POWER LEGEND AND SYMBOLS
<br />SYMBOL DESCRIPTION
<br />+96" OR 7'-6" AFF MOUNTING HEIGHT FROM FINISHED FLOOR TO BOTTOM LINE OF OUTLET OR EQUIPMENT. FOR
<br />LIGHT FIXTURES, IT IS TO BOTTOM OF FIXTURE.
<br />MAIN SWITCHBOARD, POWER OR LIGHT, FLOOR STANDING ENCLOSURE, (SEE SINGLE LINE
<br />DIAGRAM AND LOAD SUMMARY)
<br />BRANCH PANELBOARD, WALL MOUNTED, SEE PLANS AND SCHEDULE. (SURFACE MOUNTED)
<br />DISCONNECT SWITCH H.P. RATED 600 VOLTS RATED. "F" INDICATES FUSE TYPE. FUSES PER
<br />APPROVED MANUFACTURERS SHOP DRAWINGS.
<br />OR
<br />EQUIPMENT
<br />ID. No.
<br />SHEET No.
<br />DETAIL No.
<br />EQUIPMENT REFERENCE
<br />DETAIL REFERENCE
<br />DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS) MOUNTED +15" A.F.F. TO
<br />BOTTOM OF DEVICE U.O.N.
<br />MOLDED CASE CIRCUIT BREAKER
<br />EXISTING (DASH INDICATES) ELECTRICAL EQUIPMENT
<br />SURFACE MOUNTED EXIT SIGN/BUG EYE COMBO
<br />EXISTING LIGHTING FIXTURE
<br />LIGHTING LEGEND AND SYMBOLS
<br />SYMBOL DESCRIPTION
<br />(E)
<br />ABBREVIATIONS
<br />A AMPERE
<br />AF AMPERE FRAME RATING (CIRCUIT BREAKER)
<br />AFF ABOVE FINISHED FLOOR
<br />AFG ABOVE FINISHED GRADE
<br />AFU AMPERE FUSE RATING (FUSE)
<br />AIC AMPERE INTERRUPTING CAPACITY
<br />AS AMPERE SWITCH RATING (FUSE)
<br />AT AMPERE TRIP RATING (CIRCUIT BREAKER)
<br />AWG AMERICAN WIRE GAUGE
<br />BKBD BACKBOARD
<br />BLDG BUILDING
<br />BKR BREAKER
<br />C CONDUIT
<br />CB CIRCUIT BREAKER
<br />CKT CIRCUIT
<br />CFSD COMBINATION FIRE SMOKE DAMPER
<br />CO CONDUIT ONLY
<br />CONC CONCRETE
<br />CT CURRENT TRANSFORMER
<br />CU COPPER
<br />CL CENTERLINE
<br />DISC DISCONNECT
<br />DSBN DISTRIBUTION SECTION
<br />DN DOWN
<br />DWG DRAWING
<br />EA EACH
<br />EC ELECTRICAL CONTRACTOR
<br />EM EMERGENCY
<br />EMT ELECTRICAL METALLIC TUBING
<br />EXIST, (E)EXISTING
<br />EXO EXTERNAL OPERABLE DISCONNECT
<br />F FUSE
<br />FA FIRE ALARM
<br />FACP FIRE ALARM CONTROL PANEL
<br />FF FINISHED FLOOR
<br />FG FINISHED GRADE
<br />FLA FULL LOAD CURRENT
<br />FLUOR FLUORESCENT
<br />GEC GROUNDING ELECTRODE CONDUCTOR
<br />GEN GENERATOR
<br />GFCI GROUND FAULT CIRCUIT INTERRUPTER
<br />GFP GROUND FAULT PROTECTION
<br />GND GROUND
<br />HOA HAND-OFF-AUTOMATIC
<br />HP HORSE POWER
<br />HV HIGH VOLTAGE
<br />IDF INTERMEDIATE DISTRIBUTION FRAME
<br />IG ISOLATED/INSULATED GROUND
<br />INCAND INCANDESCENT
<br />ISC SHORT CIRCUIT CURRENT AVAILABLE IN RMS
<br />SYMMETRICAL AMPERES
<br />J-BOX JUNCTION BOX
<br />KCMIL THOUSAND CIRCULAR MILS
