A. CLASSES OF CONCRETE <br />USAGE: ALL NEW CONCRETE <br />1. PROVIDE f'c=4000 PSI 28 DAY MINIMUM COMPRESSIVE STRENGTH, NORMALWEIGHT <br />CONCRETE, MAXIMUM WATER TO CEMENT RATIO OF 0.45, AND MAX AGGREGATE SIZE <br />OF 3/4". <br />2. NORMAL WEIGHT AGGREGATE SHALL BE NONREACATIVE AS DETERMINED BY ONE OF <br />THE METHODS OF ASTM C33 APPENDIX XI: METHODS FOR EVALUATING POTENTIAL <br />FOR DELETERIOUS EXPANSION DUE TO ALKAI REACTIVITY OF AN AGGREGATE. <br />AGGREGATES DEEMED TO BE DELETERIOUS OR POTENTIALLY DELETERIOUS <br />MAY BE USED WITH THE ADDITION OF A MATERIAL THAT HAS BEEN SHOWN TO <br />PREVENT HARMFUL EXPANSION IN ACCORDANCE WITH APPENDIX XI OF ASTM C33, <br />WHEN APPROVED BY THE BUILDING OFFICIAL. <br />3. THE MAXIMUM PERCENTAGE OF POZZOLANS, INCLUDING FLY ASH AND SILICA FUME, <br />AND SLAG CEMENT IN CONCRETE ASSIGNED TO ALL EXPOSURE CATEGORIES SHALL <br />PER THE FOLLOWING: <br />a) THE MAXIMUM PERCENTAGE LIMITS SHALL INCLUDE THE FLY ASH OR <br />OTHER POZZOLANS, SLAB CEMENT, AND SILICA FUME USED IN THE <br />MANUFACTURE OF ASTM C595 AND C1157 BLENDED CEMENTS. <br />b) THE INDIVIDUAL LIMITS SHALL APPLY REGARDLESS OF THE NUMBER OF <br />CEMENTITIOUS MATERIALS IN A CONCRETE MIX. <br />LIMITS ON CEMENTITIOUS MATERIALS FOR CONCRETE <br />4. THE CONCRETE MIX DESIGNS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL BY <br />THE REGISTERED DESIGN PROFESSIONAL PRIOR TO FABRICATION AND INSTALLATION. <br />B. HORIZONTAL CONSTRUCTION JOINTS IN CONCRETE POURS <br />1. THERE SHALL BE NO HORIZONTAL CONSTRUCTION JOINTS IN ANY <br />CONCRETE POURS UNLESS SHOWN ON THE DRAWINGS. THE ARCHITECT/ENGINEER <br />SHALL APPROVE ALL DEVIATIONS OR ADDITIONAL JOINTS IN WRITING. <br />C. REINFORCING STEEL <br />1. ALL REINFORCING STEEL SHALL BE ASTM A 615 GRADE 60 UNLESS NOTED <br />OTHERWISE ON THE DRAWINGS OR IN THESE NOTES. <br />2. REINFORCING STEEL: PROVIDE REINFORCING STEEL CONFORMING TO ASTM <br />A 706 FOR ALL REINFORCING STEEL REQUIRED TO BE WELDED AND WHERE <br />NOTED ON THE DRAWINGS. <br />3. HEADED STUD ANCHORS FOR EMBEDDED PLATES: AWS D1.1 TYPE A STUDS <br />MANUFACTURED IN CONFORMANCE WITH SPECIFICATION ASTM A 108 WITH A <br />MINIMUM TENSILE STRENGTH OF 61,000 PSI. <br />D. REINFORCING STEEL COVERAGE <br />1. REINFORCING STEEL COVERAGE SHOULD CONFORM TO THE <br />COVER SPECIFIED ON DETAILS. COVER SPECIFIED SHALL BE CONSIDERED MINIMUMS <br />THAT MAY REQUIRE INCREASING WHERE REINFORCING STEEL INTERSECTS FOR <br />DIFFERENT MEMBER TYPES. COVER IN STRUCTURAL MEMBERS NOT SPECIFIED IN THE <br />DETAILS SHALL CONFORM TO THE REQUIREMENTS OF ACI 318 UNLESS SPECIFIED <br />OTHERWISE ON THE DRAWINGS. <br />E. SPLICES AND HOOKS IN REINFORCING STEEL <br />1. SPLICE LOCATION AND TYPE AND HOOKS FOR UNSCHEDULED BEAMS, <br />SLABS AND WALLS: <br />a. BEAMS AND SLABS. UNSCHEDULED BEAMS AND SLABS, INCLUDING <br />GRADE BEAMS, SHALL HAVE CONTINUOUS TOP BARS LAPPED AT MIDSPAN <br />BETWEEN SUPPORTS WITH A CLASS B TENSION SPLICE. BOTTOM BARS SHALL <br />BE LAPPED AT THE SUPPORTS WITH A CLASS B TENSION SPLICE. ALL BEAM <br />BARS SHALL BE HOOKED AT DISCONTINUOUS END, UNLESS NOTED <br />OTHERWISE. <br />FLY ASH OR OTHER POZZOLANS <br />CONFORMING TO ASTM C618 <br />SLAG CEMENT CONFORMING TO ASTM <br />C989 <br />SIICA FUME CONFORMING TO ASTM C1240 <br />TOTAL OF FLY ASH OR OTHER POZZOLANS <br />AND SILICA FUME <br />TOTAL OF FLY ASH OR OTHER POZZOLANS, <br />SLAG CEMENT, AND SILICA FUME <br />CEMENTITIOUS MATERIALS MAXIMUM PERCENT