Laserfiche WebLink
CONCRETE FLOORS: <br />UL-CLASSIFIED <br />TYPE OF PENETRANT SYSTEM F-RATING (HR)T-RATING (HR) <br />CIRCULAR BLANK <br />OPENING <br />2 <br />3 <br />1.5 <br />3 <br />C-AJ-0090 <br />C-AJ-0086 <br />SINGLE METAL PIPE <br />OR CONDUIT <br />2 0C-AJ-1126 <br />SINGLE OR <br />BUNDLED CABLES <br />2 0C-AJ-3095 <br />GYPSUM WALLBOARD ASSEMBLIES: <br />UL-CLASSIFIED <br />TYPE OF PENETRANT SYSTEM F-RATING (HR)L-RATING <br />METAL PIPES OR <br />CONDUIT <br />1 <br />2 <br />W-L-1054 <br />W-L-1054 <br />NON-METALLIC <br />PIPE OR CONDUIT <br />1 <br />2 <br />W-L-2128 <br />W-L-2128 <br />SINGLE OR <br />BUNDLED CABLES <br />1 <br />2 <br />W-L-3065 <br />W-L-3065 <br />CABLE TRAY 1 <br />2 <br />W-L-4011 <br />W-L-4011 <br />INSULATED PIPES 1 <br />2 <br />W-L-5028 <br />W-L-5028 <br />1 CFM / SF <br />1 CFM / SF <br />8 CFM / SF <br />8 CFM / SF <br />5 CFM / SF <br />5 CFM / SF <br />1 CFM / SF <br />1 CFM / SF <br />CONTRACTOR TO PROVIDE FIRESTOPPING SUBMITTAL TO ARCHITECT OF RECORD FOR REVIEW AND APPROVAL. <br />SUBMITTAL SHALL INCLUDE FIRESTOPPING DETAILS (WITH APPROVED UL REFERENCE) COORDINATED WITH A LOCATION <br />FLOOR PLAN. SUBMITTAL TO INCLUDE ENGINEERING JUDGEMENT IF REQUIRED. SIMILAR FOR FIRE-PROOFING <br />PROVISIONS IF NECESSARY. (IN OSHPD APPLICATIONS, THIS SUBMITTAL SHALL BE REVIEWED IN THE FIELD FOR <br />CONCURRENCE BY THE FLSO) <br />1. CERTIFIED SINGLE-AND DOUBLE-GANG METALLIC OUTLET AND SWITCH BOXES WITH METALLIC OR <br />NONMETALLIC COVER PLATES MAY BE USED IN NONBEARING STEEL STUD WALLS WITH RATINGS NOT <br />EXCEEDING 2 HR. THE METALLIC OUTLET OR SWITCH BOXES SHOULD BE SECURELY FASTENED TO THE STUDS <br />AND THE OPENING IN THE WALLBOARD FACING SHOULD BE CUT SO THAT THE CLEARANCE BETWEEN THE BOX <br />AND THE WALLBOARD DOES NOT EXCEED 1/8 IN. THE SURFACE AREA OF INDIVIDUAL METALLIC OUTLET OR <br />SWITCH BOXES SHOULD NOT EXCEED 16 SQIN. THE AGGREGATE SURFACE AREA OF THE BOXES SHOULD NOT <br />EXCEED 100 SQ IN. PER 100 SQ FT OF WALL SURFACE. THE AGGREGATE SURFACE AREA OF THE BOXES MAY BE <br />EXCEEDED WHEN WALL-OPENING PROTECTIVE MATERIALS (PER UL CLIV) ARE INSTALLED ACCORDING TO THE <br />REQUIREMENTS OF THEIR CERTIFICATION. <br />2. METALLIC BOXES LOCATED ON OPPOSITE SIDES OF WALLS OR PARTITIONS SHOULD BE SEPARATED BY A <br />MINIMUM HORIZONTAL DISTANCE OF 24 IN. THIS MINIMUM SEPARATION DISTANCE BETWEEN METALLIC BOXES <br />MAY BE REDUCED WHEN WALL-OPENING PROTECTIVE MATERIALS (PER UL CLIV) ARE INSTALLED ACCORDING TO <br />THE REQUIREMENTS OF THEIR CERTIFICATION. <br />FIRE-STOPPING SUBMITTAL <br />METAL BACK BOX PROTECTION <br />FLEXIBLE CONDUIT <br />OR PIPE <br />1 <br />2 <br />W-L-1243 <br />W-L-1243 <br />5 CFM / SF <br />5 CFM / SF <br />WHERE THE PENETRATING ITEM IN THE INDIVIDUAL DESIGN IS INDICATED AS A METALLIC PIPE, CONDUIT, TUBE, DUCT OR <br />CABLE, AND THE FIRESTOP SYSTEM CONSISTS AT MINIMUM OF A FILL MATERIAL (SUCH AS SEALANTS, PUTTY OR <br />MORTAR) , THE PENETRANT MAY PASS THROUGH THE OPENING IN THE WALL OR FLOOR ASSEMBLY AT ANY ANGLE, <br />PROVIDED THE ANNULAR SPACE IS MAINTAINED ON BOTH SIDES OF THE WALL OR FLOOR ASSEMBLY AND ALL OTHER <br />SPECIFICATIONS IN THE DESIGN ARE SATISFIED . IN ALL OTHER CASES, EXCEPT WHERE OTHERWISE INDICATED IN THE <br />SYSTEM, THE PENETRATING ITEM SHOULD PENETRATE THE WALL OR FLOOR ASSEMBLY AT A 90° ANGLE. <br />THROUGH-PENETRATION FIRESTOP SYSTEMS <br />PARTITION TYPE TAG <br />MODIFIER (ADDITIONAL DESIGNATIONS) <br />STUD SIZE <br />PARTITION TYPE <br />HOURLY FIRE RATING (A DASH (-) INDICATES A NON-RATED PARTITION.) <br />1. PARTITION TYPES SHOWN THIS SHEET REFER TO BASE WALL ONLY. REFER TO OTHER SCHEDULES <br />AND DETAILS FOR FINISHES. <br />2. REFER TO FLOOR PLANS FOR LOCATIONS AND IDENTIFICATION OF ALL FIRE RESISTANCE AND / OR <br />SMOKE RATED PARTITIONS. <br />3. IDENTIFY ALL FIRE RESISTANCE AND / OR SMOKE RATED PARTITIONS WITH LABELS 12 INCHES <br />ABOVE THE CEILING OR 10 FEET MAX. ABOVE THE FLOOR IF NO CEILING. USE 1 1/2" HIGH LETTERS, <br />CLEARLY LEGIBLE & READABLE AGAINST A CONTRASTING BACKGROUND. <br />4. UL DESIGN NUMBERS REFER TO THE UNDERWRITERS FIRE LABORATORY RESISTANCE DIRECTORY, <br />LATEST EDITION. <br />5. FIRE RESISTANCE RATED PARTITIONS TO HAVE FIRESTOPPING SEALANT AT THE HEAD, SILL, AND <br />JUNCTURES WITH DISSIMILAR MATERIALS, SUCH AS PIPES, DUCTS, CONDUITS, ETC. <br />6. NON-RATED PARTITIONS TO HAVE ACOUSTICAL SEALANT CONTINUOUS AT THE HEAD, SILL, AND <br />JUNCTURES WITH DISSIMILAR MATERIALS AND ALL AROUND PENETRATIONS AND OPENINGS. <br />7. REFER TO THE GYPSUM BOARD MATERIAL SCHEDULE THIS SHEET FOR A DESCRIPTION OF THE TYPE <br />OF GYPSUM BOARD PANELS AND WHERE THEY ARE USED. <br />8. STC RATINGS SHOWN ARE BASED ON LABORATORY TESTED ASSEMBLIES AND WILL NOT <br />NECESSARILY REFLECT THE ACTUAL PERFORMANCE OF THE COMPLETED PARTITIONS. <br />9. LIMITING HEIGHT INDICATES GIVE THE MAXIMUM UNSUPPORTED HEIGHT FOR THAT PARTITION TYPE <br />BASED ON A DEFLECTION CRITERIA RATION OF L/240. WHERE FLOOR TO STRUCTURE HEIGHT OF <br />PARTITION EXCEEDS THE INDICATED LIMITING HEIGHT, PROVIDE SUPPLEMENTAL BRACING TO THE <br />STRUCTURE OVERHEAD AS REQUIRED TO MAINTAIN DEFLECTION RATIO WITHIN L/240. <br />10. FOR PARTITION