ELECTRICAL SPECIFICATIONS <br />PART 1 GENERAL <br />1.01 SCOPE OF WORK <br />A.WORK COVERED BY THIS SECTION CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES, AND MATERIALS, <br />UNLESS OTHERWISE SPECIFIED, AND IN PERFORMING ALL OPERATIONS NECESSARY FOR THE INSTALLATION OF A <br />COMPLETE AND OPERABLE ELECTRICAL SYSTEM AS REQUIRED BY THESE SPECIFICATIONS AND AS INDICATED ON THE <br />DRAWINGS. <br />B.THE CONTRACTOR SHALL EXAMINE ALL DRAWINGS AND SPECIFICATIONS IN A MANNER TO BE FULLY COGNIZANT OF <br />ALL WORK REQUIRED UNDER THIS SECTION. <br />C.THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS UNLESS OTHERWISE ARRANGED AND <br />SCHEDULE ALL REQUIRED INSPECTIONS FOR THE EXECUTION OF THE WORK UNDER THIS CONTRACT. <br />1.02 GENERAL REQUIREMENTS <br />A.WORK DONE UNDER THIS SECTION SHALL COMPLY WITH THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE, <br />NEC (NATIONAL ELECTRICAL CODE), THE STATE OF CALIFORNIA TITLE 24, THE STATE BUILDING STANDARDS, (OSHA) <br />OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, AND TO ANY APPLICABLE LOCAL JURISDICTIONAL <br />REQUIREMENTS. IN CASE OF CONFLICT BETWEEN REQUIREMENT, THE MOST RESTRICTIVE SHALL APPLY. <br />1.03 ELECTRICAL CONTRACTOR'S RESPONSIBILITY <br />A.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN A COMPLETE SET OF DRAWINGS AND SPECIFICATIONS. <br />CONTRACTOR SHALL CHECK THE DRAWINGS OF THE OTHER TRADES AND SHALL CAREFULLY READ THE ENTIRE <br />SPECIFICATIONS AND DETERMINE HIS RESPONSIBILITIES. <br />B.BEFORE SUBMITTING THE BID, THE ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND FULLY ACQUAINT <br />HIMSELF WITH EXISTING CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL THE EQUIPMENT <br />AND ASSOCIATED WIRING IN SUCH A MANNER AS TO CONFORM WITH THE EXISTING STRUCTURE OF THE BUILDING, <br />AVOID OBSTRUCTIONS, AND MEET APPLICABLE CODE REQUIREMENTS. <br />C.THE INTENT OF THESE DRAWINGS IS TO DESCRIBE A COMPLETE AND OPERABLE SYSTEM. WHERE EXISTING <br />CONDITIONS DIFFER FROM DRAWINGS, ADJUSTMENT SHALL BE MADE AND ALLOWANCES INCLUDED FOR ALL <br />NECESSARY EQUIPMENT TO COMPLETE ALL PARTS OF THE DRAWINGS AND SPECIFICATIONS. BRING ANY QUESTIONS <br />TO THE ARCHITECT OR ENGINEER'S ATTENTION PRIOR TO BIDDING. <br />D.WHEREVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT, DEVICES, CIRCUIT BREAKERS, <br />ETC., ARISES ON THE DRAWING AND/OR SPECIFICATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING <br />AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITION NOTED ON DRAWINGS <br />AND/OR IN SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS AS REQUIRED BY THE OWNER AND <br />ENGINEER. <br />1.04 WORK NOT INCLUDED <br />A.CERTAIN LABOR, MATERIALS, OR EQUIPMENT MAY BE FURNISHED UNDER OTHER CONTRACTS BY THE OWNER. WHEN <br />SUCH IS THE CASE, THE EXTENT, SOURCE, AND DESCRIPTION OF THESE ITEMS WILL BE INDICATED ON THE DRAWINGS <br />OR DESCRIBED IN THE SPECIFICATIONS. UNLESS OTHERWISE NOTED, ALL LABOR, MATERIALS AND EQUIPMENT FOR <br />THE COMPLETE INSTALLATION OF THE ELECTRICAL WORK SHALL