OF TOTAL <br />CEMENTITIOUS MATERIALS BY MASS <br />25 <br />50 <br />10 <br />35 <br />50 <br />R <br />SHEET TITLE <br />PROJECT <br />FACILITY <br />FAC NO:BLDG NO:FLOOR LEV:SECTION: <br />KP PROJ. NO. <br />MATTERPORT LINK: <br />555 W. Fifth Street Suite 2950 | Los Angeles, CA 90013 USA <br />ARCHITECT <br />CONSULTANT <br />ARCHITECT SEAL CONSULTANT SEAL <br />KAISER FOUNDATION HOSPITALS <br />NATIONAL FACILITIES SERVICES <br />1800 HARRISON STREET OAKLAND, <br />CALIFORNIA 94612 <br />ISSUE / REVISION LOG <br />NO.ISSUED DATE <br />0 <br />5' <br />50 <br />' <br />GR <br />A <br />P <br />H <br />I <br />C <br /> <br />S <br />C <br />A <br />L <br />E <br />S <br />: <br />1/ <br />1 <br />6 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />25 <br />' <br />1/ <br />8 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />5' <br />0 <br />12 <br />' <br />1/ <br />4 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />6' <br />1/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />1' <br />0 <br />2' <br />1- <br />1 <br />/ <br />2 <br />" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />0 <br />1' <br />3" <br /> <br />= <br /> <br />1 <br />' <br />- <br />0 <br />" <br />IF <br /> <br />T <br />H <br />I <br />S <br /> <br />S <br />H <br />E <br />E <br />T <br /> <br />I <br />S <br /> <br />N <br />O <br />T <br /> <br />30 <br />" <br />x <br />4 <br />2 <br />" <br />, <br /> <br />I <br />T <br /> <br />I <br />S <br /> <br />A <br /> <br />R <br />E <br />D <br />U <br />C <br />E <br />D <br /> <br />PR <br />I <br />N <br />T <br /> <br />- <br /> <br />S <br />C <br />A <br />L <br />E <br /> <br />AC <br />C <br />O <br />R <br />D <br />I <br />N <br />G <br />L <br />Y <br />AGENCY APPLICATION NUMBER <br />AGENCY APPROVAL STAMP <br />THIS DOCUMENT IS THE PROPERTY OF THE OWNER AND IS <br />NOT TO BE USED WITHOUT OWNER'S WRITTEN PERMISSION. <br />HZ PROJ. NO. <br />Phone 310.820.4600 | Fax 310.207.4215 <br />www.huitt-zollars.com <br />S09.23018.00 <br />Autodesk Docs://S09-23018-00 Kaiser SAN 1st Fl GenRad/S09-23018-00 Kaiser SAN 1st Fl GenRad.rvt <br />5/16/2024 11:56:34 AM <br />S0-01 <br />GENERAL NOTES <br />CA361 1 <br />CAP028060R314412.44 <br />A. GENERAL BUILDING CODE <br />1. THE CONSTRUCTION DOCUMENTS ARE BASED ON THE <br />REQUIREMENTS OF THE CALIFORNIA BUILDING CODE 2022. <br />2. BUILDING OCCUPANCY CATEGORY: II (PER CBC TABLE 1604.5) <br />B. SEISMIC DESIGN CRITERIA <br />1. THE STRUCTURE AND COMPONENTS OF THE BUILDING HAVE BEEN <br />DESIGNED IN ACCORDANCE WITH AFOREMENTIONED BUILDING CODE WITH <br />THE FOLLOWING CRITERIA: <br />a. 0.2 SEC. SPECTRAL ACCELERATION (SS): 1.287G <br />b. 1 SEC. SPECTRAL ACCELERATION (S1): 0.459G <br />c. SITE CLASS: D <br />d. SITE COEFFICIENT, SHORT PERIOD (FA): 1.20 <br />e. SITE COEFFICIENT, 1 SEC. PERIOD (FV): 1.841 <br />f. 0.2 SEC SPECTRAL RESPONSE COEFF. (SDS): 1.029G <br />g. 1 SEC SPECTRAL RESPONSE COEFF. (SD1): 0.57G <br />h. RISK CATEGORY: IV <br />i. OCCUPANCY IMPORTANCE FACTOR, I: 1.0 <br />j. SEISMIC DESIGN CATEGORY: D <br />A. MATERIAL <br />1. HOT ROLLED STRUCTURAL MEMBERS: ALL HOT ROLLED STEEL <br />PLATES, SHAPES, SHEET PILING, AND BARS SHALL BE NEW STEEL <br />CONFORMING TO ASTM SPECIFICATION A6. <br />2. ASTM SPECIFICATION AND GRADE: CLEARLY MARK THE GRADE OF <br />STEEL ON EACH PIECE, WITH A DISTINGUISHING MARK VISIBLE FROM FLOOR <br />SURFACES, FOR THE PURPOSE OF FIELD INSPECTION OF PROPER GRADE OF <br />STEEL. UNLESS