<br />KW KILOWATT
<br />KV KILO VOLT
<br />KVA KILO VOLT-AMPERE
<br />LDC LOCAL DISTRIBUTION CABINET
<br />LDF LOCAL DISTRIBUTION FRAME
<br />LCL LONG CONTINUOUS LOAD
<br />LTG LIGHTING
<br />LV LOW VOLTAGE
<br />MFR MANUFACTURER
<br />MAX MAXIMUM
<br />MCC MOTOR CONTROL CENTER
<br />MIN MINIMUM
<br />MH MANHOLE / METAL HALIDE
<br />M/M METER AND MAIN SECTION
<br />MULTI MULTI-METER SECTION
<br />MV MEDIUM VOLTAGE
<br />NC NORMALLY CLOSED
<br />NEC NATIONAL ELECTRICAL CODE
<br />NEMA NATIONAL ELECTRICAL MANUFACTURER'S
<br />ASSOCIATION
<br />NEW (N)NEW, TO BE FURNISHED AND INSTALLED BY
<br />CONTRACTOR
<br />NF NON-FUSED
<br />NIC NOT IN CONTRACT
<br />N/L NIGHT LIGHT
<br />NO NUMBER, NORMALLY OPEN
<br />NTS NOT TO SCALE
<br />OC ON CENTER
<br />OD OUTSIDE DIAMETER
<br />P POLE
<br />PB PULL BOX
<br />PF POWER FACTOR
<br />PNL PANEL
<br />POC POINT OF CONNECTION
<br />PP POWER POLE
<br />PWR POWER
<br />PVC POLYVINYL CHLORIDE
<br />QUAD QUADRUPLEX
<br />QTY QUANTITY
<br />REQD REQUIRED
<br />REQMT REQUIREMENT
<br />RGS RIGID GALVANIZED STEEL
<br />RMC RIGID METALLIC CONDUIT
<br />RM ROOM
<br />RNC RIGID NONMETALLIC CONDUIT
<br />SHT SHEET
<br />SN SOLID NEUTRAL
<br />SPEC SPECIFICATIONS
<br />SPDT SINGLE POLE, DOUBLE THROW
<br />SPST SINGLE POLE, SINGLE THROW
<br />SW SWITCH
<br />SWBD SWITCHBOARD
<br />TC TIME CLOCK
<br />TEL TELEPHONE
<br />TERM TERMINAL
<br />TP TEMPORARY POLE
<br />TYP TYPICAL
<br />UGPS UNDERGROUND PULL SECTION
<br />UL UNDERWRITERS LABORATORY
<br />UPS UNINTERRUPTIBLE POWER SUPPLY
<br />UON UNLESS OTHERWISE NOTED
<br />V VOLT, VOLTAGE
<br />VA VOLT-AMPERE
<br />VFC VARIABLE FREQUENCY CONTROLLER
<br />VFD VARIABLE FREQUENCY DRIVE
<br />W WATT
<br />WH WATT-HOUR
<br />WP WEATHERPROOF
<br />WT WEATHERTIGHT
<br />WW WIREWAY
<br />XP EXPLOSION PROOF
<br />Z IMPEDANCE
<br />4W FOUR-WIRE
<br />3W THREE-WIRE
<br />5S JUNCTION BOX
<br />(4 11/16" SQUARED X2 1/8" DEEP)
<br />Ø DIAMETER, PHASE
<br />#NUMBER
<br />°C DEGREE CELSIUS
<br />(E)EXISTING DEVICE TO REMAIN
<br />(R)REMOVE EXISTING DEVICE AND ASSOCIATED
<br />CONDUIT AND WIRE
<br />(RL)REMOVE EXISTING DEVICE AND RELOCATE AS
<br />SHOWN ON PLAN
<br />(NL)NEW LOCATION OF RELOCATED DEVICE
<br />APPLICABLE CODES
<br />GENERAL NOTES
<br />NOTE TO CONTRACTOR
<br />DO NOT SCALE DRAWINGS
<br />CONTRACTOR SHALL VERIFY PLANS AND EXISTING DIMENSIONS AND CONDITIONS ON THE JOB SITE AND SHALL
<br />IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE WORK OR BE
<br />RESPONSIBLE FOR THE SAME.