BE PROVIDED UNDER THIS SECTION OF THESE <br />SPECIFICATIONS. <br />1.05 SPECIAL REQUIREMENTS <br />A.THE DRAWINGS INDICATE GENERAL ARRANGEMENT OF CIRCUITS, OUTLETS, LOCATIONS OF MOTOR CONTROLLERS <br />WITH DISCONNECTS, PANELBOARDS, CONDUIT ROUTING, AND OTHER WORK. INFORMATION SHOWN ON THE <br />DRAWINGS IS ESSENTIALLY DIAGRAMMATIC; HOWEVER, RECIRCUITING OR RELOCATING ELECTRICAL EQUIPMENT WILL <br />NOT BE PERMITTED WITHOUT SPECIFIC WRITTEN APPROVAL OF THE ENGINEER. <br />1.06 SUBMITTALS <br />A.AFTER AWARD OF THE CONTRACT AND BEFORE ANY MATERIALS ARE DELIVERED TO THE JOB SITE, A COMPLETE LIST <br />OF ALL MATERIALS PROPOSED TO BE FURNISHED AND INSTALLED UNDER THIS SECTION MUST BE PROVIDED. <br />B.SUBMIT TO THE ENGINEER FOR APPROVAL ONE PRINT AND ONE REPRODUCIBLE OF ALL LIGHTING FIXTURES, <br />SWITCHGEAR, PANELBOARDS, MOTOR CONTROL CENTERS, TRANSFORMERS, AND MOTOR STARTERS. SHOP <br />DRAWINGS SHALL INCLUDE MANUFACTURER'S PRINTED INFORMATION FOR EACH OF THESE ITEMS IDENTIFIED ON THE <br />DRAWINGS. THE INFORMATION SHALL INCLUDE, AS MINIMUM, OVERALL DIMENSIONS, WEIGHT, PHASE, VOLTAGE <br />RATINGS, WIRING DIAGRAMS, AND NAMEPLATE DATA. <br />1.07 STANDARDS AND MATERIALS <br />A.ALL MATERIALS SHALL CONFORM WITH THE CURRENT APPLICABLE INDUSTRY STANDARDS, NEMA (NATIONAL <br />ELECTRICAL MANUFACTURER'S ASSOCIATION), ANSI (AMERICAN NATIONAL STANDARDS INSTITUTE), IPCEA (INSULATED <br />POWER CABLE ENGINEERS ASSOCIATION), IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS), NATIONAL <br />ELECTRICAL SAFETY CODE. <br />B.UNLESS OTHERWISE INDICATED, ALL MATERIALS SHALL BE UNDERWRITERS LABORATORIES LISTED AND LABELED, OR <br />CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY. <br />C.WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS THE ELECTRICAL MECHANICAL EFFICIENCY. <br />DEFECTIVE AND DAMAGED MATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO FINAL APPROVAL AND <br />ACCEPTANCE. THE DRAWINGS AND SPECIFICATIONS TAKE PRECEDENCE WHEN THEY ARE MORE STRINGENT THAN <br />CODES, STATUTES, OR ORDINANCES IN EFFECT. APPLICABLE CODES, STANDARDS, ORDINANCES, AND STATUTES TAKE <br />PRECEDENCE WHEN THEY ARE MORE STRINGENT OR CONFLICT WITH THE DRAWINGS OR SPECIFICATIONS. <br />1.08 DELIVERY AND STORAGE OF MATERIALS <br />A.THE CONTRACTOR SHALL INVESTIGATE EACH SPACE IN THE BUILDING THROUGH WHICH EQUIPMENT MUST PASS TO <br />REACH ITS FINAL LOCATIONS. IF NECESSARY, THE MANUFACTURER SHALL BE REQUIRED TO SHIP HIS MATERIAL IN <br />SECTIONS, SIZED TO PERMIT PASSING THROUGH SUCH RESTRICTED AREAS IN THE BUILDING. <br />B.THE CONTRACTOR SHALL RETAIN IN HIS POSSESSION AND SHALL BE RESPONSIBLE FOR ALL PORTABLE AND <br />DETACHABLE PARTS OF PORTIONS OF INSTALLATIONS SUCH AS FUSES, KEY LOCKS, ADAPTERS, BLOCKING CLIPS, AND <br />INSERTS UNTIL FINAL COMPLETION OF WORK. THESE PARTS SHALL BE DELIVERED TO THE OWNER UPON COMPLETION <br />OF THE WORK. <br />PART 2 PRODUCTS <br />2.01 EQUIPMENT AND MATERIALS <br />A.ALL MATERIALS FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE NEW, FREE FROM DEFECTS, AND <br />SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE OF THE WORK. SHOULD ANY <br />TROUBLE DEVELOP DURING THEIR PERIOD DUE TO DEFECTIVE MATERIALS OR FAULTY WORKMANSHIP, THE <br />CONTRACTOR SHALL FURNISH ALL NECESSARY MATERIALS AND LABOR TO CORRECT THE TROUBLE WITHOUT ANY <br />COST TO THE OWNER. ANY DEFECTIVE MATERIAL OR INFERIOR WORKMANSHIP NOTED AT THE TIME OF INSTALLATION <br />SHALL BE CORRECTED IMMEDIATELY TO THE SATISFACTION OF THE OWNER. <br />B.ALL MAJOR EQUIPMENT COMPONENTS SHALL HAVE THE MANUFACTURER'S NAME, ADDRESS, MODEL NUMBER, AND <br />SERIAL NUMBER PERMANENTLY ATTACHED IN A CONSPICUOUS MANNER. <br />2.02 CONDUIT <br />A.PROVIDE RACEWAYS AS INDICATED ON THE DRAWINGS AND AS HEREIN SPECIFIED. CONDUITS SHALL BE RIGID STEEL <br />"GRC" (THICK WALL) GALVANIZED; ELECTRICAL METALLIC TUBING "EMT" (THIN WALL); FLEXIBLE STEEL, GALVANIZED; <br />LIQUID-TIGHT, FLEXIBLE STEEL CONDUIT WITH GROUND BOND; ALUMINUM CONDUIT; OR SCHEDULE 40 PVC. <br />B.ALL EMPTY CONDUITS (CO) SHALL BE SCHEDULE 40 PVC UNLESS OTHERWISE INDICATED ON THE DRAWING. <br />C.WHERE CONDUIT CROSSES AN EXPANSION JOINT, PROVIDE APPROVED FITTINGS WHICH ALLOW DEFLECTIONS <br />EQUIVALENT TO TWICE THE MOVEMENT ALLOWED BY THE DESIGN. <br />2.03 CONDUCTORS <br />A.PROVIDE A COMPLETE SYSTEM OF CONDUCTORS IN RACEWAY SYSTEMS AS SHOWN ON THE DRAWINGS AND THEN <br />HEREIN SPECIFIED. <br />B.LIGHTING AND POWER CONDUCTORS SHALL BE COPPER, 600 VOLT, TYPE THWN/THHN, NO. 12 MINIMUM UNLESS <br />OTHERWISE NOTED. <br />C.CONTROL CONDUCTORS SHALL BE 600V, TYPE THWN/THHN, NO.14 MINIMUM SIZE UNLESS OTHERWISE NOTED. <br />2.04 FITTINGS <br />A.CONNECTOR, COUPLING, LOCKNUT, BUSHINGS AND CAPS USED WITH RIGID CONDUIT SHALL BE STEEL, THREADED <br />AND GALVANIZED. BUSHINGS SHALL BE INSULATED. <br />B.EMT FITTINGS, CONNECTORS AND COUPLINGS SHALL BE STEEL, ZINC, OR CADMIUM PLATED, COMPRESSION TYPE, <br />WITH INSULATED THROAT. <br />C.FLEXIBLE STEEL CONDUIT CONNECTORS SHALL BE TWIST-IN-TYPE WITH INSULATED THROAT. THE FINISH SHALL BE <br />ZINC OR CADMIUM PLATING. <br />D.EMT CONDUIT FITTINGS SHALL BE THE COMPRESSION TYPE; SET SCREW FITTINGS SHALL NOT BE USED. <br />2.05 JUNCTION AND PULL BOXES <br />A.FOR INTERIOR DRY LOCATIONS, BOXES SHALL BE GALVANIZED ONE-PIECE DRAWN STEEL, KNOCKOUT TYPE WITH <br />REMOVABLE, MACHINE SCREW SECURED COVERS. <br />B.ALL BOXES SHALL BE SIZED FOR THE NUMBER AND SIZES OF CONDUCTORS AND CONDUITS ENTERING THE BOX AND <br />EQUIPPED WITH PLASTER RINGS WHERE REQUIRED. <br />2.06 OUTLET BOXES (NOT USED) <br />2.07 SWITCHES <br />A.ALL DEVICES SHALL CONFORM TO NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) STANDARDS AND <br />SHALL BE UNDERWRITERS' LABORATORIES, INC., (UL) LISTED AND LABELED AND SHALL BE "SPECIFICATION GRADE," <br />MEETING THE REQUIREMENTS OF FEDERAL SPECIFICATION WS-896-E, FOR SWITCHES. <br />1.WALL SWITCHES SHALL BE SPECIFICATION COMMERCIAL GRADE (MINIMUM), FULLY ENCLOSED, QUIET-TYPE TUMBLER <br />SWITCHES RATED 20 AMPERES, 120/277-VOLT, BAKELITE OR COMPOSITION, BACK AND SIDE WIRED, BUMPER PAD, FULL <br />RATING