Fruit Street <br />SHEET INDEX <br />SHEET DESCRIPTION REVISIONS <br />S-1 COVER SHEET/GENERAL NOTES <br />S-2 FOUNDATION PLAN <br />S-3 ROOF FRAMING PLAN <br />SD1 STANDARD DETAILS <br />SD2 FOUNDATION & ROOF FRAMING DETAILS <br />GENERAL NOTES <br />1.THE STRUCTURES DEPICTED HEREIN HAVE BEEN DESIGNED PER THE 2022 CALIFORNIA BUILDING CODE PRIMARILY TO SAFEGUARD <br />AGAINST MAJOR STRUCTURAL DAMAGE AND LOSS OF LIFE, NOT NECESSARILY TO LIMIT DAMAGE OR MAINTAIN FUNCTION. <br />2.THESE DRAWINGS HAVE BEEN PREPARED USING STANDARDS OF PROFESSIONAL CARE AND COMPLETENESS NORMALLY EXERCISED <br />UNDER SIMILAR CIRCUMSTANCES BY REPUTABLE STRUCTURAL ENGINEERS IN THIS OR SIMILAR LOCALITIES. THESE DRAWINGS <br />ASSUME THAT THE WORK DEPICTED WILL BE PERFORMED BY AN EXPERIENCED CONTRACTOR AND OR WORKMEN WHO HAVE A <br />WORKING KNOWLEDGE OF THE APPLICABLE CODE STANDARDS AND REQUIREMENTS AND OF INDUSTRY ACCEPTED STANDARD GOOD <br />PRACTICE. AS NOT EVERY CONDITION OR ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN ON THESE DRAWINGS, IT IS UNDERSTOOD <br />THAT THE CONTRACTOR WILL USE INDUSTRY ACCEPTED STANDARD GOOD PRACTICE FOR ALL MISCELLANEOUS WORK NOT <br />EXPLICITLY SHOWN ON THE DRAWINGS. <br />3.CALCULATIONS AND DESIGN OF MISCELLANEOUS NON-STRUCTURAL ITEMS, SUCH AS STAIRS, RAILINGS, NON-STRUCTURAL WALLS <br />AND PREFABRICATED STRUCTURAL ITEMS, FOR EXAMPLE, FLOOR AND ROOF TRUSSES, ARE NOT INCLUDED AND ARE TO BE <br />PROVIDED BY OTHERS UNLESS SPECIFICALLY NOTED ON THESE DRAWINGS. <br />4.THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE <br />CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES. <br />IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DESIGN AND PROVIDE ADEQUATE SHORING, BRACING, FORMWORK, ETC... AS <br />REQUIRED FOR THE PROTECTION OF LIFE AND PROPERTY DURING CONSTRUCTION. CONSTRUCTION MATERIALS STACKED ON FLOOR <br />OR ROOF FRAMING SHALL BE UNIFORMLY SPREAD OUT SUCH THAT DESIGN LIVE LOAD PER SQUARE FOOT AS STATED HEREIN IS <br />NOT EXCEEDED. VISITS TO THE SITE BY THE STRUCTURAL ENGINEER SHALL NOT BE CONSIDERED AN INSPECTION, BUT AS A <br />RESOURCE FOR THE CONTRACTOR. <br />5.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXCAVATION PROCEDURES INCLUDING SHORING AND PROTECTION OF <br />ADJACENT PROPERTY, STRUCTURES, STREETS AND UTILITIES IN ACCORDANCE WITH THE LOCAL BUILDING CODES, REGULATIONS <br />AND SAFETY REQUIREMENTS. <br />6.THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL DIMENSIONS, CONDITIONS AND ELEVATIONS WITH <br />ARCHITECTURAL DRAWINGS PRIOR TO START OF CONSTRUCTION. THE CONTRACTOR SHALL INFORM THE ARCHITECT IN WRITING <br />OF ANY DISCREPANCIES OR OMISSIONS NOTED ON THE DRAWINGS. ANY SUCH DISCREPANCY, OMISSION, OR VARIATION NOT <br />REPORTED BEFORE START OF CONSTRUCTION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. WHERE DISCREPANCIES <br />OCCUR IN THESE DRAWINGS, NOTES AND DETAILS ON DRAWINGS TAKE PRECEDENCE OVER GENERAL STRUCTURAL NOTES AND <br />TYPICAL DETAILS. <br />7.IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN DOCUMENTED ENGINEER'S APPROVAL AND BUILDING DEPARTMENT <br />APPROVAL FOR STRUCTURAL REVISIONS PRIOR TO CONSTRUCTION OF SAID REVISIONS. THE ENGINEER OF RECORD ASSUMES NO <br />LIABILITY FOR DAMAGES INCURRED BY THE CONTRACTOR OR CLIENT DUE TO UNAPPROVED STRUCTURAL ALTERATIONS. <br />8.ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE 2022 CALIFORNIA BUILDING CODE AND ANY OTHER REGULATORY <br />AGENCIES WHICH HAVE AUTHORITY OVER ANY PORTION OF THE WORK, AND THOSE CODES AND STANDARDS LISTED IN THESE <br />NOTES AND SPECIFICATIONS. <br />9.OPENINGS, POCKETS, ETC... LARGER THAN 6 INCHES SHALL NOT BE PLACED IN SLABS, DECKS, BEAMS, JOISTS, COLUMNS WALLS, <br />ETC., UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS. NOTIFY THE STRUCTURAL ENGINEER WHEN DRAWINGS <br />BY OTHERS SHOW OPENINGS, POCKETS, ETC., NOT SHOWN ON THE STRUCTURAL DRAWINGS, BUT WHICH ARE LOCATED ON <br />STRUCTURAL MEMBERS SPECIFIED ON THE APPROVED STRUCTURAL DRAWINGS. <br />10.ASTM SPECIFICATIONS NOTED ON THESE CONSTRUCTION DOCUMENTS SHALL BE THE LATEST ACCEPTED VERSION. <br />FOUNDATION <br />1.THIS FOUNDATION IS DESIGNED PER THE 2022 CALIFORNIA BUILDING CODE MINIMUM REQUIREMENTS. A SOILS INVESTIGATION BY <br />A QUALIFIED GEOTECHNICAL ENGINEER IS RECOMMENDED TO DETERMINE THE SITE SOIL'S DESIGN CHARACTERISTICS. NGW DOES <br />NOT ASSUME LIABILITY FOR STRUCTURAL DAMAGE DUE TO SOIL RELATED PROBLEMS WHICH COULD BE MITIGATED PER THE <br />RECOMMENDATIONS OF A QUALIFIED GEOTECHNICAL ENGINEER. <br />2.IF THE SOIL IS FOUND TO HAVE AN EXPANSION INDEX GREATER THAN 20, THE FOUNDATION SYSTEM SHALL BE DESIGNED PER <br />SECTION 1808.6 OF THE 2022 CBC. <br />3.ALL FOOTINGS SHALL EXTEND 12 INCHES MINIMUM BELOW GRADE. GRADE IS DEFINED AS TOP OF SLAB FOR INTERIOR FOOTINGS, <br />LOWEST ADJACENT COMPACTED SUBGRADE (BUILDING PAD PRIOR TO PLACEMENT OF LANDSCAPE) OR NATURAL GRADE WITHIN 10 <br />FEET OF BUILDING PERIMETER FOOTINGS. FOOTING EXCAVATIONS SHALL BE CLEAN AND FREE FROM LOOSE DEBRIS, STANDING <br />WATER, OR UNCOMPACTED MATERIAL AT THE TIME OF CONCRETE PLACEMENT. <br />4.ALLOWABLE DEAD PLUS LIVE LOAD SOIL PRESSURE = 1,500 PSF (U.N.O.). <br />5.BACKFILL AGAINST FOUNDATION WALLS OR EXTERIOR WALLS BELOW GRADE SHALL NOT BE PLACED UNTIL AFTER THE TOP OF <br />THE WALLS IS RESTRAINED BY THE COMPLETED INTERIOR FLOOR SYSTEMS AND ALL ELEMENTS HAVE REACHED THEIR DESIGN <br />STRENGTH. <br />6.TRENCHES AND EXCAVATIONS UNDER OR ADJACENT TO FOUNDATIONS SHALL BE PROPERLY BACKFILLED AND COMPACTED. <br />CONCRETE <br />1.FOUNDATIONS DESIGNED PER THE 2022 CALIFORNIA BUILDING CODE MINIMUM REQUIREMENTS, HAVE BEEN DESIGNED BASED UPON <br />A 28-DAY MINIMUM F'c = 2,500 PSI FOR ALL CONCRETE IN CONTACT WITH THE SOIL THEREFORE SPECIAL INSPECTION WILL NOT <br />BE REQUIRED. WHERE REQUIRED BY THE GOVERNING BUILDING ENTITY, A GEOTECHNICAL ENGINEER SHALL PROVIDE THE <br />LOCATION OF ON-SITE SOILS CLASSIFIED AS MODERATE, SEVERE OR VERY SEVERE SULPHATE EXPOSURE. THE CONCRETE DESIGN <br />FOR SULFATE (SO4) EXPOSURE AS DETERMINED PER ASTM D516 OR D4130 SHALL CONFORM WITH ACI 318-14, SECTION 19.3: <br />EXPOSURE CLASS % SO4 BY MASS MAX WATER : CEMENT MIN F'c AT 28 DAYS CEMENT TYPE CALCIUM CHLORIDE <br />S1 0.1 < SO4 < 0.2 0.50 4,000 psi II NO RESTRICTION <br />S2 0.2 < SO4 < 2.0 0.45 4,500 psi V NOT PERMITTED <br />S3 2.0 < SO4 0.45 4,500 psi V NOT PERMITTED <br />THE CONTRACTOR SHALL SAVE ALL BATCH RECEIPTS FOR BUILDING DEPARTMENT REVIEW. <br />2.ALL CONCRETE SHALL BE NORMAL WEIGHT OF 145 POUNDS PER CUBIC FOOT USING HARDROCK AGGREGATES. <br />3.WATER SHALL BE CLEAN AND POTABLE. UNLESS WATER REDUCERS ADDED, THE MAX. SLUMP SHALL