Wind Load Cont. <br />1.0 ASCE 7-16 Sec 26.8.2 <br />0.57 ASCE 7-16 Table 26.10-1 <br />0.85 ASCE 7-16 Table 26.6-1 <br />1.00 ASCE 7-16 Table 26.9-1 <br />11.18 psf <br />23.0 Degrees <br />1.5 Conservatively assuming all exposed <br />0.8 conservatively assuming 10 ft2 effective area <br />Uplift (W)Zone(1,2e) Zone(2r, 2n) Zone(3e)Zone(3r) <br />Fig. 30-3-2 GCp=-1.3 -1.7 -1.7 -1.8 <br />Eq. 29.4-7 P=qh(GCp)(γE)(γa)=-17.44 -22.81 -22.81 -24.15 <br />GCp=0.6 Figure 30.3-2 <br />P=qh(GCp)(γE)(γa)=4.43 Equation 29.4-7 <br />Rafter Attachments: 0.6D+0.6W (CD=1.6) <br />Connection Check <br />Attachment max. spacing=4 ft <br />5/16" Lag Screw Withdrawal Value=266 lbs/in Table 12.2A - NDS <br />2.5 in DFL Assumed <br />Prying Coefficient 1.4 <br />Allowable Capacity= 760 lbs <br />Zone Trib Width Area (ft) Uplift (lbs) Down (lbs) <br />Zone(1,2e)4 11.0 74.2 81.7 <br />Zone(2r, 2n)4 11.0 93.7 81.7 <br />Zone(3e)4 11.0 93.7 81.7 <br />Zone(3r)4 11.0 98.5 81.7 <br />Conservative Max=98.5 <760 <br />CONNECTION IS OK <br />Risk Category = <br />KZ = <br />Kd = <br />Ke = <br />2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw. <br />Embedment in sheading or other material does not count. <br />II <br />V= <br />Exposure = <br />1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift <br />governs <br />γE= <br />γa= <br /> KZt = <br />qh= 0.00256KzKztKdKeV2= <br />Pitch = <br />Lag Screw Penetration <br />projects@evengineersnet.com <br />http://www.evengineersnet.com <br />Signed: 09/18/2024 <br />Exp: 06/30/2026 <br />3902 S Alder St <br />4/30/2025