FOR INDUCTIVE OR NON-INDUCTIVE LOADS AND INCANDESCENT OR FLUORESCENT LIGHTING LOADS. <br />2.SINGLE POLE SWITCHES: G.E. 59511, HUBBELL #1221, ARROW #1991 OR PASS & SEYMOUR 20AC1. <br />3.THREE-WAY QUIET SWITCHES: G.E. 59531, HUBBELL #1223, ARROW #1993 OR PASS& SEYMOUR 20AC3. <br />4.WALL SWITCH AND PILOT LIGHTS SHALL BE FLUSH MOUNTED COMBINATION WALL TYPE WITH SWITCH AND PILOT LIGHT <br />EQUIPPED WITH A 6-WATT, 125-VOLT CANDELABRA BASE LAMP. THE PILOT LIGHT SHALL HAVE A GREEN JEWEL WITH <br />BRASS RIM FLUSH MOUNTED IN THE WALL PLATE. <br />5.ALL SWITCHES SHALL BE OF THE SAME MANUFACTURE. <br />6.NORMAL SWITCH COLOR IS WHITE APPROVED BY ARCHITECT/OWNER. SWITCHES CONTROLLING CIRCUITS CONNECTED <br />TO EMERGENCY POWER SOURCE SHALL BE RED. <br />7.30 AMP MOTOR RATED SNAP SWITCHES SHALL BE LEVITON MS302-DS. PROVIDED IN NEMA 1 OR 3R ENCLOSURE AS <br />SHOWN ON DRAWING. <br />B.SENSOR SWITCH (MOTION SENSOR) <br />1.WALL SENSOR SWITCH SHALL BE WATT STOPPER DUAL TECHNOLOGY OCCUPANCY SENSOR LEVITON MODEL <br />#OSSMT-GD (FOR SINGLE POLE SWITCHING) & LEVITON MODEL #OSSMD-GD FOR (DUAL SWITCHING). <br />2.CEILING SENSOR SWITCH SHALL BE WATT STOPPER DUAL-TECHNOLOGY MODE. <br />3.PROVIDE 120/277V CEILING SENSOR POWER PACK INSTALLED IN J-BOX NEXT TO LIGHTING CIRCUIT. <br />2.08 RECEPTACLES (NOT USED) <br />2.09 DEVICE PLATES (NOT USED) <br />2.10 PANELBOARDS (NOT USED). <br />2.11 INTERIOR LIGHTING FIXTURES <br />A.FURNISH, INSTALL AND WIRE LIGHTING FIXTURES SCHEDULED OR INDICATED BY TYPE DESIGNATION ON THE <br />DRAWINGS. IF TYPE DESIGNATION IS OMITTED, FIXTURES SHALL BE OF THE SAME TYPE AS SHOWN FOR ROOMS OF <br />SIMILAR USAGE. VERIFY BEFORE PURCHASE AND INSTALLATION. NO ALTERNATIVE FIXTURES WILL BE ACCEPTED. <br />B.LOCATIONS OF FIXTURES ON ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. VERIFY LOCATION AND SPACING WITH <br />ARCHITECTURAL REFLECTED CEILING PLANS AND OTHER REFERENCE DATA BEFORE PURCHASING. COORDINATE <br />SPACE CONDITIONS, INCLUDING HEADROOM CLEARANCES AND INTERFERENCES WITH CEILING COMPONENTS SUCH <br />AS DUCTS, OPENINGS, BEAMS AND PIPING PRIOR TO INSTALLATION. <br />C.CHECK THE ARCHITECTURAL FINISHES AND, REGARDLESS OF THE CATALOG PREFIXES AND SUFFIXES SHOWN, <br />FURNISH FIXTURES WITH THE PROPER TRIM, FRAMES, SUPPORTS, HANGERS AND OTHER MISCELLANEOUS <br />APPURTENANCES OR PROPERLY COORDINATE WITH SAID FINISHES. WHERE REQUIRED, FURNISH REINFORCING FOR <br />CEILING CONSTRUCTION TO SUPPORT THE WEIGHT OF THE FIXTURES. <br />D.FIXTURES SHALL BE FREE OF LIGHT LEAKS AND DESIGNED TO PROVIDE SUFFICIENT VENTILATION OF LAMPS AND <br />BALLASTS, INCLUDING VENT HOLES WHERE REQUIRED. OUTDOOR FIXTURES WITH VENT HOLES SHALL HAVE WIRE <br />MESH SCREENS IN THE VENT HOLES. <br />E.REPLACE BLEMISHED, DAMAGED OR UNSATISFACTORY FIXTURES AT NO ADDITIONAL COST TO THE OWNER AND IN A <br />MANNER SATISFACTORY TO THE ARCHITECT. <br />F.EXIT SIGNS LIGHTS SHALL BE LED TYPE AND PROVIDED WITH AN INTEGRAL EMERGENCY BATTERY PACK. <br />G.LED LIGHT FIXTURES <br />A.GENERAL: <br />1.LED LIGHT FIXTURES SHALL BE IN ACCORDANCE