BE 5" <br />4.PORTLAND CEMENT SHALL CONFORM TO ACI 318-14. TYPE V CEMENT SHALL BE USED FOR CONCRETE IN CONTACT WITH THE SOIL <br />CATEGORIZED AS MODERATE TO SEVERE SULPHATE EXPOSURE. CEMENT SHALL BE TYPE V WITH POZZOLAN WHERE CONCRETE IS <br />IN CONTACT WITH SOIL CATEGORIZED AS VERY SEVERE SULFATE EXPOSURE. TYPE II CEMENT MAY BE USED ELSEWHERE. <br />5.CONCRETE MIXES SHALL BE DESIGNED BY A CERTIFIED LABORATORY. MIX DESIGNS FOR CONCRETE SLABS SHALL BE <br />PROPORTIONED SO AS TO MINIMIZE SHRINKAGE. <br />6.FLY ASH SHALL COMPLY WITH ASTM C-618, AND SHALL BE APPROVED BY THE ARCHITECT PRIOR TO BEING USED ON A PROJECT. <br />7.ALL ITEMS TO BE CAST IN CONCRETE SUCH AS REINFORCING, DOWELS, BOLTS, ANCHORS, SLEEVES, ETC. SHALL BE SECURELY <br />POSITIONED IN THE FORMS PRIOR TO PLACEMENT OF THE CONCRETE. <br />8.CONCRETE MIXING, PLACEMENT AND QUALITY SHALL BE PER ACI 318-14. MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED. <br />SLABS ON GRADE NEED BE VIBRATED ONLY AROUND AND UNDER FLOOR DUCTS OR SIMILAR ELEMENTS. REMOVE ALL DEBRIS <br />FROM FORMS BEFORE PLACING CONCRETE. CONCRETE SHALL NOT BE DROPPED THROUGH REINFORCING STEEL SO AS TO NOT <br />CAUSE SEGREGATION OF AGGREGATES. UNCONFINED FALL OF CONCRETE SHALL NOT EXCEED FIVE FEET. <br />9.CONCRETE SLAB ON GRADE CONTROL JOINTS SHOULD BE SPACED A MAXIMUM OF 30 x THE SLAB THICKNESS AND SHOULD OCCUR <br />AT ANY ABRUPT CHANGES IN WIDTH, DEPTH, OR CHANGE IN SLOPE. CONTROL JOINTS SHOULD BE 1/3 THE DEPTH OF SLAB AND <br />MAY BE TOOLED AT TIME OF FINISHING OR SAW CUT AS SOON AS POSSIBLE TO PREVENT IRREGULAR SHRINKAGE CRACKS. KEYED <br />OR DOWELED CONTROL JOINTS NEED ONLY OCCUR AT EXPANSION JOINTS OR COLD JOINTS WHERE CONTINUOUS REINFORCEMENT <br />DOES NOT OCCUR. POST-TENSIONED CONCRETE SLABS ON GRADE SHALL NOT HAVE CONTROL JOINTS UNLESS SPECIFICALLY <br />SPECIFIED ON THE PLANS. <br />10.PROTECT CONCRETE FROM DAMAGE OR REDUCED STRENGTH DUE TO COLD OR HOT WEATHER IN ACCORDANCE WITH ACI 305 AND <br />306. CONTRACTOR SHALL TAKE SPECIAL CURING PRECAUTIONS TO MINIMIZE SHRINKAGE CRACKING OF CONCRETE SLABS. <br />11.CONSTRUCTION JOINTS OR POUR JOINTS IN STRUCTURAL ELEMENTS (BEAMS, COLUMNS, ELEVATED SLABS, ETC.) NOT <br />SPECIFICALLY SHOWN OR NOTED ON THE DRAWINGS REQUIRE PRIOR APPROVAL OF THE ENGINEER. CONTRACTOR SHALL SUBMIT <br />SHOP DRAWINGS SHOWING PROPOSED JOINTS TO ENGINEER FOR APPROVAL. <br />12.PIPES AND ELECTRICAL CONDUITS SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE EXCEPT WHERE SPECIFICALLY APPROVED <br />BY THE ENGINEER. EMBEDDED ITEMS SHALL NOT IMPAIR THE STRENGTH OF THE MEMBER. <br />CONNECTION HARDWARE <br />1.UNLESS NOTED OTHERWISE, ALL HANGERS, CLIPS, STRAPS, HOLD-DOWNS, MISC. STRUCTURAL CONNECTORS, ETC. SHOWN ON <br />PLANS OR DETAILS SHALL BE SIMPSON STRONG-TIE OR EQUAL. SEE SIMPSON CATALOG, SHEET 12 FOR THE CODE REFERENCE KEY <br />CHART. EQUIVALENT ALTERNATIVES MAY BE USED PROVIDED THEY HAVE EQUIVALENT CAPACITY FOR THE INTENDED APPLICATION <br />AND A CURRENT ICC APPROVAL. <br />2.ALL HARDWARE SHALL BE INSTALLED WITH FASTENERS PER MFR'S SPECIFICATIONS. ALL HANGERS SHALL BE INSTALLED WITH <br />MAXIMUM NUMBER OF FASTENERS REQUIRED PER MFR'S SPECIFICATIONS UNLESS SPECIFIED OTHERWISE. <br />3.FASTENERS INSTALLED ON PRESERVATIVE-TREATED, FIRE-RETARDANT-TREATED WOOD OR HARDWARE EXPOSED TO WEATHER <br />SHALL BE