WITH "BRITTLE" FINISHES SUCH AS PLASTER AND CERAMIC TILE, DESIGN PARTITION <br />SYSTEM TO MAINTAIN DEFLECTION RATIO WITH L/360. <br />1. ADDITIONAL DESIGNATION 'X' TO PARTITION TYPE INDICATES ADDITIONAL LAYER 5/8" GYP. BD. EACH <br />FINISHED SIDE. <br />2. ADDITIONAL DESIGNATION 'S' TO PARTITION TYPE INDICATES ACCOUSTICAL INSULATION IN STUD SPACE <br />FULL HEIGHT. <br />3. ADDITIONAL DESIGNATION 'L' TO PARTITION TYPE INDICATES LEAD SHIELDING REQUIREMENT WITH <br />THICKNESS PER PHYSICIST REPORT. <br />PARTITION TYPE MODIFIER NOTES: <br />PARTITION NOTES: <br />GYPSUM WALL BOARD SCHEDULE <br />5/8" TYPE "X" GYPSUM BOARD ALL PARTITIONS UNO BELOW, OR OTHERWISE ON FLOOR PLANS <br />PROVIDE BEHIND ALL PLUMBING FIXTURES (WATER CLOSETS, <br />URINALS, LAVATORIES, EWC'S, ETC) TO A HEIGHT OF 4' AFF <br />AND 8' WIDE (CENTER ON FIXTURE) <br />PARTITIONS EXPOSED DIRECTLY TO RUNNING WATER & <br />SCHEDULED TO RECEIVE TILE. EXAMPLES: SHOWERS, <br />BATHTUB ENCLOSURE <br />USE AT ALL TOILET ROOMS, HOUSEKEEPING / JANITOR <br />CLOSETS. <br />5/8" MOLD, WATER, ABUSE & FIRE <br />RESISTANT GYPSUM BOARD <br />1/2" CEMENTITIOUS OR <br />5/8" TILE BACKER BOARD <br />5/8" TYPE "X" <br />MOISTURE RESISTANT <br />5/8" ABUSE & FIRE RESISTANT <br />GYPSUM BOARD <br />AS INDICATED ON PLANS <br />5/8" THICK LEAD BACKED GYP. BD <br />(RAY-BAR TYPE "RB-LBG" <br />INSTALLED VERTICALLY, OR <br />EQUAL) <br />AS INDICATED ON PLANS. SEE LEAD SHIELDING SHEET Q8-11 <br />1 <br />A4L <br />(NON-STRUCTURAL INTERIOR PARTITION) <br />PARTIAL HEIGHT GYP. BD. EACH SIDE WITH OPTIONS FOR FULL HEIGHT STUD <br />(BRACING CAN BE USED AS AN ALTERNATE WHERE FIELD CONDITIONS DO NOT <br />ALLOW FULL HEIGHT STUDS) <br />TYPE B <br />PARTITION <br />TYPE <br />LIMITING HT <br />16" OC <br />B1 <br />B2 <br />B3 <br />B4 <br />B6 <br />3/ <br />4 <br />" <br />CONT ACOUS SEALANT <br />TYP. BOTH SIDES <br />OVERHEAD STRUCTURE <br />RUNNER <br />TOP OF METAL STUD <br />4" <br />. <br />. <br />. <br />5 1/4" <br />. <br />B6 <br />B4 <br />B3 <br />B2 <br />B1 <br />2 1/2" 18 GA METAL STUD (250S162-43) @ 16" O.C. <br />3 5/8" 16 GA METAL STUD (362S162-54) @ 16" O.C. <br />4" 16 GA METAL STUD (400S162-54) @ 16" O.C. <br />1 5/8" 20 GA METAL STUD (162S162-33) @ 16" O.C. <br />9'-6" <br />12'-6" <br />16'-0" <br />17'-3" <br />20'-0" <br />02 <br />A5-02 <br />07 <br />A5-02 <br />08 <br />A5-02 <br />03 <br />A5-02 <br />ALT. <br />ALT. <br />4 7/8" <br />3 3/4" <br />7 1/4" <br />2 7/8" <br />5/8" THICK LEAD BACKED GYP. BD. <br />(WHERE OCCURS - SEE WALL TYPE MODIFIERS) <br />ACOUSTICAL BATT INSULATION <br />(WHERE OCCURS - SEE