WITH IES, NFPA, UL, AS SHOWN ON THE DRAWINGS, AND AS <br />SPECIFIED. <br />2.LED LIGHT FIXTURES SHALL BE REDUCTION OF HAZARDOUS SUBSTANCES (ROHS)-COMPLIANT. <br />3.LED DRIVERS SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED: <br />a.MINIMUM EFFICIENCY: 85% AT FULL LOAD. <br />b.MINIMUM OPERATING AMBIENT TEMPERATURE: -20 DEG C. (-4 DEG F.) <br />c.INPUT VOLTAGE: 120 - 277V (±10%) AT 60 HZ. <br />d.INTEGRAL SHORT CIRCUIT, OPEN CIRCUIT, AND OVERLOAD PROTECTION. <br />e.POWER FACTOR: >=0.95. <br />f.TOTAL HARMONIC DISTORTION: <=20%. <br />g.COMPLY WITH FCC 47 CFR PART 15. <br />4.LED MODULES SHALL INCLUDE THE FOLLOWING FEATURES UNLESS OTHERWISE INDICATED: <br />a.COMPLY WITH IES LM-79 AND LM-80 REQUIREMENTS. <br />b.MINIMUM CRI 80 AND COLOR TEMPERATURE 4000K UNLESS OTHERWISE SPECIFIED IN LUMINAIRE SCHEDULE. <br />c.MINIMUM RATED LIFE: 50,000 HOURS PER IES L70. <br />d.LIGHT OUTPUT LUMENS AS INDICATED IN THE LUMINAIRE SCHEDULE. <br />2.12 LOW VOLTAGE SWITCHGEAR (NOT USED) <br />2.13 CIRCUIT AND MOTOR DISCONNECTS (NOT USED) <br />2.14 TRANSFORMERS (NOT USED) <br />2.15 ELECTRICAL CONNECTIONS <br />A.UNLESS OTHERWISE NOTED, ALL WIRING FOR MOTORS, STARTERS, CONTROLS, AND EQUIPMENT SHALL BE PROVIDED <br />BY THE ELECTRICAL CONTRACTOR. WHERE MOTORS FOR MECHANICAL EQUIPMENT ARE FURNISHED BY OTHER <br />DIVISIONS, WIRING SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, EXCEPT WHERE WIRED <br />INTEGRALLY WITH THE EQUIPMENT. <br />B.CONNECTION AND CONTROL DIAGRAMS FOR ALL MECHANICAL AND CONTROL EQUIPMENT SHALL BE FURNISHED <br />UNDER OTHER DIVISIONS, AND BE APPROVED BY THE OWNER FOR CONNECTION BY THE ELECTRICAL CONTRACTOR. <br />2.16 SUPPORTING DEVICES <br />A.ALL EQUIPMENT CONDUITS SHALL BE SUPPORTED, ANCHORED AND BRACED IN ACCORDANCE WITH THE MOST <br />STRINGENT CODES AND REQUIREMENTS. COMPLY WITH CHAPTER 23 OF THE LATEST CBC (CALIFORNIA BUILDING <br />CODE). <br />PART 3 EXECUTION <br />3.01 WORKMANSHIP AND COMPLETION OF INSTALLATION <br />A.WORKMANSHIP AND NEAT APPEARANCE SHALL BE AS IMPORTANT AS THE ELECTRICAL AND MECHANICAL EFFICIENCY. <br />DEFECTIVE AND DAMAGED MATERIALS SHALL BE REPLACED OR REPAIRED PRIOR TO FINAL INTERPRETATIONS <br />INCLUDED. ANY DEFICIENCY PERTAINING TO EITHER WORKMANSHIP OR MATERIALS FOUND BY THE INSPECTOR SHALL <br />BE CORRECTED WITHOUT ADDITIONAL COST TO THE OWNER. <br />B.THE CONTRACTOR SHALL MAINTAIN ON JOB SITE A SET OF THE WORKING DRAWINGS WHICH SHALL BE UPDATED DAILY <br />IN DETAIL FOR WORK ACCOMPLISHED. UPON COMPLETION OF THE WORK, A SET OF REPRODUCIBLE CONTRACT <br />DRAWINGS SHALL BE OBTAINED FROM THE GENERAL CONTRACTOR AND ALL CHANGES AS NOTED ON THE RECORD <br />SET OF PRINTS SHALL BE INCORPORATED THEREON WITH RED INK IN A NEAT, LEGIBLE, UNDERSTANDABLE AND <br />PROFESSIONAL MANNER. <br />C.ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT SHALL BE INSTALLED COMPLETE, THOROUGHLY <br />CLEANED, AND ALL RESIDUE REMOVED FROM INSIDE SURFACES. EXTERIOR SURFACES OF ALL MATERIAL AND <br />EQUIPMENT SHALL BE CLEANED AND DELIVERED IN A PERFECT, UNBLEMISHED CONDITION. <br />D.UPON COMPLETION OF THE INSTALLATION AND AS A CONDITION OF ITS ACCEPTANCE FURNISH ONE COPY OF THE <br />FINAL INSPECTION CERTIFICATE TO THE OWNER. <br />3.02 PREPARATION COORDINATION. <br />A.THE CONTRACTOR SHALL COORDINATE THIS WORK WITH ALL OTHER CONTRACTORS FURNISHING LABOR, MATERIALS <br />AND WORK, SO THAT THE WORK AS WHOLE SHALL BE EXECUTED AND COMPLETED WITHOUT CONFLICT OR DELAY. <br />B.EXAMINE THE DRAWINGS AND SPECIFICATIONS AND DETERMINE THE WORK TO BE PERFORMED BY THE ELECTRICAL, <br />MECHANICAL AND OTHER TRADES. PROVIDE THE TYPE AND AMOUNT OF ELECTRICAL MATERIALS AND EQUIPMENT <br />NECESSARY TO PLACE THIS WORK IN PROPER OPERATION, COMPLETELY WIRED TESTED AND READY FOR USE. THIS <br />SHALL INCLUDE ALL CONDUIT, WIRE, DISCONNECTS, RELAYS, AND OTHER DEVICES FOR THE REQUIRED OPERATION <br />SEQUENCE OF ALL ELECTRICAL, MECHANICAL, AND OTHER SYSTEMS OR EQUIPMENT. <br />C.PERFORM ALL WORK IN A MANNER WHICH WILL NOT CAUSE UNNECESSARY INCONVENIENCE OR DANGER TO THE <br />OCCUPANTS, NOR INTERFERE WITH THE ACTIVITIES IN THE BUILDING. <br />D.THE CONTRACTOR SHALL COORDINATE AND SCHEDULE EACH POWER INTERRUPTION WITH OWNER, AND SHALL <br />PROVIDE AT LEAST TWO WEEKS NOTICE OF PROPOSED INTERRUPTION AND WORK TO BE ACCOMPLISHED. <br />3.03 TRENCHING AND BACKFILLING (NOT USED) <br />3.04 CORE CUTTING, DRILLING, AND PATCHING (NOT USED) <br />3.05 INSTALLATION <br />A.WORKMANSHIP IS TO BE NEAT, BY EXPERIENCED WORKMEN WITH ADEQUATE SUPERVISION, AND IN LINE WITH <br />NORMAL INDUSTRY WORK PRACTICES. <br />B.MAINTAIN WORKING CLEARANCE AROUND ELECTRICAL EQUIPMENT, IN ACCORDANCE WITH CODE REQUIREMENTS AS A <br />MINIMUM. <br />C.WHERE LIGHTING FIXTURES AND OTHER ELECTRICAL ITEMS ARE SHOWN IN CONFLICT WITH LOCATIONS OF <br />STRUCTURAL MEMBERS AND MECHANICAL OR OTHER EQUIPMENT, FURNISH AND INSTALL ALL REQUIRED SUPPORTS <br />AND WIRING TO CLEAR THE ENCROACHMENT. <br />D.VERIFY LOCATION OF EACH OUTLET FOR POWER, SIGNAL, TELEPHONE/DATA, AND EACH LIGHTING FIXTURE WITH <br />ARCHITECT PRIOR TO ROUGH-IN. INCLUDE IN BID COST OF RELOCATING EACH ITEM WITHIN TEN-FEET RADIUS OF ITS <br />INDICATED LOCATION. <br />E.ALL CONDUIT TO BE RUN CONCEALED UNLESS OTHERWISE NOTED. ALL CONDUITS SHALL BE ROUTED OVERHEAD IN <br />CEILING SPACES. NO CONDUITS SHALL BE PERMITTED IN CONCRETE SLAB, MASONRY WALLS UNLESS SPECIFICALLY <br />SO INDICATED. CONDUIT SHALL BE RUN SO AS NOT TO INTERFERE WITH OTHER PIPING FIXTURES OR EQUIPMENT. <br />F.WHERE ALLOWED, EXPOSED CONDUIT RUNS SHALL BE INSTALLED PARALLEL OR PERPENDICULAR TO WALLS, <br />STRUCTURAL MEMBERS, OR INTERSECTION OF VERTICAL PLANES AND CEILINGS. <br />G.ALL ELECTRICAL CONDUITS AND OTHER ELECTRICAL RACEWAYS PASSING THROUGH FIRE RATED CEILINGS, SLABS, <br />CABLE TRAYS, WALLS AND PARTITIONS SHALL BE SEALED TO PREVENT THE SPREAD OF FIRE, SMOKE, AND GASSES. <br />USE A UL LISTED AND APPROVED FIRE-STOP MATERIAL EQUAL TO RATING OF A WALL OR A FLOOR SLAB PENETRATED; <br />INSTALLATION OF FIRE-STOP MATERIAL SHALL BE IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. <br />H.UNLESS