OF HOT DIPPED ZINC-COATED GALVANIZED STEEL, STAINLESS STEEL, SILICON BRONZE, OR COPPER PER CBC 2304.10.5.1. <br />OR RBC R317.3. COATING WEIGHTS FOR ZINC-COATED FASTENERS SHALL BE IN ACCORDANCE WITH ASTM A 153. <br />4.HOLD-DOWN HARDWARE BOLTED CONNECTIONS SHALL BE RE-TIGHTENED JUST PRIOR TO COVERING FRAMING. <br />5.INTERIOR NON-BEARING, NON-SHEAR WALLS ON CONCRETE SLAB ON GRADE SHALL BE ATTACHED TO THE SLAB WITH <br />GALVANIZED 0.145"Ø X 3" POWDER ACTUATED SHOT PIN w/ 1"Ø WASHER AT 32" O.C., 6" TO 10" FROM EA END OF <br />EACH SEGMENT. USE SIMPSON PDPWL-300MG SHOT PIN PER ICC REPORT ESR-2138 (AND LADBS RR 25469 OR <br />EQUIV. FASTENER APPROVED BY THE ICC AND LADBS RATED FOR PRESSURE TREATED WOOD. <br />6.FOR ALL LAG SCREW INSTALLATIONS IN FRAMING LUMBER (SPECIFIC DENSITY "G" LESS THAN OR EQUAL TO 0.5), PROVIDE A LEAD <br />HOLE OF DIA. BETWEEN 40% AND 70% OF THE THREADED SHANK DIA. TO THE DEPTH OF EMBEDMENT (60% TO 75% FOR <br />0.5<G<0.6, 65% TO 85% FOR G>0.6). A LEAD HOLE IS NOT REQUIRED FOR 3/8" DIA. SCREWS AND SMALLER. USE HIGHER <br />PERCENTAGE FOR LARGER DIA. SCREWS. PROVIDE A LEAD HOLE OF EQUAL DIA. OF AND TO THE SAME DEPTH AS THE <br />UNTHREADED PORTION OF THE SHANK. (SEE NDS 2015) <br />7.ALL HOLES FOR THROUGH BOLTS SHALL BE OF 1/32 TO 1/16" GREATER DIA. THAT BOLT SHANK. <br />REINFORCING STEEL <br />1.REINFORCING STEEL SHALL CONFORM TO REQUIREMENTS OF ASTM A615. REINFORCING SHALL BE GRADE 60 (Fy = 60 KSI) <br />DEFORMED BARS FOR ALL BARS #5 AND LARGER AND ALL BARS USED FOR CONCRETE WALLS, BEAMS ELEVATED SLABS AND <br />COLUMN PRIMARY REINFORCING. REINFORCING MAY BE GRADE 40 (Fy = 40 KSI) DEFORMED BARS FOR ALL BARS #4 AND SMALLER <br />U.N.O. ON PLANS OR DETAILS. ALL REINFORCING TO BE WELDED SHALL BE ASTM A706, GRADE 60 LOW ALLOY WELDABLE STEEL. <br />2.ALL DIMENSIONS SHOWING THE LOCATION OF REINFORCING STEEL NOT NOTED AS "CLEAR" OR "CLR" ARE TO CENTER OF STEEL. <br />MINIMUM, COVER FOR NON-PRESTRESSED CONCRETE REINFORCING SHALL BE AS FOLLOWS: (U.N.O. ON THESE PLANS OR PLAN <br />DETAILS) <br />EXPOSURE REBAR SIZE MIN. COVER TOLERANCE <br />CAST AGAINST EARTH ALL 3" 3/8" <br />EXPOSED TO EARTH OR WEATHER:#5 & SMALLER 1 1/2" 3/8" <br />#6 & LARGER 2" 3/8" <br />NOT EXPOSED TO WEATHER: <br />ROOF SLABS ALL 1" 1/8" <br />STRUCT.SLABS & WALLS ALL 3/4" 1/8" <br />BEAMS & COLUMNS ALL 1 1/2" 3/8" <br />SLAB ON GRADE ALL 1 1/2" 1/4" <br />3.LAP SPLICES OF REINFORCING STEEL IN CONCRETE BEAMS, SLABS AND FOOTINGS SHALL BE ACCORDING TO ACI 318-14, SEC. 25.5 <br />OR LAP SCHEDULE WHERE PRESENT, U.N.O.. STAGGER SPLICES A MINIMUM OF ONE LAP LENGTH. NO TACK WELDING OF <br />REINFORCING BARS ALLOWED. LATEST ACI CODE AND DETAILING MANUAL APPLY. PROVIDE BENT CORNER BARS TO MATCH AND <br />LAP WITH HORIZONTAL BARS AT ALL CORNERS AND INTERSECTIONS PER TYPICAL DETAILS. VERTICAL WALL BARS SHALL BE <br />SPLICED AT OR NEAR FLOOR LINES. SPLICE TOP BARS AT CENTER LINE OF SPAN AND BOTTOM BARS AT THE SUPPORT IN <br />SPANDRELS, BEAMS, GRADE BEAMS, ETC. U.N.O. ON THE PLANS. <br />4.ALL REINFORCING SHALL BE BENT COLD, ONE TIME ONLY. FIELD BENDING OF REBAR SHALL NOT BE ALLOWED UNLESS <br />SPECIFICALLY NOTED ON THE PLANS. <br />5.REINFORCING BAR SPACING SHOWN ON PLANS REPRESENT THE MAXIMUM ON CENTER SPACING. ALL BARS SHALL BE DETAILED <br />AND PLACED PER CRSI SPECIFICATIONS AND HANDBOOK. DOWEL