<br />RACEWAY CONCEALED IN WALLS OR ABOVE CEILING, 3/4" UON
<br />1.2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
<br />2.2022 CALIFORNIA BUILDING CODE (CBC),PART 2, TITLE 24 C.C.R. (IBC WITH AMENDMENTS)
<br />3.2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R. (NEC WITH AMENDMENTS)
<br />4.2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R. (UMC WITH AMENDMENTS)
<br />5.2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R. (UPC WITH AMENDMENTS)
<br />6.2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R. (IFC WITH AMENDMENTS)
<br />7.2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
<br />8.2022 TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
<br />9.2022 CALIFORNIA ENERGY CODE (PART 6, TITLE 24 C.C.R.)
<br />10.2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CGBSG), PART 11, TITLE 24 C.C.R.s
<br />11.CITY OF FONTANA MUNICIPAL CODE; ORDINANCE 1918
<br />1.EQUALS SHALL BE CONSIDERED UPON SUBMITTAL REVIEW AND APPROVAL. PLEASE NOTE THAT IF AN ALTERNATE IS CONSIDERED:
<br />a.THE CONTRACTOR IS COMPLETELY AND SOLELY RESPONSIBLE FOR ALL ASPECTS OF THE SUBSTITUTION INCLUDING UPDATING CONSTRUCTION DOCUMENTS, OBTAINING APPROVALS AND PERMITS FROM LOCAL AUTHORITY, AND COORDINATING WITH ALL TRADES TO ENSURE
<br />CHANGES TO AFFECTED BUILDING SYSTEM ARE ACCOUNTED FOR AND ACCEPTABLE TO THE ENGINEERING TEAM. CONTRACTOR SHALL ENSURE SUBSTITUTED EQUIPMENT MEETS OR EXCEEDS DESIGN INTENT REGARDING RATINGS, PERFORMANCE, DIMENSIONAL CLEARANCES,
<br />PHYSICAL DIMENSIONS (MAX/MIN), WEIGHT LIMITATIONS, AND OTHER ASPECTS, PROVING SUBSTITUTION IS SUITABLE TO THE APPLICATION. ENGINEERS WILL REVIEW THE RATING AND PERFORMANCE OF SUBSTITUTED EQUIPMENT ONLY AND WILL NOT ASSUME RESPONSIBILITY FOR
<br />SUBSTITUTION AT ANY LEVEL.
<br />b.IF CONTRACTOR CANNOT MAKE SUBSTITUTED EQUIPMENT WORK IN THIS PROJECT, CONTRACTOR SHALL REVERT TO REQUIREMENTS OF PERMITTED CONSTRUCTION DOCUMENTS AT THEIR EXPENSE.
<br />c.IT IS UNDERSTOOD BY ALL PARTIES THAT ANY SUBSTITUTIONS OF SPECIFIED PRODUCTS ARE DONE FOR THE PURPOSE OF COST SAVINGS TO THE OWNER. THEREFORE, ANY MATERIAL SUBSTITUTION OR DEVIATIONS PROPOSED BY THE CONTRACTOR SHALL BE INCLUDED WITH THE
<br />INITIAL BID AND SHALL SHOW A LINE ITEMS CREDIT TO THE OWNER FOR EACH SUBSTITUTION IN LIEU OF SPECIFIED PRODUCTS.
<br />d.CONTRACTOR SHALL PROVIDE A POINT BY POINT PHOTOMETRIC STUDY FOR ALL AREAS WHERE ALTERNATE FIXTURES ARE SUBMITTED. LIGHT LEVELS WILL BE REVIEWED FOR COMPLIANCE WITH PROJECT REQUIREMENTS AND BASIS OF DESIGN VALUES.
<br />2.THE FIXTURE SCHEDULE INDICATES GENERAL DESCRIPTION OF LIGHTING FIXTURES AND MANUFACTURERS CATALOG NUMBERS. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO DETERMINE THE CORRECT CEILING CONFIGURATION AND PROVIDE THE FIXTURES WITH ALL NECESSARY
<br />TRIMS AND MOUNTING HARDWARE SO THAT BOTH THE CEILING SYSTEM AND THE FIXTURE CONSTRUCTION MATCHES. PROVIDE SEISMIC HANGERS AS REQUIRED.
<br />3.IT SHALL BE CONTRACTORS RESPONSIBILITY TO VERIFY THE EXACT LOCATION OF ALL LIGHTING FIXTURES AND TYPE OF CEILING WITH ARCHITECTURAL REFLECTED CEILING PLAN PRIOR TO ANY WORK. SEE ARCHITECTURAL REFLECTED CEILING PLAN PRIOR TO ANY WORK. SEE ARCHITECTURAL
<br />ELEVATION DRAWING FOR MOUNTING HEIGHTS OF WALL MOUNTED FIXTURES.
