My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
800 N Tustin Ave Unit #H - Plan
PBA
>
Building
>
ProjectDox
>
T
>
Tustin Ave
>
800 N Tustin Ave Unit# H
>
800 N Tustin Ave Unit #H - Plan
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
6/6/2025 1:17:29 PM
Creation date
6/6/2025 1:16:48 PM
Metadata
Fields
Template:
Plan
Permit Number
20184073
30147809
40139552
101120961
Full Address
800 N Tustin Ave Unit# H
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
146
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
Show annotations
View images
View plain text
1.MAXIMUM AVAILABE FAULT CURRENT FROM SCE UTILITY COMPANY IS: 30,000 AIC. <br />AFC = 30,000 + MOTOR CONTRIBUTION = 30,000 + (6 X 70) = 30,420 A <br />2.ALL EQUIPMENT BUSSING AND GROUNDING ELECTRODE SHALL BE COPPER AND ALL WIRES <br />SHALL BE COPPER, THWN/THHN UNLESS NOTED OTHERWISE. <br />3.THE MAIN SWITCHBOARD AND PANEL BOARDS SHALL BE BY ONE MANUFACTURER ONLY. <br />4.ALL FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE HOLDER. <br />5.MAIN SWITCHGEAR CIRCUIT BREAKERS TO BE FULLY RATED FOR THE FAULT CURRENT <br />AVAILABLE. <br />6.ALL CIRCUIT BREAKER SHALL BE LABELLED TO CLEARLY INDICATE AREA BEING SERVED. <br />7.UNDERGROUND CONDUIT SHALL BE MINIMUM OF PVC SCHEDULE 40. REFER TO 2022 CEC TABLE <br />300.5 FOR THE MINIMUM COVER REQUIREMENTS OF DIRECT BURIAL CABLE. <br />8.ALL METAL PIPING & STRUCTURES INCLUDING GAS PIPING THAT IS LIKELY TO BE ENERGIZED <br />SHALL BE BONDED TO THE SERVICE GROUNDING POINT AS DESCRIBED IN CEC SECTION 250.104. <br />FIELD VERIFY & PROVIDE BONDING JUMPERS AS REQUIRED. <br />9.ALL TERMINATIONS AND CIRCUIT BREAKERS SHALL BE RATED FOR 75 DEGREES CENTIGRADE. <br />10.ALL ELECTRICAL EQUIPMENT, PANELS, FEEDERS, ETC. ARE NEW UNLESS NOTED OTHERWISE. <br />11.ALL THE ELECTRICAL SERVICES AND REQUIREMENTS ARE SUBJECT TO THE APPROVAL BY THE <br />UTILITY COMPANY AND THE DEPARTMENT OF BUILDING AND SAFETY. VERIFY EXACT <br />REQUIREMENTS PRIOR TO ROUGH-INS. <br />12.ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH SCE SERVICE <br />PLANNER FOR THE PRIMARY ELECTRICAL SERVICE PRIOR TO ANY WORK. <br />13.FEEDER LENGTH IS FOR CALCULATION ONLY NOT FOR BIDDING PURPOSES. <br />14.THE MAIN SERVICE SHALL BE TESTED BY A THIRD PARTY NRTL TESTING LABORATORY AND <br />SHALL BE CERTIFIED FOR SERVICE GROUND FAULT PROTECTION. THE MAIN SERVICE SHALL <br />NOT BE ENERGIZED PRIOR TO BUILDING INSPECTORS' RECEIPT OF THE THIRD PARTY TESTING <br />REPORT. <br />REFERENCE NOTES: <br />GENERAL NOTES <br />1.3/4"C - 1#6 CU G.. <br />2.TRANSFORMER PRIMARY DISCONNECTING MEANS SHALL BE LOCKABLE IN ACCORDANCE WITH <br />CEC 110.25 AND IT'S LOCATION SHALL BE FIELD MARKED ON THE TRANSFORMER PER CEC <br />450.14. <br />3.PROVIDE SURGE PROTECTION DEVICE FOR THE MAIN SWITCHBOARD. <br />4.PROVIDE EMON-DMON TYPE ELECTRICAL METER IN THE ELECTRICAL CLOSET NEXT TO MAIN <br />SWITCHBOARD TO MEASURE THE ELECTRICAL USAGE OF PANEL 'LA'. <br />- <br />MAIN SWITCHBOARD 