ALL VERTICAL REINFORCING TO FOUNDATION, AS SPECIFIED ON <br />PLANS OR DETAILS. MINIMUM CLEAR SPACING BETWEEN PARALLEL REINFORCEMENT SHALL BE THE LARGER OF 1 1/2 TIMES <br />NOMINAL BAR DIAMETER, 1 1/3 TIMES MAXIMUM AGGREGATE SIZE OR 1 1/2". <br />6.EPOXY GROUTED REBAR ANCHORAGE SHALL BE SPECIFICALLY DETAILED. REBARS SHALL BE INSTALLED WITH EPOXY ADHESIVE <br />APPROVED FOR CRACKED CONCRETE (SIMPSON SET-3G EPOXY PER ICC-ESR 4057, HILTI HIT-RE500 EPOXY PER ICC-ESR 2322). THE <br />EPOXY GROUTED BARS SHALL BE INSTALLED PER MANUFACTURERS SPECIFICATIONS AND ICBO/ESR REPORT REQUIREMENTS. <br />ALTERNATE ICC APPROVED EPOXY APPROVED FOR WIND AND SEISMIC TENSION LOADS IN CRACKED CONCRETE MAY BE USED, WITH <br />WRITTEN APPROVAL FROM THE ENGINEER. <br />7.ALL EPOXY REBAR INSTALLATIONS REQUIRE SPECIAL INSPECTION. <br />ANCHOR BOLTS <br />1.SILL PLATE ANCHORAGE AT CONCRETE OR MASONRY SHALL BE 5/8" DIAMETER EMBEDDED ANCHOR BOLTS w/ 3X3X.229" SQ. <br />PLATE WASHER. SILL PLATE ANCHOR BOLTS SHALL BE EMBEDDED 7 INCHES MINIMUM INTO THE CONCRETE. HOLD-DOWN <br />ANCHORS SHALL NOT BE CONSIDERED AS PART OF THE REQUIRED SILL PLATE ANCHOR BOLTS AS SPECIFIED IN THE SHEARWALL <br />SCHEDULE OR GSN (MIN). INTERIOR WALLS MAY BE ANCHORED TO THE CONCRETE WITH, EMBEDDED ANCHOR BOLTS, EXPANSION <br />ANCHORS OR POWDER DRIVEN FASTENERS AS SPECIFIED BELOW, U.N.O. SPECIFICALLY ON THE PLANS. <br />2.SHEARWALL ANCHOR SPACING SHALL BE PER THE ANCHOR BOLT SCHEDULE FOR THE SPECIFIED SHEAR TYPE ON PLAN. NON- <br />SHEAR WALL SILL ANCHORS SHALL BE SPACED NO MORE THAN 72" O.C. EACH SILL PLATE SEGMENT SHALL HAVE A MINIMUM OF <br />TWO ANCHOR BOLTS. ONE ANCHOR BOLT SHALL BE INSTALLED BETWEEN 6" AND 12" FROM THE END OF EACH SILL PLATE. <br />3.ALL HOLD-DOWN ANCHORS, SHEAR WALL ANCHOR BOLTS AND ANCHOR BOLTS OF NON-STANDARD SPACING SHALL BE SECURED IN <br />PLACE PRIOR TO FOUNDATION INSPECTION. <br />4.INTERIOR EMBEDDED 5/8" DIA. ANCHOR BOLTS MAY BE REPLACED ON A ONE-FOR-ONE BASIS w/ 5/8" SIMPSON-STRONGTIE <br />STRONG-BOLT 2 WEDGE ANCHORS PER ICC-ESR 3037, HILTI KWIK BOLT EXPANSION ANCHORS PER ICBO/ESR-1917 OR ITW RED HEAD <br />TRUBOLT + WEDGE ANCHORS PER ICC-ESR-3772. DO NOT USE EXPANSION ANCHORS WITHIN 8" OF FOUNDATION EDGE. <br />5.EXTERIOR AND INTERIOR EMBEDDED 5/8" DIA. ANCHOR BOLTS MAY BE REPLACED ON A ONE-FOR-ONE BASIS w/ 5/8" A307 OR A36 <br />ALLTHREAD ANCHOR BOLTS OF THE SAME DIAMETER w/ 5" MIN. EMBEDMENT AND EPOXY ADHESIVE APPROVED FOR WIND AND <br />SEISMIC LOADS IN CRACKED CONCRETE (SIMPSON SET-XP EPOXY PER ICC-ESR 2508, HILTI HIT-RE500 V3 EPOXY PER ICC ELC-3814 ). <br />ALL ANCHORS SHALL BE 1 3/4" CLEAR OF THE EDGE OF SLAB U.N.O. <br />6.EPOXY GROUTED ALL-THREAD ANCHORS SHALL BE SPECIFICALLY DETAILED AND FOR EACH HOLD-DOWN SIZE AND CONFIGURATION. <br />WHERE EMBED ANCHORS HAVE BEEN OMITTED, THE CONTRACTOR SHALL CONTACT THE ENGINEER OF RECORD TO OBTAIN <br />RETROFIT ANCHOR SPECIFICATIONS. ANCHORS SHALL BE INSTALLED WITH EPOXY ADHESIVE APPROVED FOR CRACKED CONCRETE <br />(SIMPSON SET-3G EPOXY PER ICC-ESR 4057, HILTI HIT-RE500 V3 EPOXY PER ICC ELC-3814). THE EPOXY GROUTED BOLTS SHALL <br />BE INSTALLED PER MANUFACTURERS SPECIFICATIONS AND ICBO/ESR REPORT REQUIREMENTS. ALTERNATE ICC APPROVED EPOXY <br />APPROVED FOR WIND AND SEISMIC TENSION LOADS IN CRACKED CONCRETE MAY BE USED, WITH WRITTEN APPROVAL FROM THE <br />ENGINEER. <br />7.ALL EPOXY ANCHOR INSTALLATIONS REQUIRE SPECIAL INSPECTION. <br />WOOD <br />1.STRUCTURAL SAWN LUMBER DESIGN VALUES SHALL COMPLY WITH THE LATEST EDITION OF THE GRADING RULES OF THE WESTERN WOOD <br />PRODUCTS ASSOCIATION (WWPA) DOC PS 20. ALL SAWN LUMBER SHALL BE STAMPED WITH THE GRADE MATCH OF AN APPROVED LUMBER <br />GRADING AGENCY. STRUCTURAL SAWN LUMBER COMPONENTS SHALL HAVE THE FOLLOWING MIN. GRADE U.N.O.: <br />USE LUMBER GRADE . <br />2x TOP PLATES DOUGLAS FIR/LARCH No. 2 . <br />2x4 STUDS, 2x6 STUDS 10 ft & UNDER DOUGLAS FIR/LARCH STUD GRADE . <br />2x6 STUDS OVER 10 ft DOUGLAS FIR/LARCH No. 2 . <br />JOISTS, RAFTERS, ALL OTHER 2x DOUGLAS FIR/LARCH No. 2 . <br />4x POSTS & BEAMS DOUGLAS FIR/LARCH No. 2 . <br />6x & WIDER POSTS & BEAMS DOUGLAS FIR/LARCH No. 1 . <br />2.ALL SILL PLATES IN CONTACT WITH CONCRETE SHALL BE NATURALLY RESISTANT TO OR PRESSURE TREATED FOR RESISTANCE TO INSECTS <br />AND DECAY. <br />3.ALL BEAMS SHALL BE CONSIDERED DROPPED U.N.O. ON THE PLANS. GIRDER TRUSS/BEAM PLATE SHALL HAVE FULL BEARING (2) 2x STUDS <br />MINIMUM. NAIL STUDS TOGETHER PER TYPICAL NAILING SCHEDULE. BEAMS OR TWO PLY (OR LARGER) GIRDER TRUSSES BEARING ON TOP <br />PLATES SHALL BE ATTACHED TO TOP PLATES WITH A34 OR A35 ONE SIDE AND (2) 16d TOENAILS ON THE OTHER SIDE. <br />4.UNLESS SPECIFICALLY NOTED ON THE PLAN, DOOR & WINDOW OPENINGS AT EXTERIOR WALLS FOLLOWING MIN NUMBER OF KING STUDS EACH <br />END: <br />MAX. OPENING WIDTH ALLOWED FOR THE GIVEN KING STUD COUNT <br />WALL HEIGHT (1) 2x4 (2) 2x4 (3) 2X4 (1) 2X6 (2) 2X6 (3) 2X6 <br />8 ft 5'-8"12'-6"22'-6"13'-6"29'-0"36'-O" <br />9 ft 4'-0"9'-6"15'-0"10'-6"22'-6"34'-6" <br />10 ft 3'-2"7'-8"12'-4"8'-4"18'-0"27-8" <br />12 ft ------------7'-3"15'-6"24'-6" <br />2X4 KING STUDS SHALL BE CONNECTED TO PLATES w/ (2) 16d T&B MIN, 2x6 KING STUDS w/ (3) 16d T&B. <br />5.A HOLE NOT GREATER IN DIAMETER THAN 40% OF THE STUD WIDTH MAY BE BORED IN ANY WOOD STUD. BORED HOLES NOT GREATER THAN <br />60% OF THE WIDTH OF THE STUD ARE PERMITTED IN NONBEARING PARTITIONS OR IN ANY WALL WHERE EACH BORED STUD IS DOUBLED <br />PROVIDED NOT MORE THAN TWO SUCH SUCCESSIVE DOUBLED STUDS ARE SO BORED. IN NO CASE SHALL THE EDGE OF THE BORED HOLE BE <br />NEARER THAN 5/8" IN TO THE EDGE OF THE STUD. BORED HOLES SHALL NOT BE LOCATED AT THE SAME SECTION OF STUD AS A CUT OR <br />NOTCH. (2308.5.10 CBC 2022) DO NOT NOTCH JOISTS, RAFTERS OR BEAMS, EXCEPT WHERE SHOWN IN DETAILS. OBTAIN ENGINEER'S <br />APPROVAL FOR ANY HOLES OR NOTCHES NOT DETAILED. <br />6.ALL BOLTS SHALL BE INSTALLED IN HOLES BORED WITH A BIT 1/16 INCH LARGER THAN THE DIA. OF THE BOLT. BOLTS AND NUTS SEATING <br />ON WOOD SHALL HAVE CUT STEEL WASHERS UNDER HEADS AND NUTS. DING THREADS TO PREVENT LOOSENING. LAG BOLTS SHALL BE <br />INSTALLED IN PRE-DRILLED HOLES BY TURNING WITH A WRENCH. <br />7.ALL NAILS EXCEPT 16d NAILS SHALL BE COMMON NAILS U.N.O. 16d NAILS MAY BE 16d COMMON (.162"x3 1/2"), 16d SINKER OR 12d COMMON <br />(.144"x3 1/4"), 16d BOX (.135" x 3 1/2"), PNEUMATIC "P-NAIL" or "SHORT" (.131" x 3 1/4") UNLESS SPECIFIED OTHERWISE. NAILS SHALL BE <br />DRIVEN SO THAT HEADS ARE FLUSH WITH WOOD SURFACE. OVER-OR UNDER-DRIVEN NAILS WILL NOT BE ACCEPTABLE. MISC. NAILING <br />SHALL BE PER CBC TABLE 2304.10.1 FASTENING SCHEDULE. <br />8.ALL PLYWOOD LAID WITH FACE GRAIN PERPENDICULAR