<br />4.A JUNCTION BOX MUST BE PROVIDED WITH ALL EXIT LIGHTS CONNECTED TO MORE THAN ONE SET OF CONDUCTORS UNLESS THE EXIT LIGHT FIXTURE IS FURNISHED WITH AN APPROVED OUTLET BOX FOR THROUGH WIRING.
<br />5.BATTERY PACK EMERGENCY TEST SWITCHES SHALL BE INTEGRAL TO LIGHT FIXTURE. COORDINATION OF SWITCH LOCATION IS REQUIRED WITH DESIGN TEAM IF INTEGRAL INSTALLATION IS NOT POSSIBLE.
<br />6.FIXTURES DESIGNATED AS EMERGENCY SHALL BE SUPPLIED WITH INTEGRAL BATTERY PACK CAPABLE OF POWERING LAMPS FOR 90 MINUTES.
<br />7.PROVIDE ALL REQUIRED MOUNTING HARDWARE ANCHORAGE AND SUPPORTS TO INSTALL LIGHTING FIXTURES.
<br />8.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THAT THE FIXTURE BALLAST OR DRIVER VOLTAGE MATCHES THE CIRCUIT VOLTAGE SUPPLYING FIXTURE PRIOR TO ORDERING.
<br />9.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY BALLAST/DRIVER DIMMING CONFIGURATION IS COMPATIBLE WITH CONTROLS BEING PROVIDED PRIOR TO ORDERING FIXTURES. EX. 2 WIRE, 3 WIRE, 4 WIRE, 0-10V, CAT 5, ETC.
<br />10.LED LIGHT FIXTURES SHALL BE IN ACCORDANCE WITH IES, NFPA, UL, AS SHOWN ON THE DRAWINGS, AND AS SPECIFIED.2SINGLE LINE DIAGRAM
<br />2000A
<br />UGPS
<br />EXISTING SERVICE
<br />GROUND
<br />1 2
<br />(E)
<br />2500A
<br />3P
<br />G
<br />N
<br />2000A
<br />(E)
<br />3P
<br />(E)
<br />200A
<br />3P
<br />(E) MAIN SWITCHBOARD 'MSB1'
<br />2000A 480Y/277V 3Ø 4W 42KAIC
<br />EXISTING
<br />EXISTING
<br />PANEL
<br />LA
<br />(E) XFMR
<br />7.5 KVA
<br />EXISTING
<br />EXISTING
<br />EXISTING
<br />2500A 'MSB2'
<br />(E)
<br />400A
<br />3P
<br />3
<br />TITLE 24 ENERGY FORMS
<br />LIGHTING CONTROLS AND ENERGY COMPLIANCE FORMS ARE NOT
<br />REQUIRED PER:
<br />CALIFORNIA ENERGY CODE (TITLE 24)
<br />SECTION 130.1(c)1
<br />EXCEPTION 5: ILLUMINATION PROVIDE BY LIGHTING EQUIPMENT THAT IS
<br />DESIGNATED FOR EMERGENCY LIGHTING, CONNECTED TO AN EMERGENCY
<br />POWER SOURCE OR BATTERY SUPPLY, AND IS INTENDED TO FUNCTION IN
<br />EMERGENCY MODE ONLY WHEN NORMAL POWER IS ABSENT.
<br />1PANEL SCHEDULE
<br />(E)
<br />EMERGENCY LIGHTING FIXTUREF1E
<br />1.ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO
<br />THE LATEST CALIFORNIA CODE OF REGULATIONS (CCR),
<br />NATIONAL ELECTRICAL CODE EDITION AND ALL
<br />APPLICABLE LOCAL CODES AND REGULATIONS.
<br />2.WHERE WIRE SIZES ARE INDICATED ON PLANS, FOR
<br />INDIVIDUAL CIRCUITS, THE WIRE SIZE INDICATED SHALL
<br />APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE
<br />NOTED.
<br />3.CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION
<br />BOXES, SWITCHES, ETC. AND MAKE FINAL CONNECTION AS
<br />REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING
<br />ELECTRICAL CONNECTIONS.