NOTED OTHERWISE ON THE DRAWINGS, STRUCTURAL STEEL <br />SHALL BE AS FOLLOWS: <br />a. W- AND WT-SHAPES: ASTM A 992. <br />b. C-SHAPES: ASTM A 36 <br />c. L-SHAPES: ASTM A 36 UNO. <br />d. ROUND HSS: ASTM A 500, GRADE C (FY=46 KSI). <br />e. RECTANGULAR HSS: ASTM A 500, GRADE C (FY=50 KSI). <br />f. STEEL PIPES: ASTM A 53 (TYPES E OR S), GRADE B. <br />g. BASE PLATES: ALL BASE PLATES SHALL CONFORM TO ASTM A <br />36 UNLESS NOTED OTHERWISE ON THE DRAWINGS. <br />h. CONNECTION MATERIAL: <br />1) ALL CONNECTION MATERIAL, EXCEPT AS NOTED <br />OTHERWISE HEREIN OR ON THE DRAWINGS, INCLUDING <br />BEARING PLATES, GUSSET PLATES, STIFFENER PLATES, FILLER <br />PLATES, ANGLES, ETC. SHALL CONFORM TO ASTM A 36 UNLESS <br />A HIGHER GRADE OF STEEL IS NOTED ON OTHERWISE. <br />i. OTHER STEEL: ANY OTHER STEEL NOT INDICATED OTHERW ISE <br />SHALL CONFORM TO ASTM A 992 OR ASTM A 572, GRADE 50, EXCEPT <br />PLATES AND ANGLES THAT SHALL BE ASTM A 36. <br />B. STRUCTURAL BOLTS AND THREADED FASTENERS <br />1. A 325 BOLTS: ALL BOLTS IN STRUCTURAL CONNECTIONS SHALL <br />CONFORM TO ASTM A 325 TYPE 1, UNLESS INDICATED OTHERWISE ON THE <br />DRAWINGS. <br />2. THREADED ROUND STOCK: THREADED RODS SHALL CONFORM TO: <br />a. ASTM A 36 UNO. <br />3. ALL OFF-SITE FABRICATION OF STRUCTURAL STEEL COMPONENTS INCLUDING <br />STEEL STAIRS AND PRE-CAST CONCRETE SHALL BE DONE IN AN APPROVED <br />FABRICATOR SHOP AS REQUIRED BY CITY OF SANTA ANA. <br />THE RECEIPT OF ANY SHIPMENT OF OFF-SITE FABRICATED ITEMS <br />4. NOMINAL HOLE DIMENSIONS SHALL BE STANDARD SIZE PER AISC TABLE J3.3, <br />UNLESS NOTED OTHERWISE. <br />A. SUBMITTALS TO BE PROVIDED TO STRUCTURAL ENGINEER <br />MEP EQUIPMENT DEFERRED SUBMITTALS <br />STRUCTURAL STEEL <br />PREQUALIFIED WELD PROCEDURES & WELDER CERTIFICATIONS <br />CONCRETE RINFORCING STEEL <br />CONCRETE MIX DESIGNS <br />POST INSTALLED ANCHOR MANUFACTURER INFORMATION <br />REINFORCEMENT SCAN AND LOCATIONS <br />CONCRETE SAWCUT LAYOUT <br />UNISTRUCT SYSTEMS AND PRODUCT DATA <br />1. SUBMITTAL REQUIREMENTS: <br />a. ALL SHOP DRAWINGS MUST BE REVIEWED AND <br />ELECTRONICALLY STAMPED BY THE GENERAL CONTRACTOR PRIOR TO <br />SUBMITTAL. <br />b. CONTRACTOR SHALL PROVIDE THE SUBMITTAL IN ELECTRONIC <br />PORTABLE DOCUMENT FORMAT (PDF). <br />c. THE OMISSION FROM THE SHOP DRAWINGS OF ANY MATERIALS <br />REQUIRED BY THE CONTRACT DOCUMENTS TO BE FURNISHED SHALL <br />NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF <br />FURNISHING AND INSTALLING SUCH MATERIALS, REGARDLESS OF <br />WHETHER THE SHOP DRAWINGS HAVE BEEN REVIEWED AND <br />APPROVED. <br />B. REPRODUCTION <br />1. THE USE OF ELECTRONIC FILES OR REPRODUCTIONS OF THESE <br />CONTRACT DOCUMENTS BY ANY CONTRACTOR, SUBCONTRACTOR, ERECTOR, <br />FABRICATOR, OR MATERIAL SUPPLIER IN LIEU OF PREPARATION OF SHOP <br />DRAWINGS SIGNIFIES THEIR ACCEPTANCE OF ALL INFORMATION SHOWN <br />HEREON AS CORRECT, AND OBLIGATES THEMSELVES TO ANY JOB EXPENSE, <br />REAL OR IMPLIED, ARISING DUE TO ANY ERRORS THAT MAY OCCUR HEREON. <br />A. CONTRACT DOCUMENTS <br />1. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO OBTAIN <br />ALL CONTRACT DOCUMENTS AND LATEST ADDENDA AND TO SUBMIT SUCH <br />DOCUMENTS TO ALL SUBCONTRACTORS AND MATERIAL SUPPLIERS PRIOR TO <br />THE SUBMITTAL OF SHOP DRAWINGS, FABRICATION OF ANY STRUCTURAL <br />MEMBERS, AND ERECTION IN THE FIELD. <br />2. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS <br />REPRESENT THE FINISHED STRUCTURE, AND, EXCEPT WHERE SPECIFICALLY <br />SHOWN, DO NOT INDICATE THE METHOD OR MEANS OF CONSTRUCTION. THE <br />CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE <br />SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, <br />PROCEDURES, TECHNIQUES, AND SEQUENCE. <br />B. DRAWING CONFLICTS <br />1. THE GENERAL CONTRACTOR SHALL COMPARE THE ARCHITECTURAL <br />AND STRUCTURAL DRAWINGS AND REPORT ANY DISCREPANCY BETWEEN <br />EACH SET OF DRAWINGS AND WITHIN EACH SET OF DRAWINGS TO THE <br />ARCHITECT AND ENGINEER PRIOR TO THE FABRICATION AND INSTALLATION OF <br />ANY STRUCTURAL MEMBERS. <br />C. CONFLICTS IN STRUCTURAL REQUIREMENTS <br />1. WHERE CONFLICT EXISTS AMONG THE VARIOUS PARTS OF THE <br />STRUCTURAL CONTRACT DOCUMENTS, STRUCTURAL DRAWINGS, GENERAL <br />NOTES, AND SPECIFICATIONS, THE STRICTEST REQUIREMENTS, AS INDICATED <br />BY THE ENGINEER, SHALL GOVERN. <br />D. EXISTING CONDITIONS <br />1. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND <br />CONDITIONS OF THE EXISTING BUILDING AT THE JOB SITE AND REPORT ANY <br />DISCREPANCIES FROM ASSUMED CONDITIONS SHOWN ON THE DRAWINGS TO <br />THE ARCHITECT AND ENGINEER PRIOR TO THE FABRICATION AND ERECTION <br />OF ANY MEMBERS. <br />2. WORK SHOWN ON THE DRAWINGS IS NEW, UNLESS NOTED AS <br />EXISTING. <br />3. EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS WAS OBTAINED <br />FROM EXISTING CONSTRUCTION DOCUMENTS AND LIMITED SITE <br />OBSERVATION. THESE DRAWINGS OF EXISTING CONSTRUCTION ARE <br />AVAILABLE FOR CONTRACTOR USE. HOWEVER, THE AVAILABLE DRAWINGS OF <br />EXISTING CONSTRUCTION ARE NOT NECESSARILY COMPLETE. THE <br />CONTRACTOR SHALL FIELD VERIFY ALL PERTINENT INFORMATION. <br />4. DEMOLITION, CUTTING, DRILLING, ETC. OF EXISTING WORK SHALL BE <br />PERFORMED WITH GREAT CARE SO AS NOT TO JEOPARDIZE THE STRUCTURAL <br />INTEGRITY OF THE EXISTING BUILDING. IF ANY ARCHITECTURAL, STRUCTURAL, <br />OR MEP MEMBERS NOT DESIGNATED FOR REMOVAL INTERFERE WITH THE <br />NEW WORK, THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY AND APPROVAL <br />OBTAINED PRIOR TO REMOVAL OF THOSE MEMBERS. <br />5. THE CONTRACTOR SHALL SAFELY SHORE EXISTING CONSTRUCTION <br />WHEREVER EXISTING SUPPORTS ARE REMOVED TO ALLOW THE INSTALLATION <br />OF NEW WORK. ALL SHORING METHODS AND SEQUENCING OF DEMOLITION <br />SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND HIS ENGINEER. <br />6. THE CONTRACTOR SHALL VERIFY THE LOCATION OF EXISTING <br />UTILITIES PRIOR TO THE START OF CONSTRUCTION AND TAKE CARE TO <br />PROTECT EXISTING UTILITIES THAT ARE TO REMAIN IN SERVICE. <br />7. THE CONTRACTOR SHALL REPAIR ALL DAMAGE CAUSED DURING <br />CONSTRUCTION WITH SIMILAR MATERIALS AND WORKMANSHIP TO RESTORE <br />CONDITIONS TO LEVELS ACCEPTABLE TO THE ARCHITECT. <br />PART I - DESIGN CRITERIA 01 <br />PART IV -STRUCTURAL STEEL 09 <br />PART III - CONCRETE ANCHORAGE 06 <br />PART VI - SUBMITTALS 12 <br />PART VII - MISCELLANEOUS 14 <br />A. NEW EXPANSION BOLTS SHALL BE HILTI KB-TZ2 (ICC ESR 4266) UNO. <br />B. TESTING REQUIREMENTS SHALL BE IN ACCORDANCE WITH CBC 1901.3 <br />1. POST-INSTALLED ANCHOR TEST PROCEDURES SHALL BE BASED ON THE APPROVED <br />ICC EVALUATION REPORT AND CRITERIA IN THIS SECTION. POST INSTALLED ANCHORS <br />SHALL BE TENSION TESTED EXCEPT FOR TORQUE-CONTROLLED (EXPANSION) <br />ANCHORS. REFER TO THE POST INSTALLED ANCHOR TABLES IN THIS SECTION FOR <br />ANCHOR TYPE, TEST FREQUENCY, AND TEST LOADS. ANCHOR TESTS SHALL BE <br />PERFORMED ONLY AFTER