'MSB' <br />400A, 277/480V, 3PH, 4W, 42KAIC <br />INCOMING UNDERGROUND SERVICE <br />CONDUCTOR FROM SCE TRASFORMER <br />M <br />400A <br />3P 125A <br />3P <br />70A <br />3P <br />1- <br />1 <br />/ <br />2 <br />" <br />C <br /> <br />- <br /> <br />3 <br /># <br />1 <br /> <br />C <br />U <br /> <br />+ <br /> <br />1 <br /># <br />6 <br /> <br />C <br />U <br /> <br />G <br />. <br />L= <br />4 <br />0 <br />' <br />, <br /> <br />% <br />V <br />D <br /> <br />= <br /> <br />0 <br />. <br />2 <br />4 <br />% <br />SCE METER <br />G <br />N <br />1"C., 1#3/0 CU TO BUILDING STEEL <br />1"C., 1#3/0 CU UFER GROUND <br />1"C., 1#3/0 TO COLD WATER <br />PIPING WITHIN 5FT OF <br />ENTRANCE TO BUILDING <br />400A BUS <br />(N) XFMR 'TLA' <br />45KVA <br />480-120/208V <br />3PH, 4W <br />%Z = 3.9% <br />PANEL <br />'LA' <br />150A <br />MCB <br />1 <br />Isc = 3.1kA <br />AFC = 30,420A <br />SEE GENERAL NOTE 1 <br />1 4 <br />MRI <br />CHILLER <br />@ ROOF <br />60AS <br />60AF <br />3P <br />60A <br />3P <br />3 <br />MRI MAIN <br />DISC. <br />PANEL <br />(MDP) <br />200AS <br />125AF <br />3P <br />Isc=18.9kA <br />1- <br />1 <br />/ <br />4 <br />" <br />C <br /> <br />- <br /> <br />3 <br /># <br />4 <br /> <br />C <br />U <br /> <br />+ <br /> <br />1 <br /># <br />8 <br /> <br />C <br />U <br /> <br />G <br />. <br />L= <br />6 <br />0 <br />' <br />, <br /> <br />% <br />V <br />D <br /> <br />= <br /> <br />0 <br />. <br />3 <br />5 <br />% <br />2 <br />2" <br />C <br /> <br />- <br /> <br />4 <br /># <br />1 <br />/ <br />0 <br /> <br />C <br />U <br /> <br />+ <br /> <br />1 <br /># <br />6 <br /> <br />C <br />U <br /> <br />G <br />. <br />L= <br />1 <br />0 <br />' <br />, <br /> <br />% <br />V <br />D <br /> <br />= <br /> <br />0 <br />. <br />1 <br />4 <br />% <br />125A <br />3P <br />1- <br />1 <br />/ <br />2 <br />" <br />C <br /> <br />- <br /> <br />3 <br /># <br />1 <br /> <br />C <br />U <br /> <br />+ <br /> <br />1 <br /># <br />1 <br /> <br />C <br />U <br /> <br />G <br />. <br />L= <br />7 <br />0 <br />' <br />, <br /> <br />% <br />V <br />D <br /> <br />= <br /> <br />0 <br />. <br />4 <br />2 <br />% <br />2 <br />CT <br />SCAN <br />200AS <br />125AF <br />3P <br />1" <br />C <br /> <br />- <br /> <br />3 <br /># <br />6 <br /> <br />C <br />U <br /> <br />+ <br /> <br />1 <br /># <br />1 <br />0 <br /> <br />C <br />U <br /> <br />G <br />. <br />L= <br />5 <br />0 <br />' <br />, <br /> <br />% <br />V <br />D <br /> <br />= <br /> <br />0 <br />. <br />3 <br />4 <br />% <br />Isc=14.8kA Isc=9.3kA Isc=11.2kA <br />SPD <br />30A <br />3P <br />3 <br />5 <br />10KAIC <br />M 4 <br />SHEET <br />PA / PM: <br />JOB NO.: <br />DRAWN BY: <br />CAUTION: 24"x36" <br />RE <br />M <br />A <br />R <br />K <br />S <br />DA <br />T <br />E <br />de <br />b <br />s <br />@ <br />s <br />h <br />p <br />a <br />r <br />t <br />n <br />e <br />r <br />s <br />. <br />n <br />e <br />t <br />ma <br />r <br />c <br />o <br />h <br />@ <br />s <br />h <br />p <br />a <br />r <br />t <br />n <br />e <br />r <br />s <br />. <br />n <br />e <br />t <br />(7 <br />1 <br />4 <br />) <br />3 <br />9 <br />0 <br />. <br />8 <br />6 <br />0 <br />0 <br />ar <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />e <br /> <br />a <br />n <br />d <br /> <br />p <br />l <br />a <br />n <br />n <br />i <br />n <br />g <br />PA <br />R <br />T <br />N <br />E <br />R <br />S <br />ww <br />w <br />. <br />s <br />h <br />p <br />a <br />r <br />t <br />n <br />e <br />r <br />s <br />. <br />n <br />e <br />t <br />07 <br />- <br />0 <br />3 <br />- <br />2 <br />0 <br />2 <br />4 <br />PL <br />A <br />N <br /> <br />C <br />H <br />E <br />C <br />K <br /> <br />S <br />U <br />B <br />M <br />I <br />T <br />T <br />A <br />L <br />UN <br />I <br />T <br />E <br />D <br /> <br />M <br />E <br />D <br />I <br />C <br />A <br />L <br /> <br />I <br />M <br />A <br />G <br />I <br />N <br />G <br /> <br />H <br />E <br />A <br />L <br />T <br />H <br />C <br />A <br />R <br />E <br />80 <br />0 <br /> <br />N <br />. <br /> <br />T <br />U <br />S <br />T <br />I <br />N <br /> <br />A <br />V <br />E <br />N <br />U <br />E <br />, <br />SA <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />5 <br />TE <br />N <br />A <br />N <br />T <br /> <br />I <br />M <br />P <br />R <br />O <br />V <br />E <br />M <br />E <br />N <br />T <br /> <br />F <br />O <br />R <br />: <br />Un <br />i <br />t <br />e <br />d <br /> <br />M <br />e <br />d <br />i <br />c <br />a <br />l <br /> <br />I <br />m <br />a <br />g <br />i <br />n <br />g <br /> <br />H <br />e <br />a <br />l <br />t <br />h <br />c <br />a <br />r <br />e <br />SU <br />I <br />T <br />E <br /> <br />- <br /> <br />H <br />Mechanical . Electrical . Plumbing <br />225 E Broadway, Suite 101A <br />Glendale, CA 91205 <br /># 213.820.3683 <br />Hestrada@elogicsce.com <br />10 <br />- <br />2 <br />8 <br />- <br />2 <br />0 <br />2 <br />4 <br />PL <br />A <br />N <br /> <br />C <br />H <br />E <br />C <br />K <br /> <br />R <br />E <br />S <br />U <br />B <br />M <br />I <br />T <br />T <br />A <br />L <br />1 <br />SI <br />N <br />G <br />L <br />E <br /> <br />L <br />I <br />N <br />E <br /> <br />D <br />I <br />A <br />G <br />R <br />A <br />M <br />E2.01 <br />1 <br />PA <br />R <br />T <br />N <br />E <br />R <br />S <br />SA <br />URABH JAGD ISH PANDY <br />AREG <br />I <br />STERED PROF E SS IONAL ENGI <br />N <br />EER <br />ELECTRICALSTATE OF CALIFORNIA <br />E-23194 <br />EXP. 6-30- 46 <br />1 <br />di <br />g <br />i <br />t <br />a <br />l <br /> <br />s <br />t <br />a <br />m <br />p <br /> <br />a <br />n <br />d <br /> <br />s <br />i <br />g <br />n <br />a <br />t <br />u <br />r <br />e <br />, <br /> <br />d <br />a <br />t <br />e <br /> <br />1 <br />1 <br />- <br />1 <br />3 <br />- <br />2 <br />0 <br />2 <br />4 <br />800 N Tustin Ave Unit <br />#H1/23/2025