<br />4.DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL
<br />ARRANGEMENT OF SYSTEMS AND WORK INCLUDED.
<br />FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK
<br />DRAWINGS OR OTHER TRADES RELATING TO WORK TO
<br />VERIFY SPACE IN WHICH WORK WILL BE INSTALLED.
<br />MAINTAIN HEADROOM AND MINIMUM CODE REQUIRED
<br />WORKING CLEARANCES AT ALL TIMES.
<br />5.PROVIDE PULL BOXES WHEREVER NECESSARY TO
<br />FACILITATE PULLING OF CONDUCTORS. COORDINATE
<br />LOCATIONS OF BOXES WITH OTHER TRADES TO AVOID
<br />CONFLICT. PULL BOXES SHALL BE ACCESSIBLE. THE SIZE
<br />OF PULL BOX SHALL COMPLY WITH N.E.C. REQUIREMENTS.
<br />6.ALL ELECTRIC MATERIAL SHALL BE LISTED BY "UL" FOR
<br />THE TYPE OF APPLICATION AND "UL" LABEL SHALL
<br />APPEAR ON ALL ELECTRICAL EQUIPMENT.
<br />7.ALL DISTRIBUTION AND CONTROL EQUIPMENT (SUCH AS
<br />CB's, SWITCHES, CONTACTORS, ETC.), TERMINATIONS
<br />SHALL BE FULLY RATED PER UL AS FOLLOWS:
<br />a. 125A OR LESS : 60°C OR MORE;
<br />b. MORE THAN 125A : 75°C OR MORE.
<br />8.ANY ERRORS, OMISSIONS, OR DESIGN DISCREPANCIES ON
<br />PLANS OR SPECIFICATIONS SHALL BE BROUGHT TO THE
<br />ATTENTION OF THE ELECTRICAL ENGINEER FOR
<br />CLARIFICATION OR CORRECTION PRIOR TO
<br />CONSTRUCTION AND PREPARATION OF SUBMITTAL
<br />PACKAGES.
<br />9.CONDUCTORS SHALL HAVE UNDERWRITER'S
<br />LABORATORIES, INC.(UL) LISTED, 600 VOLT INSULATION OF
<br />TYPE SPECIFIED BELOW OR ELSEWHERE IN THE
<br />SPECIFICATIONS. CONDUCTORS SHALL BE COPPER.
<br />1. BRANCH CIRCUITS - LIGHTING AND POWER.
<br />a. #10 AWG AND SMALLER, SOLID WIRE TYPE THW OR
<br />THHN/THWN, THHW(THHN FOR DRY LOCATION ONLY).
<br />b. #8 AWG TO #2 AWG, STRANDED TYPE THW OR
<br />THHN/THHW.
<br />c. #1 AWG AND LARGER, STRANDED TYPE XHHW.
<br />2. FEEDERS : TYPE THW OR THHN/THWN, OR XHHW.
<br />10.PROVIDE GREEN INSULATED GROUNDING CONDUCTOR IN
<br />EACH RACEWAY INCLUDING CONDUITS, PLUG STRIPS,
<br />WIREMOLD. SIZE OF GROUNDING SHALL BE IN
<br />ACCORDANCE WITH NATIONAL ELECTRIC CODE ARTICLE
<br />250.
<br />11.WIRING METHOD SHALL BE EMT ABOVE GROUND AND
<br />MOUNTED IN CONCEALED SPACES AND SCHEDULE-40 PVC
<br />FOR UNDERGROUND INSTALLATION. USE RIGID WHEN
<br />ENCASED IN CONCRETE OR SUSCEPTIBLE TO DAMAGE.
<br />12.USE 10AWG CONDUCTORS FOR 20 AMPERE, 120V BRANCH
<br />CIRCUITS LONGER THAN 75 FEET.
<br />USE 10AWG CONDUCTORS FOR 20 AMPERE, 277V BRANCH
<br />CIRCUITS LONGER THAN 200 FEET.
<br />13.ALL FLUORESCENT LUMINAIRES THAT UTILIZE DOUBLE
<br />ENDED LAMPS THAT CONTAIN BALLAST(S) THAT CAN BE
<br />SERVICED IN PLACE SHALL HAVE A DISCONNECTING
<br />MEANS EITHER INTERNAL OR EXTERNAL TO EACH
<br />LUMINAIRE. THE LINE SIDE TERMINALS OF THE
<br />DISCONNECTING MEANS SHALL BE GUARDED. [CEC
<br />410.130(G)(1)].