EPOXY AND ANCHORAGE BASE MATERIAL HAVE ACHIEVED <br />FULL STRENGTH AND CURING TIME. <br />2. TEST ACCEPTANCE CRITERIA SHALL BE BASED ON THE APPROVED ICC EVALUATION <br />REPORT AND THE FOLLOWING MINIMUM REQUIREMENTS. <br />a. HYDRAULIC RAM METHOD: ANCHORS TESTED WITH A HYDRAULIC JACK OR <br />SPRING LOADED APPARATUS SHALL MAINTAIN THE TEST LOAD FOR A MINIMUM <br />OF 15 SECONDS AND SHALL EXHIBIT NO DISCERNIBLE MOVEMENT DURING THE <br />TENSION TEST. FOR ADHESIVE ANCHORS, WHERE OTHER THAN BOND IS <br />BEING TESTED, THE TESTING APPARATUS SUPPORT SHALL NOT BE LOCATED <br />WITHIN 1.5 TIMES THE ANCHORS EMBEDMENT DEPTH TO AVOID RESTRICTING <br />THE CONCRETE SHEAR CONE TYPE FAILURE MECHANISM. <br />b. TORQUE WRENCH METHOD: TORQUE-CONTROLLED POST-INSTALLED <br />ANCHORS TESTED WITH A CALIBRATED TORQUE WRENCH SHALL ATTAIN THE <br />SPECIFIED TORQUE WITHIN 1/2 TURN OF THE NUT, OR ONE QUARTER TURN OF <br />NUT FOR A 3/8" SLEEVE ANCHOR ONLY. <br />3. TESTING SHALL BE DONE IN THE PRESENCE OF THE SPECIAL INSPECTOR AND A <br />REPORT OF THE TEST RESULTS SHALL BE SUBMITTED TO THE EOR. IF <br />ANY ANCHOR FAILS TESTING THEN ALL ANCHORS OF THE SAME TYPE SHALL BE <br />TESTED UNTIL 20 CONSECUTIVE ANCHORS PASS OR ALL ANCHORS HAVE BEEN <br />TESTED, WHICHEVER IS LESS. TEST FREQUENCY AS NOTED IN THE <br />ANCHOR TABLES BELOW CAN THEN BE RESUMED ON THE REMAINING ANCHORS. <br />4. TESTING IS NOT REQUIRED FOR POWER ACTUATED FASTENERS USED TO ATTACH <br />TRACKS OF INTERIOR NON-SHEAR WALL PARTITIONS FOR SHEAR ONLY AND WHERE A <br />MINIMUM OF 3 FASTENERS ARE USED PER TRACK SEGMENT. <br />5. TEST 50% OF ANCHORS <br />C. WHEN INSTALLING DRILLED-IN ANCHORS AND/OR POWDER DRIVEN PINS IN EXISTING NON- <br />PRESTRESSED REINFORCED CONCRETE, USE CARE AND CAUTION TO AVOID CUTTING OR <br />DAMAGING THE EXISTING REINFORCING BARS. WHEN INSTALLING THEM INTO EXISTING <br />PRESTRESSED CONCRETE (PRE- OR POST TENSIONED) LOCATE THE PRESTRESSED TENDONS <br />BY USING A NON-DESTRUCTIVE METHOD PRIOR TO INSTALLATION. EXERCISE EXTREME CARE <br />AND CAUTION TO AVOID CUTTING OR DAMAGING THE TENDONS DURING INSTALLATION. <br />MAINTAIN A MINIMUM CLEARANCE OF ONE INCH BETWEEN THE REINFORCEMENT AND THE <br />DRILLED IN ANCHOR AND/OR PIN. <br />5/8 2 3/4 5 10 4 1/2 40 <br />1/2 2 4 5 1/2 2 3/4 50 <br />3/8 2 4 4 3/8 2 1/2 30 <br /> DIA (IN) <br />EFFECTIVE <br />EMBED <br />(IN) <br />MIN. <br />CONCRETE <br />THICKNESS <br />(IN) <br />CRITICAL EDGE <br />DISTANCE (IN) <br />MIN. EDGE <br />DISTANCE (IN)TEST REQUIRED TORQUE (FT-LB) <br />HILTI KB-TZ2 CARBON EXPANSION ANCHOR - CONCRETE <br />PART VIII -SPECIAL INSPECTIONS 16 <br />A. THE OWNER'S TESTING LABORATORY SHALL PROVIDE SPECIAL INSPECTIONS <br />SERVICES IN ACCORDANCE WITH CALIFORNIA BUILDING CODE. <br />B. STATEMENT OF SPECIAL INSPECTIONS <br />1. THE TESTING LABORATORY SHALL SAMPLE AND TEST MATERIALS AS THEY ARE BEING <br />INSTALLED FOR COMPLIANCE WITH SPECIFIED ACCEPTANCE CRITERIA. THE TESTING <br />LABORATORY WILL REPORT AND INTERPRET THE TEST RESULTS. THE LABORATORY <br />SHALL MONITOR AND REPORT ON THE INSTALLATION OF CONSTRUCTION WORK AND <br />SHALL PERFORM TESTS ON THE COMPLETED CONSTRUCTION AS REQUIRED TO <br />INDICATE CONTRACTOR’S COMPLIANCE WITH THE VARIOUS MATERIAL <br />SPECIFICATIONS GOVERNING THIS WORK. <br />2. TESTS AND INSPECTIONS SHALL BE CONDUCTED IN ACCORDANCE WITH SPECIFIED <br />REQUIREMENTS, AND IF NOT SPECIFIED, IN ACCORDANCE W ITH THE APPLICABLE <br />STANDARDS OF THE AMERICAN SOCIETY FOR TESTING AND MATERIALS OR OTHER <br />RECOGNIZED AND ACCEPTED AUTHORITIES IN THE FIELD. <br />3. SPECIAL INSPECTOR RESPONSIBILITIES: <br />a. THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED TO ASCERTAIN <br />THAT, TO THE BEST OF HIS/HER KNOWLEDGE, IT IS IN CONFORMANCE WITH THE <br />APPROVED DESIGN DRAWINGS. <br />b. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE <br />BUILDING OFFICIAL, THE ARCHITECT/ENGINEER, AND THE OWNER. ALL <br />DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE <br />ARCHITECT/ENGINEER, CONTRACTOR, AND OWNER. A REPORT THAT THE <br />CORRECTED WORK HAS BEEN INSPECTED SHALL BE SENT TO THE BUILDING <br />OFFICIAL, THE ARCHITECT/ENGINEER, AND THE OWNER. <br />C. QUALIFICATIONS: <br />1. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE <br />COMPETENCE, TO THE SATISFACTION OF THE BUILDING OFFICIAL, FOR INSPECTION <br />OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION BEING INSPECTED. <br />THE SPECIAL INSPECTOR SHALL MEET THE LEGAL QUALIFICATIONS OF THE BUILDING <br />CODE HAVING JURISDICTION AND BE ON THE APPROVED LIST OF THE CITY OF SANTA ANA. <br />2. THE TESTING LABORATORY SHALL MEET THE BASIC REQUIREMENTS OF ASTM E 329 <br />AND SHALL SUBMIT TO THE OWNER, ARCHITECT, AND ENGINEER EVIDENCE OF <br />CURRENT ACCREDITATION FROM THE AMERICAN ASSOCIATION FOR LABORATORY <br />ACCREDITATION, THE AASHTO ACCREDITATION PROGRAM OR THE “NIST” NATIONAL <br />VOLUNTARY LABORATORY ACCREDITATION PROGRAM. <br />3. THE SPECIAL INSPECTOR SHALL BE CERTIFIED WITH VALID AND CURRENT <br />CERTIFICATIONS AND ON THE APPROVED LIST OF THE CITY OF SANTA ANA. <br />4. QUALIFICATIONS OF WELDING INSPECTORS: INSPECTORS PERFORMING VISUAL WELD <br />INSPECTION SHALL MEET THE REQUIREMENTS OF AWS D1.1 SECTION 6.1.4. <br />INSPECTORS SHALL HAVE CURRENT CERTIFICATION AS AN AWS CERTIFIED WELDING <br />INSPECTOR (CWI). ASSISTANT INSPECTORS, IF ANY, SHALL BE SUPERVISED BY AN <br />INSPECTOR AND SHALL BE QUALIFIED BY TRAINING AND EXPERIENCE TO PERFORM <br />THE SPECIFIC FUNCTIONS TO WHICH THEY ARE ASSIGNED. <br />5. QUALIFICATIONS OF STEEL INSPECTORS: PERFORMED BY QUALIFIED TECHNICIANS <br />WITH A MINIMUM OF TWO YEARS OF EXPERIENCE IN STRUCTURAL STEEL TESTING AND <br />INSPECTION. <br />D. TESTING REQUIREMENTS <br />1. CONCRETE <br />a. VERIFY ALL OPENINGS, SAWCUTS, AND CORING ARE THE CORRECT SIZE AND <br />LOCATION. VERIFY THAT THE OPENINGS ARE SHOWN ON THE STRUCTURAL <br />DRAWINGS AND NOTIFY THE ENGINEER IMMEDIATELY OF ANY OPENINGS IN THE <br />FIELD THAT ARE NOT SHOWN ON THE DRAWINGS. <br />2. ALL POST INSTALLED ANCHORS: VERIFY THAT THE ANCHOR IS INSTALLED IN <br />ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTION AS <br />WELL AS THE FOLLOWING DESIGN REQUIREMENTS: <br />a. TESTING REQUIREMENTS IN ACCORDANCE WITH CBC 1910.5. <br />b. ANCHOR MANUFACTURER AND PRODUCT, INCLUDING MATERIAL, IS IN <br />ACCORDANCE WITH DESIGN DRAWINGS OR APPROVED SUBSTITUTION. <br />c. ANCHOR DIAMETER, LENGTH AND INSTALLED EMBEDMENT DEPTH. <br />d. DRILL BIT TYPE AND DIAMETER. <br />e. ANCHOR EDGE DISTANCE AND SPACING. <br />f. HOLE DIAMETER AND DEPTH. <br />g. HOLE CLEANING PROCEDURE AND CLEANLINESS. <br />3. STEEL <br />a. THE TESTING LABORATORY SHALL PROVIDE TEST REPORTS OF INSPECTIONS. ALL <br />TEST REPORTS SHALL INDICATE TYPES AND LOCATIONS OF DEFECTS FOUND <br />DURING INSPECTION, THE MEASURES REQUIRED AND PERFORMED TO CORRECT <br />SUCH DEFECTS, STATEMENTS OF FINAL APPROVAL OF WELDING