TO SUPPORTS SHALL BE C-D OR C-C SHEATHING CONFORMING TO AWC SDPWS TABLE <br />4.2 (AF&PA DOC 2) AND SHALL CONFORM TO THE FOLLOWING NOMINAL THICKNESS, SPAN RATING AND NAILING PATTERN UNLESS SPECIFIED <br />OTHERWISE.: <br />THICKNESS SPAN RATING FIELD NAILING EDGE NAILING (EN) BOUNDARY NAILING (BN) <br />3/8"24/0 8d AT 12" O.C.8d AT 6" O.C.8d AT 6" O.C. <br />7/16"24/16 8d AT 12" O.C.8d AT 6" O.C.8d AT 6" O.C. <br />15/32"32/16 8d AT 12" O.C.8d AT 6" O.C.8d AT 6" O.C. <br />19/32"32/16 8d AT 12" O.C.8d AT 6" O.C.8d AT 6" O.C. <br />3/4"48/24 10d AT 12" O.C.10d AT 6" O.C.10d AT 6" O.C. <br />1"60/48 10d AT 12" O.C.10d AT 6" O.C.10d AT 6" O.C. <br />1 1/8"48 10d AT 12" O.C.10d AT 6" O.C.10d AT 6" O.C. <br />9.REFER TO 2022 CRC TABLES R602.3 (1-4) FOR ALTERNATIVE FASTENERS, WALL SHEATHING AND ALLOWABLE SPANS. <br />10.A.P.A. PERFORMANCE RATED SHEATHING (OSB) MAY BE USED AS AN ALTERNATE TO PLYWOOD WITH PRIOR APPROVAL OF OWNER AND <br />ARCHITECT. RATED SHEATHING SHALL COMPLY WITH PSI-95 AND/OR PSI-92, EXPOSURE 1, AND SHALL HAVE A SPAN RATING EQUIVALENT TO <br />OR BETTER THAN THE PLYWOOD IT REPLACES. ATTACHMENT AND THICKNESS (WITHIN 1/32") SHALL BE THE SAME AS THE PLYWOOD IT <br />REPLACES. INSTALL PER MFR'S RECOMMENDATIONS. <br />11.GLUE-LAMINATED BEAMS (GLULAM or GLB) SHALL BE DOUGLAS FIR COMBINATION 24F-V4 ON SINGLE SPANS, 24F-V8 FOR CANTILEVERED OR <br />MULTI-SPAN BEAMS, U.N.O. ON THE PLANS. THE GLB BEAMS SHALL HAVE THE FOLLOWING MINIMUM BASE PROPERTIES: E = 1,800,000 psi; <br />Fb = 2,400 psi; Fv = 265 psi; Fc = 1,650 psi (PARALLEL), Fc = 650 psi (PERPENDICULAR); Ft = 1,100 psi. FABRICATION AND HANDLING SHALL <br />CONFORM WITH THE LATEST AITC AND AST STANDARDS. BEAMS SHALL BEAR AN APPROPRIATE GRADE STAMP CLEARLY NOTING ITS DESIGN <br />PROPERTIES. BEAMS SHALL BE MANUFACTURED WITH INDUSTRY STANDARD MINIMUM CAMBER UNLESS CAMBER IS SPECIFICALLY NOTED ON <br />THE DRAWINGS. <br />SPECIAL INSPECTION NOTES <br />1.ALL SPECIAL INSPECTIONS REQUIRED SHALL BE PERFORMED IN ACCORDANCE WITH SECTION 1704 & 1705 OF THE 2022 CALIFORNIA BUILDING <br />CODE. <br />2.IN ADDITION TO STANDARD INSPECTION BY THE BUILDING OFFICIAL REQUIRED PER CBC, THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL <br />INSPECTORS WHO SHALL PROVIDE INSPECTION DURING CONSTRUCTION FOR THE TYPES OF WORK LISTED BELOW. <br />3.THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE, TO THE SATISFACTION OF THE BUILDING <br />OFFICIAL, FOR INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION. <br />4.THE SPECIAL INSPECTOR SHALL INSPECT THE WORK ASSIGNED FOR CONFORMANCE WITH THE APPROVED CONTRACT DRAWINGS AND <br />SPECIFICATIONS. SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL. THE ENGINEER OF RECORD AND <br />OTHER DESIGNATED PERSONS. ALL DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR <br />CORRECTION, THEN IF UNCORRECTED IN A REASONABLE PERIOD OF TIME, THE ENGINEER AND THE BUILDING OFFICIAL SHALL BE NOTIFIED. <br />THE SPECIAL INSPECTOR SHALL SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO <br />THE BEST OF THE INSPECTOR'S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS AND THE APPLICABLE <br />CODE PROVISIONS. <br />5.INSPECTORS SHALL INSPECT FROM AN APPROVED SET OF CONTRACT DRAWINGS, SHOP DRAWINGS SHALL NOT BE USED IN LIEU OF THE <br />APPROVED CONTRACT DRAWINGS FOR INSPECTION