Laserfiche WebLink
08/06/2024 <br />RE: Structural Certification for Installation of Residential Solar <br /> MARIA PAZ:3040 BRADFORD PL B, SANTA ANA, CA 92707 <br />Attn: To Whom It May Concern <br />Design Criteria <br />Code 2022 California Building Code (ASCE 7-16) <br />Risk category II Wind Load (component and Cladding) <br />Roof Dead Load Dr 10 psf V 95 mph <br />PV Dead Load DPV 3 psf Exposure B <br />Roof Live Load Lr 20 psf <br />This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the PV <br />system to existing roof framing. From the field observation report, the roof is made of Composition shingle <br />roofing over roof plywood supported by 2X8 Rafters at 16 inches. The slope of the roof was approximated to be 2 <br />degrees. <br /> the existing roof <br />framing has been determined to be adequate to support the imposed loads without structural upgrades. <br />Contractor shall verify that existing framing is consistent with the described above before install. Should they find <br />any discrepancies, a written approval from SEOR is mandatory before proceeding with install. Capacity <br />calculations were done in accordance with applicable building codes. <br />projects@evengineersnet.com <br />http://www.evengineersnet.com <br />3040 S Bradford Pl Unit# <br />B9/5/2024