DATE:V I N C I & A S S O C I A T E S SHEET: <br />PROJECT:Santa Ana Distribution Center 1 Structural Engineers JOB NO.:22-3457 <br />1995 S Standard Ave & 1895 S Standard Ave175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360 ENGR.:JRV <br />Santa Ana, CA 805.496.2100 • VinciSE.com <br />CLIENT:Axis Solar <br />CHECK OF EXISTING ROOF STRUCTURE <br />Existing Roof Dead Load 11.25 psf <br />Existing Roof Live Load:20 psf reducable <br />PV Array Dead Load 2.85 psf <br />Per 2022 California Building Code Section 1607.14.4.1 <br />when a PV array is installed less than 24" above the surface of the roof <br />surface, the live load can be ignored below the PV array. <br />Therefore - if the 20 psf (12psf min when reduced) is eliminated below <br />the proposed PV Arrays, the roof is more than capable of supporting <br />the additional 2.85 psf dead load due to the proposed array. <br />Therefore, by observation, the existing roof structure is sufficient. <br />5/14/2024 1895 & 1995 S Standard <br />Ave1/7/2025