AND BOLTING OF <br />SHOP AND FIELD CONNECTIONS, AND OTHER FABRICATION AND ERECTION DATA <br />PERTINENT TO THE SAFE AND PROPER WELDING AND BOLTING OF SHOP AND <br />FIELD CONNECTIONS. WELD INSPECTION REPORTS SHALL BE SIGNED BY AN <br />INSPECTOR WITH CURRENT CERTIFICATION AS AN AWS CERTIFIED WELDING <br />INSPECTOR (CWI). IN ADDITION TO THE PARTIES LISTED IN THIS SPECIFICATION, <br />THE FABRICATOR AND ERECTOR SHALL RECEIVE COPIES OF THE TEST REPORTS. <br />b. REJECTION OF MATERIAL OR WORKSMANSHIP: THE OWNER, ARCHITECT, <br />ENGINEER, AND TESTING LABORATORY RESERVE THE RIGHT TO REJECT ANY <br />MATERIAL OR WORKSMANSHIP NOT IN CONFORMANCE WITH THE CONTRACT <br />DOCUMENTS AT ANY TIME DURING THE PROGRESS OF THE WORK. HOWEVER, <br />THIS PROVISION DOES NOT ALLOW WAIVING THE OBLIGATION FOR TIMELY, IN <br />SEQUENCE INSPECTIONS. <br />c. REVIEW FIELD WELDER QUALIFICATIONS BY CERTIFICATION OR VERIFY BY <br />RETESTING. OBTAIN WELDER CERTIFICATES. <br />4. WELD INSPECTION AND PROCESS MONITORING: <br />a. WELDS PERFORMED IN THE FABRICATING SHOP MAY BE INSPECTED IN THE FIELD <br />UNLESS CONTINUOUS MONITORING OF THE WELDING PROCESS IS HEREIN <br />SPECIFIED OR IF ACCESS IN THE FIELD DUE TO OTHER WORK OR SHOP FINISHES <br />MAKES FIELD INSPECTION IMPRACTICAL. <br />b. APPROVE WELDING PROCEDURE SPECIFICATIONS SUBMITTED BY THE <br />CONTRACTOR. APPROVE ANY CHANGES SUBMITTED BY THE CONTRACTOR TO ANY <br />WPS THAT HAS ALREADY BEEN APPROVED. OBTAIN THE WELDING PROCEDURE <br />QUALIFICATION RECORD (WPQR) FOR EACH SUCCESSFUL WPS QUALIFICATION. <br />E. A FINAL INSPECTION REPORT FOR ALL ITEMS REQUIRING SPECIAL INSPECTION SHALL BE <br />COMPLETED AND SUBMITTED TO THE CITY OF ANAHEIM INSPECTION DIVISION. <br />PART II -REINFORCED CONCRETE 02 <br />3 3/4 2 1/2 3 4 1/2 110 <br />3/4 3 1/4 2 1/2 3 4 1/2 110 <br />4 2 1/2 3 4 1/2 40 <br />5/8 2 3/4 2 1/2 3 4 1/2 40 <br />3 1/4 2 1/2 3 4 1/2 50 <br />1/2 2 2 1/2 3 4 1/2 50 <br />2 1/2 2 1/2 3 4 1/2 30 <br />2 2 1/2 3 4 1/2 30 <br />3/8 1 1/2 2 1/2 3 4 1/2 30 <br /> DIA <br />(IN) <br />EFFECTIVE <br />EMBEDMENT (IN) <br />MINIMUM <br />CONCRETE <br />THICKNESS OVER <br />METAL DECK (IN) <br />MAXIMUM DEPTH <br />OF METAL DECK <br />(IN) <br />MINIMUM WIDTH <br />OF CELL <br />BOTTOM (IN) <br />REQUIRED <br />TORQUE <br />(FT LB) <br />HILTI KB-TZ2 EXPANSION ANCHOR - SOFFIT OF CONCRETE FILLED DECK <br />(f'c = 3,000 PSI MINIMUM) <br />16 <br />INSPECT FORMWORK FOR SHAPE, LOCATION, AND <br />DIMENSIONS OF THE CONCRETE MEMBER BEING <br />FORMED <br />PERIODIC ACI 318: 26.11.1.2(b) <br />15 VERIFY MAINTENANCE OF SPECIFIED CONCRETE <br />CURING TEMPERATURE AND TECHNIQUES PERIODIC ACI 318: 26.5.3-26.5.5 <br />14 INSPECT CONCRETE FOR PROPER APPLICATION <br />TECHNIQUES CONTINUOUS ACI 318: 26.5 <br />13 <br />PRIOR TO CONCRETE PLACEMENT, FABRICATE <br />SPECIMENS FOR STRENGTH TESTS, PERFORM <br />SLUMP AND AIR CONTENT TESTS, AND DETERMINE <br />THE TEMPERATURE OF CONCRETE <br />CONTINUOUS <br />ASTM C172 <br />ASTM C31 <br />ACI 318: 26.5, 26.12 <br />12 VERIFY USE OF REQUIRED CONCRETE DESIGN MIX PERIODIC ACI 318: 19, 26.4.3, 26.4.4 <br />11 <br />INSPECT POST-INSTALLED MECHANICAL ANCHORS <br />AND ADHESIVE ANCHORS WHICH ARE NOT <br />DEFINED IN (10) <br />PERIODIC ACI 318: 17.8.2, 17.8.2.4 <br />10 <br />INSPECT POST INSTALLED ADHESIVE ANCHORS IN <br />HORIZONTALLY OR UPWARDLY INCLINED <br />ORIENTATIONS <br />CONTINUOUS ACI 318: 17.8.2, 17.8.2.4 <br />9 INSPECT CONCRETE REINFORCEMENT AND VERIFY <br />PLACEMENT PERIODIC ACI 318: 20, 25.2, 25.3, <br />26.6-1-26.6-3 <br />CONCRETE TESTING AND INSPECTION (CBC TABLE 1705.3) <br />8 WELDING SINGLE-PASS FILLET WELDS ≤ 5/16" PERIODIC AWS D1.1 <br />7 WELDING SINGLE-PASS FILLET WELDS > 5/16" CONTINUOUS AWS D1.1 <br />6 WELDING MULTI-PASS FILLET WELDS CONTINUOUS AWS D1.1 <br />5 WELDING COMPLETE AND PARTIAL PENETRATION <br />GROOVE WELDS CONTINUOUS AWS D1.1 <br />4 <br />MATERIAL VERIFICATION OF WELD FILLER <br />MATERIALS. IDENTIFICATION MARKINGS TO <br />CONFORM TO AWS SPECIFICATION APPROVED IN <br />CONSTRUCTION DOCUMENTS <br />PERIODIC ANSI/AISC 360: A3.5 <br />WELDING TESTING AND INSPECTION (CBC SECTION 1705.2.1) <br />3 STRUCTURAL STEEL CERTIFIED MILL TEST <br />REPORTS PERIODIC ANSI/AISC 360: A3 <br />2 <br />STRUCTURAL STEEL IDENTIFICATION MARKINGS <br />TO CONFORM TO ASTM STANDARDS SPECIFIED ON <br />THE APPROVED CONSTRUCTION DOCUMENTS <br />PERIODIC ANSI/AISC 360: A3 <br />1 <br />MATERIAL VERIFICATION OF BOLTS, NUTS, AND <br />WASHERS. IDENTIFICATION MARKINGS TO <br />CONFORM TO ASTM STANDARDS SPECIFIED IN THE <br />APPROVED CONSTRUCTION DOCUMENTS <br />PERIODIC ASTM <br />ANSI/AISC 360: A3.3 <br />STRUCTURAL STEEL TESTING AND INSPECTION (CBC SECTION 1705.2.1) <br />ITEM TESTING AND INSPECTION FREQUENCY CODE REFERENCE <br />A. MATERIAL <br /> 1. ALL UNISTRUT FRAMING MEMBERS SHALL BE EITHER A1011 SS GR33 OR SHALL BE <br /> A653 GR 33 PER MANUFACTURER SPECIFICATIONS. <br /> 2. ALL BOLTS AND NUTS SHALL HAVE UNIFIED COARSE SCREWS AND BE ASTM A576 <br />GR1015 OR A1011SS GR 45 PER MANUFACTURER SPECIFICATIONS UNLESS NOTED <br />OTHERWISE ON PLANS AND DETAILS. <br /> 3. ALL FITTINGS ARE PUNCH-PRESS FROM HOT ROLLED, PICKLED, AND OILED STEEL <br />PLATES, STRIP OR COIL AND SHALL CONFORM TO ASTM A575, A576, A635, A1011 SS <br />GR33, OR A36 PER MANUFACTURER SPECIFICATIONS. <br />B. BOLT TORQUE VALUES SHALL BE ACHIEVED AS FOLLOWS PER THE UNISTRUT <br />SPECIFICATIONS (UNLESS NOTED OTHERWISE ON PLAN): <br /> 1. 1/4" BOLT = 6LB-FT MINIMUM, 7LB-FT MAXIMUM <br /> 2. 5/16" BOLT = 11LB-FT MINIMUM, 15LB-FT MAXIMUM <br /> 3. 3/8" BOLT = 19LB-FT MINIMUM, 25LB-FT MAXIMUM <br /> 4. 1/2" BOLT = 50LB-FT MINIMUM, 70LB-FT MAXIMUM <br /> 5. 5/8" BOLT = 100LB-FT MINIMUM, 125LB-FT MAXIMUM <br /> 6. 3/4" BOLT = 125LB-FT MINIMUM, 135LB-FT MAXIMUM <br />C. MANUFACTURER QUALIFICATIONS <br /> <br /> 1. THE MANUFACTURER SHALL NOT HAVE HAD LESS THAN 10 YEAR'S EXPERIENCE IN <br />MANUFACTURING STRUT SYSTEMS. <br /> 2. THE MANUFACTURER MUST CERTIFY ALL COMPONENTS SUPPLIED HAVE BEEN <br />PRODUCED IN ACCORDANCE WITH AN ESTABLISHED QUALITY ASSURANCE <br />PROGRAM. <br />D. INSTALLER QUALIFICATIONS <br /> 1. INSTALL MUST BE A UNISTRUT TRAINED MANUFACTURER'S AUTHORIZED <br />REPRESENTATIVE/INSTALLER WITH NOT LESS THAN 5 YEARS EXPERIENCE IN THE <br />INSTALLATION OF STRUT SYSTEMS. <br />E. DURING INSTALLATION, IT SHALL BE THE RESPONSIBILITY OF THE INSTALLER TO PROTECT <br />THE UNISTRUT SYSTEM FROM DAMAGE. UPON THE COMPLETION OF INSTALLATION, IT IS <br />THE GENERAL CONTRACTORS RESPONSIBILITY TO PROTECT THE UNISTRUT SYSTEM FROM <br />DAMAGE DURING THE REMAINDER OF CONSTRUCTION UNTIL SUBSTANTIAL COMPLETION. <br />PART V - UNISTRUT SPECIFICATIONS 11 <br />SANTA ANA MEDICAL OFFICES <br />1900 E. 4TH ST. <br />SANTA ANA, CA 92701 <br />SOCC 2023 R RAD SAN 1ST FLOOR <br />GEN RAD REPLACEMENT (5284) <br />CITY SUBMITTAL 04/19/2024 <br />BID SET 05/20/2024 <br />1900 E 4th St - <br />1011190678/9/2024