WRITTEN PERMISSION IS GRANTED BY THE ARCHITECT, NO MATERIAL SHALL BE MOUNTED ON THE EXTERIOR <br />WALLS OR PARAPET TOP OF THE BUILDING. <br />I.ALL ROTATING ELECTRICAL EQUIPMENT SHALL BE SUPPLIED WITH A FLEXIBLE, LIQUID-TIGHT CONDUIT WITH <br />APPROPRIATE SLACK AND SHALL NOT EXCEED THIRTY-SIX (36) INCHES. <br />J.ALL POWER WIRING SHALL BE INSTALLED IN CONDUIT. <br />K.TELEPHONE WIRES SHALL BE PLENUM RATED CABLE FOR MOUNTING IN CEILING SPACES WITHOUT CONDUIT UNLESS <br />OTHERWISE NOTED. <br />L.ALL WIRES FOR ALL SYSTEMS SHALL BE CONTINUOUS FROM SWITCH TO TERMINAL OR FURTHEST OUTLET. NO JOINTS <br />SHALL BE MADE EXCEPT IN PULL, JUNCTION OR OUTLET BOXES, OR IN PANEL OR SWITCHBOARD GUTTERS. <br />M.ALL RECEPTACLE, CONTROL DEVICE, AND SWITCH MOUNTING HEIGHTS SHALL BE COORDINATED WITH <br />ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN. <br />3.06 GROUNDING <br />A.EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH CODE SIZE GREEN GROUND, EQUIPMENT WIRE (PER NEC 250-95) <br />(NOT INDICATED ON DRAWINGS) WITHIN THE SAME CONDUIT FOR ALL CIRCUITS OF PANELBOARDS. <br />3.07 BRANCH CIRCUITS <br />A.NO MORE THAN THREE BRANCH CIRCUITS PERMITTED IN ONE CONDUIT UNLESS INDICATED OTHERWISE <br />3.08 IDENTIFICATION (NOT USED) <br />3.09 PROTECTION <br />A.USE ALL MEANS NECESSARY TO PROTECT THE WORK AND MATERIALS FROM LOSS DURING AND AFTER INSTALLATION, <br />AND PROVIDE ADEQUATE AND PROPER STORAGE FACILITIES DURING THE PROGRESS OF THE WORK. PROVIDE FOR <br />THE SAFETY AND GOOD CONDITION OF ALL WORK UNTIL FINAL ACCEPTANCE OF THE WORK BY THE OWNER. REPLACE <br />ALL DAMAGE OR DEFECTIVE WORK, MATERIAL, AND EQUIPMENT AT NO EXPENSE TO THE OWNER BEFORE <br />REQUESTING FINAL ACCEPTANCE. <br />3.10 CLEANING OF EQUIPMENT, MATERIAL, AND PREMISES <br />A.SITE SHALL BE LEFT BROOM CLEAN AFTER COMPLETION OF WORK EACH DAY. UPON COMPLETION OF THE WORK, <br />LEAVE THE PREMISES CLEAN OF ALL DIRT AND DEBRIS. <br />B.ALL EQUIPMENT AND MATERIAL CONNECTED WITH THIS PROJECT SHALL BE INSTALLED COMPLETE, THOROUGHLY <br />CLEANED, AND ALL RESIDUE REMOVED FROM INSIDE SURFACES. EXTERIOR SURFACES OF ALL MATERIAL AND <br />EQUIPMENT SHALL BE CLEANED AND DELIVERED IN A PERFECT, UNBLEMISHED CONDITION. <br />3.11 HANDLING OF WIRE AND CABLE <br />A.HANDLE WIRE AND CABLE SO AS TO AVOID DAMAGE TO CONDUCTORS AND TAKE EVERY PRECAUTION TO AVOID SHARP <br />BENDING OR SCORING OF THE CABLE. CABLE SHALL NOT BE LAID NOR DRAGGED UPON THE GROUND. <br />B.THE CONTRACTOR SHALL BE REQUIRED TO REMOVE AND REPLACE AT HIS OWN EXPENSE ALL WIRE AND CABLE <br />DAMAGED DUE TO IMPROPER HANDLING, AND SHALL PAY FOR THE NEW WIRE OR CABLE. <br />3.12 TESTING AND INSPECTIONS <br />A.THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND ARRANGE ALL REQUIRED INSPECTIONS <br />FOR THE EXECUTION OF THE WORK UNDER THIS CONTRACT. <br />B.THE CONTRACTOR SHALL REPLACE ALL DAMAGED OR DEFECTIVE EQUIPMENT OR WORK. <br />C.ALL CIRCUITS SHALL BE TESTED FOR CONTINUITY AND CIRCUIT INTEGRITY BY THE CONTRACTOR. ADJUSTMENTS <br />SHALL BE MADE FOR CIRCUITS NOT COMPLYING WITH TESTING