Laserfiche WebLink
JOB NAME _Kaiser SAN 1st Fl GenRad <br />JOB NO. DATE _S09-23018 03/04/2024 <br />ENGINEER DWG. REF _OS -- <br />Connection Design P1937 Fitting - main rail to sub rail attachment <br />Stub Design Loads: <br />≔Tu 702.2 lbf ≔Vx 344.5 lbf ≔Vy 130.2 lbf <br />≔t 0.25 in ≔w 1.86 in ≔Fy 33 ksi ≔Ωb 1.67 <br />≔Mn =⋅――⋅w t 2 <br />4 <br />――Fy <br />Ωb <br />0.574 ⋅kip in <br />≔lever_arm =――――――― <br />―――――――-5.375 in 1.656 in <br />2 <br />2 <br />0.93 in <br />≔Mu =⋅――Tu <br />2 <br />lever_arm 0.326 ⋅kip in <br />≔Rn_t =―――――⋅A Fy_uni <br />Omega_axial <br />20.368 kip <br />=if <br />else <br />>Rn_t Tu <br />‖ <br />‖‖“Design Acceptable” <br />‖ <br />‖‖“Failure” <br />“Design Acceptable” <br />≔DCRT =――Tu <br />Rn_t <br />0.034 <br />P2786 fitting <br />≔Tu 702.2 lbf Stubs force <br />≔Rn 1000 lbf <br />=if <br />else <br />>Rn ――Tu <br />1 <br />‖ <br />‖“Design Acceptable” <br />‖ <br />‖“Failure” <br />“Design Acceptable” <br />≔DCRT =――Tu <br />Rn <br />0.702 <br />1900 E 4th St - <br />1011190678/9/2024