WALL TYPE MODIFIERS) <br />6" 16 GA METAL STUD (600S162-54) @ 16" O.C. <br />(NON-STRUCTURAL INTERIOR FURRING) <br />PARTIAL HEIGHT GYP. BD. WITH OPTIONS FOR FULL HEIGHT STUD (BRACING CAN <br />BE USED AS AN ALTERNATE WHERE FIELD CONDITIONS DO NOT ALLOW FULL <br />HEIGHT STUDS) <br />TYPE C <br />PARTITION <br />TYPE <br />LIMITING HT <br />16" OC <br />C1 <br />C2 <br />C3 <br />C4 <br />C6 <br />3/ <br />4 <br />" <br />CONT ACOUS SEALANT <br />TYP. BOTH SIDES <br />OVERHEAD STRUCTURE <br />RUNNER <br />TOP OF METAL STUD <br />4" <br />. <br />. <br />. <br />. <br />. <br />C6 <br />C4 <br />C3 <br />C2 <br />C1 <br />2 1/2" 16 GA METAL STUD (250S162-54) @ 16" O.C. <br />3 5/8" 16 GA METAL STUD (362S162-54) @ 16" O.C. <br />4" 16 GA METAL STUD (400S162-54) @ 16" O.C. <br />6" 16 GA METAL STUD (600S162-54) @ 16" O.C. <br />1 5/8" 16 GA METAL STUD (162S162-54) @ 16" O.C. <br />9'-6" <br />12'-6" <br />16'-0" <br />17'-3" <br />20'-0" <br />3 1/8" <br />2 1/4" <br />4 5/8" <br />02 <br />A5-02 <br />07 <br />A5-02 <br />08 <br />A5-02 <br />02 <br />A5-03 <br />ALT. <br />ALT. <br />5/8" THICK LEAD BACKED GYP. BD. (WHERE <br />OCCURS, SEE LEAD SHIELDING SHEET Q8-11) <br />ACOUSTICAL BATT INSULATION <br />(WHERE INDICATED) <br />6 5/8" <br />4 1/4" <br />R <br />No. <br />F <br />LICENSE <br />STATE <br />D <br />O <br />A RCHITECT <br />C AL IFORNIA <br />STEPHE WHITE <br />RENEWAL <br />DATE <br />C-34829 <br />N <br />08/31/25 <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO: BLDG NO:FLOOR LEV:SECTION: <br />KP PROJ. NO. <br />MATTERPORT LINK: https://my.matterport.com/show/?m=FW21iEbmuii <br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION HOSPITALS <br />NATIONAL FACILITIES SERVICES <br />1800 HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO. ISSUED DATE <br />0 <br />5' <br />50 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br />1/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />Phone 310.820.4600 | Fax 310.207.4215 <br />www.huitt-zollars.com <br />C:\Users\jpark\Documents\R314412.44 - KP SAN 1st Flr Gen Rad_A22_Central_jhaLWMQW.rvt <br />5/20/2024 10:22:45 AM <br />SOCC 2023 R RAD SAN 1ST FLOOR <br />GEN RAD REPLACEMENT (5284) <br />A5-01 <br />DETAILS - PARTITION TYPES <br />CA361 1 - - <br />CAP028060R314412.44 <br />SANTA ANA MEDICAL OFFICES <br />1900 E. 4TH ST. <br />SANTA ANA, CA 92701 <br />N/ATHROUGH PENETRATION FIRESTOPS 03 <br />N/APARTITION TYPE NOTES 013" = 1'-0"PARTITION TYPE B 06 <br />3" = 1'-0"PARTITION TYPE C 08 <br />CITY SUBMITTAL 04/19/2024 <br />BID SET 05/20/2024 <br />1900 E 4th St - <br />1011190678/9/2024