<br />14.UNLESS OTHERWISE INDICATED, SHARING OF
<br />NEUTRAL/GROUNDED CONDUCTORS AMONG SINGLE
<br />PHASE BRANCH CIRCUITS OF DIFFERENT PHASES
<br />INSTALLED IN THE SAME RACEWAY IS NOT PERMITTED.
<br />PROVIDE DEDICATED NEUTRAL/GROUNDED CONDUCTOR
<br />FOR EACH INDIVIDUAL BRANCH CIRCUIT.
<br />PROJECT TITLE
<br />DESIGNED BY
<br />DRAWN BY
<br />CHECKED BY
<br />DATE
<br />SCALE
<br />JOB NO.
<br />SHEET NO.
<br />DATE BY ISSUE FOR
<br />RM
<br />OP
<br />BK
<br />08.07.24
<br />24-212
<br />ISSUE DATE:
<br />REVISION:
<br />NUM.DATE BY REVISION FOR
<br />1
<br />2
<br />3
<br />4
<br />5
<br />7
<br />CONSULTANT
<br />PR
<br />O
<br />J
<br />E
<br />C
<br />T
<br />
<br />F
<br />O
<br />R
<br />:
<br />STAMP
<br />6
<br />SHEET TITLE
<br />50
<br />0
<br />
<br />W
<br />.
<br />
<br />W
<br />A
<br />R
<br />N
<br />E
<br />R
<br />
<br />A
<br />V
<br />E
<br />.
<br />
<br />S
<br />U
<br />I
<br />T
<br />E
<br />
<br />2
<br />0
<br />0
<br />Sa
<br />n
<br />t
<br />a
<br />
<br />A
<br />n
<br />a
<br />,
<br />
<br />C
<br />A
<br />
<br />9
<br />2
<br />7
<br />0
<br />7
<br />AS NOTED
<br />BU
<br />I
<br />L
<br />D
<br />E
<br />R
<br />S
<br />
<br />S
<br />U
<br />R
<br />P
<br />L
<br />U
<br />S
<br />R:
<br />\
<br />_
<br />P
<br />R
<br />O
<br />J
<br />E
<br />C
<br />T
<br />\
<br />2
<br />0
<br />2
<br />4
<br />\
<br />2
<br />4
<br />-
<br />2
<br />1
<br />2
<br />
<br />B
<br />U
<br />I
<br />L
<br />D
<br />E
<br />R
<br />S
<br />
<br />S
<br />U
<br />R
<br />P
<br />L
<br />U
<br />S
<br />\
<br />_
<br />C
<br />A
<br />D
<br />\
<br />2
<br />4
<br />-
<br />2
<br />1
<br />2
<br />
<br />E
<br />-
<br />F
<br />R
<br />O
<br />N
<br />T
<br /> -
<br />
<br />20
<br />2
<br />4
<br />-
<br />1
<br />1
<br />-
<br />2
<br />1
<br /> -
<br />
<br />RO
<br />Y
<br />
<br />M
<br />O
<br />R
<br />A
<br />L
<br />E
<br />S
<br />San Bernardino, CA 92408
<br />412 E. Vanderbilt Way Phone: 909.890.3700
<br />Fax: 909.890.3770
<br />Email: cadd@designwesteng.com
<br />DESIGN WEST ENGINEERING
<br />MECHANICAL ELECTRICAL ENERGY CONSULTANTS
<br />ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS
<br />ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED
<br />TO BE USED IN CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL
<br />NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE
<br />WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR
<br />DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYING SPECIFICATIONS
<br />WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING.
<br />ELECTRICAL
<br />LEGENDS & NOTES
<br />E-0.1
<br />SHEET INDEX
<br />SHEET NUMBER SHEET TITLE
<br />E-0.1 ELECTRICAL LEGENDS & NOTES
<br />E-1.2 SITE LIGHTING PLAN
<br />E-1.3 GENERAL LIGHTING PHOTOMETRICS PLAN
<br />E-1.4 EMERGENCY EGRESS LIGHTING
<br />E2.1 ELECTRICAL DETAILS
<br />E-3.1 ELECTRICAL SPECIFICATIONS
<br />SIGNED:11/21/2024
<br />500 W Warner Ave
<br />Unit B5/6/2025
|