CRITERIA. <br />D.THE CONTRACTOR SHALL FURNISH ALL INSTRUMENTS AND PERFORM ANY ADDITIONAL TESTS REQUIRED BY THE <br />AUTHORITY HAVING JURISDICTION. CONTRACTOR SHALL ALSO CORRECT ALL FAILURES AND REPLACE ANY DAMAGED <br />PORTIONS OF THE WORK RESULTING FROM THOSE TESTS. THE COST OF THE FOREGOING ITEMS SHALL BE PAID BY <br />THE CONTRACTOR. <br />E.THE CONTRACTOR SHALL FURNISH THE OWNER CERTIFICATES OF INSPECTION AND APPROVAL BY THE ELECTRICAL <br />INSPECTION AUTHORITY ON ALL WORK COMPETED AS REQUIRED. <br />F.CONTRACT DRAWINGS AND SPECIFICATIONS, GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND <br />SUPPLEMENTARY CONDITIONS, ELECTRICAL PROVISIONS AND DIVISION-1 SPECIFICATION SECTIONS APPLY TO WORK <br />OF THIS SECTION. <br />PROJECT TITLE <br />DESIGNED BY <br />DRAWN BY <br />CHECKED BY <br />DATE <br />SCALE <br />JOB NO. <br />SHEET NO. <br />DATE BY ISSUE FOR <br />RM <br />OP <br />BK <br />08.07.24 <br />24-212 <br />ISSUE DATE: <br />REVISION: <br />NUM.DATE BY REVISION FOR <br />1 <br />2 <br />3 <br />4 <br />5 <br />7 <br />CONSULTANT <br />PR <br />O <br />J <br />E <br />C <br />T <br /> <br />F <br />O <br />R <br />: <br />STAMP <br />6 <br />SHEET TITLE <br />50 <br />0 <br /> <br />W <br />. <br /> <br />W <br />A <br />R <br />N <br />E <br />R <br /> <br />A <br />V <br />E <br />. <br /> <br />S <br />U <br />I <br />T <br />E <br /> <br />2 <br />0 <br />0 <br />Sa <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />7 <br />AS NOTED <br />BU <br />I <br />L <br />D <br />E <br />R <br />S <br /> <br />S <br />U <br />R <br />P <br />L <br />U <br />S <br />R: <br />\ <br />_ <br />P <br />R <br />O <br />J <br />E <br />C <br />T <br />\ <br />2 <br />0 <br />2 <br />4 <br />\ <br />2 <br />4 <br />- <br />2 <br />1 <br />2 <br /> <br />B <br />U <br />I <br />L <br />D <br />E <br />R <br />S <br /> <br />S <br />U <br />R <br />P <br />L <br />U <br />S <br />\ <br />_ <br />C <br />A <br />D <br />\ <br />2 <br />4 <br />- <br />2 <br />1 <br />2 <br /> <br />E <br />- <br />S <br />P <br />E <br />C <br />S <br /> - <br /> <br />20 <br />2 <br />4 <br />- <br />1 <br />1 <br />- <br />2 <br />1 <br /> - <br /> <br />RO <br />Y <br /> <br />M <br />O <br />R <br />A <br />L <br />E <br />S <br />San Bernardino, CA 92408 <br />412 E. Vanderbilt Way Phone: 909.890.3700 <br />Fax: 909.890.3770 <br />Email: cadd@designwesteng.com <br />DESIGN WEST ENGINEERING <br />MECHANICAL ELECTRICAL ENERGY CONSULTANTS <br />ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS <br />ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED <br />TO BE USED IN CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL <br />NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE <br />WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR <br />DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYING SPECIFICATIONS <br />WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. <br />ELECTRICAL <br />SPECIFICATIONS <br />E-3.1 <br />SIGNED:11/21/2024 <br />500 W Warner Ave <br />Unit B5/6/2025