SHANKS EXCEPT WHERE OTHERWISE STATED. NAILS USED FOR FRAMING AND SHEATHING <br />CONNECTIONS ARE CARBON STEEL AND SHALL HAVE MINIMUM AVERAGE BENDING YIELD STRENGTHS AS SHOWN: 80 KSI FOR SHANK DIAMETER OF 0.192 <br />INCH (20D COMMON NAIL), 90 KSI FOR SHANK DIAMETERS LARGER THAN 0.142 INCH BUT NOT LARGER THAN 0.177 INCH, AND 100 KSI FOR SHANK <br />DIAMETERS OF 0.142 INCH OR LESS. CONNECTIONS USING NAILS AND STAPLES OF OTHER MATERIALS, SUCH AS STAINLESS STEEL, SHALL BE DESIGNED <br />BY ACCEPTED ENGINEERING PRACTICE OR APPROVED UNDER SECTION R104.11. <br />B. SRSRS-01 IS A ROOF SHEATHING RING SHANK NAIL MEETING THE SPECIFICATIONS IN ASTM F1667. <br />C. NAILS SHALL BE SPACED AT NOT MORE THAN 6 INCHES ON CENTER AT ALL SUPPORTS WHERE SPANS ARE 48 INCHES OR GREATER. <br />D. FOUR-FOOT BY 8-FOOT OR 4-FOOT BY 9-FOOT PANELS SHALL BE APPLIED VERTICALLY. <br />E. SPACING OF FASTENERS NOT INCLUDED IN THIS TABLE SHALL BE BASED ON TABLE R602.3(2). <br />F. FOR WOOD STRUCTURAL PANEL ROOF SHEATHING ATTACHED TO GABLE END ROOF FRAMING AND TO INTERMEDIATE SUPPORTS WITHIN 48 INCHES OF <br />ROOF EDGES AND RIDGES, NAILS SHALL BE SPACED AT 4 INCHES ON CENTER WHERE THE ULTIMATE DESIGN WIND SPEED IS GREATER THAN 130 MPH IN <br />EXPOSURE B OR GREATER THAN 110 MPH IN EXPOSURE C. <br />G. GYPSUM SHEATHING SHALL CONFORM TO ASTM C1396 AND SHALL BE INSTALLED IN ACCORDANCE WITH ASTM C1280OR GA 253. FIBERBOARD SHEATHING <br />SHALL CONFORM TO ASTM C208. <br />H. SPACING OF FASTENERS ON FLOOR SHEATHING PANEL EDGES APPLIES TO PANEL EDGES SUPPORTED BY FRAMING MEMBERS AND REQUIRED BLOCKING <br />AND AT FLOOR PERIMETERS ONLY. SPACING OF FASTENERS ON ROOF SHEATHING PANEL EDGES APPLIES TO PANEL EDGES SUPPORTED BY FRAMING <br />MEMBERS AND REQUIRED BLOCKING. BLOCKING OF ROOF OR FLOOR SHEATHING PANEL EDGES PERPENDICULAR TO THE FRAMING MEMBERS NEED NOT <br />BE PROVIDED EXCEPT AS REQUIRED BY OTHER PROVISIONS OF THIS CODE. FLOOR PERIMETER SHALL BE SUPPORTED BY FRAMING MEMBERS OR SOLID <br />BLOCKING. <br />I. WHERE A RAFTER IS FASTENED TO AN ADJACENT PARALLEL CEILING JOIST IN ACCORDANCE WITH THIS SCHEDULE, PROVIDE TWO TOE NAILS ON ONE SIDE <br />OF THE RAFTER AND TOE NAILS FROM THE CEILING JOIST TO TOP PLATE IN ACCORDANCE WITH THIS SCHEDULE. THE TOE NAIL ON THE OPPOSITE SIDE OF <br />THE RAFTER SHALL NOT BE REQUIRED. <br />4-8D BOX (2 1/2" X 0.113") OR <br />3-8D COMMON (2 1/2" X 0.131"); OR <br />3-10D BOX (3" X 0.128"); OR <br />3-3" X 0.131" NAILS <br />16D BOX (3-1/2" X 0.162"); OR <br />3" X 0.131" NAILS <br />2-8D COMMON (2 1/2" X 0.131") OR <br />2-3" X 0.131" NAILS <br />2-16D COMMON (3-1/2" X 0.162"); OR <br />3-3" X 0.131" NAILS <br />4-3" X 0.131" NAILS <br />16D COMMON (3 1/2" X 0.162") <br />10D BOX (3" X 0.128"); OR <br />3" X 0.131" NAILS <br />16D BOX (3 1/2" X 0.135"); OR <br />3" X 0.131" NAILS <br />16D COMMON (3 1/2" X 0.162") <br />16D COMMON (3 1/2" X 0.162") <br />16D BOX (3 1/2" X 0.135") <br />5-8D BOX (2 1/2" X 0.113"); OR <br />4-8D COMMON (2 1/2" X 0.131"); OR <br />4-10D BOX (3" X 0.128") <br />16D COMMON (3 1/2" X 0.162") <br />3" X 0.131" NAILS <br />8-16D COMMON (3 1/2" X 0.162"); OR <br />12-16D BOX (3 1/2" X 0.135"); OR <br />12-10D BOX (3" X 0.128"); OR <br />12-3" X 0.131" NAILS <br />3-16D BOX (3 1/2" X 0.135"); OR <br />2-16D COMMON (3 1/2" X 0.162"); OR <br />4-3" X 0.131" NAILS <br />4-8D BOX (2 1/2" X 0.113"); OR <br />3-16D BOX (3 1/2" X 0.135"); OR <br />4-8D COMMON (2 1/2" X 0.131"); OR <br />4-10D BOX (3" X 0.128"); OR <br />4-3" X 0.131" NAILS <br />3-16D BOX (3 1/2" X 0.135"); OR <br />2-16D COMMON (3 1/2" X 0.162"); OR <br />3-10D BOX (3" X 0.128"); OR <br />3-3" X 0.131" NAILS <br />3-10D BOX (3" X 0.128"); OR <br />2-16D COMMON (3 1/2" X 0.162"); OR <br />3-3" X 0.131" NAILS <br />3-8D BOX (2 1/2" X 0.113"); OR <br />2-8D COMMON (2 1/2" X 0.131"); OR <br />2-10D BOX (3" X 0.128"); OR <br />2 STAPLES 1 3/4" <br />3-8D BOX (2 1/2" X 0.113"); OR <br />2-8D COMMON (2 1/2" X 0.131"); OR <br />2-10D BOX (3" X 0.128"); OR <br />3-8D BOX (2 1/2" X 0.113"); OR <br />3-8D COMMON (2 1/2" X 0.131"); OR <br />3-10D BOX (3" X 0.128"); OR <br />WIDER THAN 1" X 8" <br />4-8D BOX (2 1/2" X 0.113"); OR <br />3-8D COMMON (2 1/2" X 0.131"); OR <br />3-10D BOX (3" X 0.128"); OR <br />4-8D BOX (2 1/2" X 0.113"); OR <br />3-8D COMMON (2 1/2" X 0.131"); OR <br />3-10D BOX (3" X 0.128"); OR <br />3-3" X 0.131" NAILS <br />8D BOX (2 1/2" X 0.113") <br />8D COMMON (2 1/2" X 0.131"); OR <br />10D BOX (3" X 0.128"); OR <br />3" X 0.131" NAILS <br />3-8D BOX (2 1/2" X 0.113"); OR <br />2-8D COMMON (2 1/2" X 0.131"); OR <br />3-10D BOX (3" X 0.128"); OR <br />3-16D BOX (3 1/2" X 0.135"); OR <br />2-16D COMMON (3 1/2" X 0.162") <br />3-16D BOX (3 1/2" X 0.135"); OR <br />2-16D COMMON (3 1/2" X 0.162") <br />3-16D COMMON (3 1/2" X 0.162"); OR <br />4-10 BOX (3" X 0.128"); OR <br />4-3" X 0.131" NAILS; OR <br />4-3" X14 GA. STAPLES, 7/16" CROWN <br />20D COMMON (4" X 0.192"); OR <br />10D BOX (3" X 0.128"); OR <br />3" × 0.131" NAILS <br />AND: <br />2-20D COMMON (4" X 0.192"); OR <br />3-10D BOX (3" X 0.128"); OR <br />3-3" X 0.131" NAILS <br />4-16D BOX (3 1/2" X 0.135"); OR <br />3-16D COMMON (3 1/2" X 0.162"); OR <br />4-10D BOX (3" X 0.128"); OR <br />4-3" X 0.131" NAILS <br />2-10D BOX (3" X 0.128"); OR <br />2 STAPLES, 1" CROWN, 16 GA., 1 3/4" LONG <br />3 STAPLES, 1" CROWN, 16 GA., 1 3/4" LONG <br />4 STAPLES, 1" CROWN, 16 GA., 1 3/4" LONG <br />2 STAPLES, 1" CROWN, 16 GA., 1 3/4" LONG <br />TABLE R602.3(1) FASTENER SCHEDULE -CRC 2022 <br />BLOCKING BETWEEN RAFTERS OR TRUSS NOT AT THE WALL <br />TOP PLATES, TO RAFTER OR TRUSS <br />END NAIL <br />FLAT BLOCKING TO TRUSS AND WEB FILLER <br />CEILING JOISTS TO TOP PLATE <br />4-8D BOX (2-1/2" X 0.113"); OR <br />3-8D COMMON (2-1/2" X 0.131"); OR <br />3-8D BOX(3" X 0.128"); OR <br />3-3" X 0.131" NAILS <br />CEILING JOIST NOT ATTACHED TO PARALLEL RAFTER, <br />LAPS OVER PARTITIONS [SEE SECTIONS R802.5.2 <br />AND TABLE R802.5.2(1)] <br />FACE NAIL <br />4-10D BOX (3" X 0.128"); OR <br />3-16D COMMON (3 1/2" X 0.162");OR <br />CEILING JOIST ATTACHED TO PARALLEL RAFTER (HEEL <br />JOINT) [SEE SECTIONS R802.5.2 AND TABLE R802.5.2(1)] <br />4 FACE NAILTABLE R802.5.2(1) <br />COLLAR TIE TO RAFTER, FACE NAIL5 FACE NAIL <br />EACH RAFTER <br />4-10D BOX (3" X 0.128"); OR <br />3-10D COMMON (3" X 0.148"); OR <br />4-3" X 0.131" NAILS <br />RAFTER OR ROOF TRUSS TO PLATE6 2 TOE NAILS ON ONE SIDE <br />AND 1 TOE NAIL ON <br />OPPOSITE SIDE OF EACH <br />RAFTER OR TRUSS <br />3-16D BOX NAILS (3 1/2"X0.135"); OR <br />3-10D COMMON (3" X 0.148"); OR <br />4-10D BOX (3" X 0.128"); OR <br />4-3" X 0.131" NAILS I <br />ROOF RAFTERS TO RIDGE, VALLEY OR HIP RAFTERS <br />OR ROOF RAFTER TO MINIMUM 2" RIDGE BEAM <br />7 TOE NAIL <br />4-16D BOX (3 1/2" X 0.135"); OR <br />3-10D COMMON (3" X 0.148"); OR <br />4-10D BOX (3" X 0.128"); OR <br />4-3" X 0.131" NAILS <br />3-16D BOX 3 1/2" X 0.135"); OR <br />2-16D COMMON (3 1/2" X 0.162"); OR <br />3-10D BOX (3" X 0.128"); OR <br />3-3" X 0.131" NAILS <br />END NAIL <br />ADJACENT FULL-HEIGHT STUD TO END OF HEADER12 <br />4-16D BOX (3 1/2" X 0.135"); OR <br />3-16D COMMON (3 1/2" X 0.162"); OR <br />4-10D BOX (3" X 0.128"); OR <br />4-3" X 0.131" NAILS <br />END NAIL <br />10D BOX (3" X 0.128"); OR <br />16" O.C. FACE NAIL <br />12" O.C. FACE NAIL <br />16" O.C. FACE NAIL <br />12" O.C. FACE NAIL <br />16D COMMON (3 1/2" x 0.162") <br />16D BOX (3 1/2" X 0.135"); OR <br />3" X 0.131" NAILS <br />2-8D COMMON (2 1/2" X 0.131"); OR <br />2-3" X 0.131" NAILS <br />6 6 FB <br />6 12 <br />8D COMMON (2 1/2" X 0.131") NAIL (ROOF); OR <br />RSRS-01; (2 3/8" x 0.113") NAIL (ROOF)B 6 6 F <br />DEFORMED 2 3/8" x 0.113" x 0.266" HEAD (WALL OR SUBFLOOR)6 12 <br />STAPLE GALVANIZED, 1 1/2" LONG; 7/16" OR 1" CROWN OR 1 1/4" <br />SCREWS, TYPE W OR S <br />1 3/4" x 0.120" GALVANIZED ROOFING NAIL, 7/16" HEAD DIAMETER; OR <br />1 1/4" LONG 16 GA.; <br />STAPLE GALVANIZED, 1 1/2" LONG; 7/16" OR 1" CROWN OR 1 1/4" <br />SCREWS, TYPE W OR S <br />DEFORMED (2 1/2" X 0.120") NAIL <br />DEFORMED (2" X 0.113"); OR <br />DEFORMED (2 1/2" X 0.120") NAIL <br />DEFORMED (2" X 0.113"); OR <br />DEFORMED (2 1/2" X 0.120") NAIL; OR <br />9. <br />SCALE: <br />DRAWN BY: <br />DATE: <br />PLAN CHECK <br />DRAWING TITLE: <br />DATEREVISIONS: <br />HN <br />12-11-2024 <br />AS NOTED <br />00-00-0000 <br />SHEET NO. OF SHEETS <br />DATE <br />00-00-2024-------- <br />00-00-0000 <br />00-00-0000 <br />00-00-0000 <br />00-00-0000 <br />CONSULTANT: <br />21 <br />0 <br /> <br />W <br />. <br /> <br />H <br />A <br />R <br />V <br />E <br />Y <br /> <br />A <br />V <br />E <br />. <br /> <br />U <br />N <br />I <br />T <br /> <br /># <br />2 <br />( <br />A <br />D <br />U <br />) <br />, <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />RESIDENTIAL PROJECT FOR: <br />210 W. HARVEY AVE.(ADU), <br />SANTA ANA, CA 92707 <br />DE <br />T <br />A <br />C <br />H <br />E <br />D <br /> <br />A <br />D <br />U <br /> <br />P <br />R <br />O <br />J <br />E <br />C <br />T <br />Exp. date: <br />STATE OF CALIFORNIACIVIL <br />REGISTERED PROFESS IONAL ENGINEER <br />HUE C . LUI <br />C-66754 <br />9/26 <br />1/29/2025 <br />HA NGUYEN - 1/29/2025 <br />GENERAL <br />NOTES <br />02 11 <br />GN <br />210 W Harvey Ave <br />Unit #24/22/2025