PURPOSES. <br />6.CERTIFICATE OF APPROVAL REGARDING MATERIALS AND INSPECTION OF PREFABRICATED ITEMS SHALL BE PROVIDED IN ACCORDANCE WITH <br />CBC CHAPTER 17. <br />7.TYPES OF WORK TO BE INSPECTED BY THE SPECIAL INSPECTOR ARE AS FOLLOWS: <br />a.DURING ALL EPOXY ANCHORING INSTALLATIONS FOR BOLTS, REBAR, THREADED ROD, ETC. PER CBC 1705.3, 7 ACI 318: 17.8.4.2 INCLUDING <br />VERIFICATION OF BOLT OR BAR MATERIALS, HOLE DEPTH AND DIAMETER, HOLE CLEANOUT, EPOXY MIXING AND PLACEMENT PROCEDURES, <br />AND EMBEDMENT DEPTH IN ACCORDANCE THE CONTRACT DRAWINGS, REFERENCE ICC ESR REPORTS AND THE MFR'S SPECIFICATIONS AND <br />RECOMMENDATIONS. <br />DESIGN VALUES <br />GRAVITY LOADS: <br />ROOF DEAD LOAD = 15.0 psf <br />ROOFING WEIGHT = 5.0 psf <br />ROOF LIVE LOAD = 20.0 psf <br />S <br />WIND: <br />BASIC WIND SPEED = 95 mp <br />EXPOSURE CATEGORY 'C' <br />RISK CATEGORY: I1 <br />ASCE 7-16 METHOD 2 PRESSURES <br />ZONE A = 23.3 psf <br />ZONE B = -7.0 psf <br />ZONE C = 14.6 psf <br />ZONE D = -4.1 psf <br />S <br />1 <br />Residence Remodel <br />1 <br />1 <br />SPECIAL INSPECTION CHECK LIST <br />NAME OF OWNER OR AGENT: <br />I, AS THE OWNER/AGENT (CONTRACTOR MAY NOT EMPLOY SPECIAL INSPECTORS), CERTIFY THAT I WILL BE <br />RESPONSIBLE FOR EMPLOYING THE SPECIAL INSPECTOR FOR EACH ITEM LISTED AS REQUIRED BY THE 2022 CA <br />BUILDING CODE, SECTION 1704 & 1705 FOR THIS PROJECT LOCATED AT THE ADDRESS LISTED ON THE TITLE BLOCK. <br />SIGNATURE , DATE <br />AS THE ENGINEER OF RECORD, I NEAL G. WANKET CERTIFY THAT I HAVE PREPARED THE FOLLOWING SPECIAL <br />INSPECTION PROGRAM REQUIRED BY THE 2022 CBC, SECTION 1704.3 FOR THIS PROJECT AT THE ADDRESS LISTED ON <br />THE TITLE BLOCK. <br />1.SEE SPECIAL INSPECTION NOTES ON THIS SHEET FOR EACH CATEGORY LISTED BELOW. <br />2.SPECIAL INSPECTORS SHALL CHECK IN WITH THE GOVERNING DEPARTMENT OF BUILDING AND SAFETY WITH <br />CREDENTIALS TO OBTAIN APPROVAL BY THE DEPARTMENT TO ACT AS THE SPECIAL INSPECTOR FOR THIS PROJECT <br />PRIOR TO BEGINNING WORK ON THIS PROJECT. <br />ITEMS TO BE INSPECTED:INSPECTOR: DUTIES: . <br />EPOXY ANCHORS/DOWELS DEPUTY INSPECTOR REFER TO SPECIAL INSPECTION NOTE 7a <br />DEPUTY INSPECTORS: <br />INLAND ENGINEERING TECHNOLOGIES, INC (951) 894-6464 <br />ACCUTECH AFFORDABLE INSPECTIONS (760) 846-1464 <br />DEPUTY SPECIAL INSPECTIONS (951) 203-5010 <br />1 <br />1 <br />1 <br />1 <br />1 <br />COVER SHEET/GENERAL NOTES <br />S-1 3 <br />N.A. <br />PROJECT NUMBER: <br />SHEET NUMBER: <br />OF <br />CL <br />I <br />E <br />N <br />T <br />: <br />TI <br />T <br />L <br />E <br />: <br />SCALE: <br />DRAWN BY: <br />PR <br />O <br />J <br />E <br />C <br />T <br /> <br />H <br />I <br />S <br />T <br />O <br />R <br />Y <br />: <br />DATE: <br />AI <br />T <br />S AT <br />O <br />C <br />F <br />E <br />CI <br />V <br />AI <br />L <br />FI <br />O <br />NR <br />LW <br />N <br />ETSIGER <br />APE <br />RED <br />R <br />SEFO L <br />.G <br />G <br />T <br />I REEN <br />O <br />SI <br />N <br />LA EKNA <br />NE <br />No <br />. <br /> <br />6 <br />8 <br />8 <br />5 <br />6 <br />Ex <br />p <br />. <br /> <br />9 <br />/ <br />3 <br />0 <br />/ <br />2 <br />5 <br />16 <br />0 <br />8 <br /> <br />W <br />. <br /> <br />F <br />e <br />s <br />c <br />u <br />e <br /> <br />L <br />a <br />n <br />e <br />, <br /> <br /># <br />2 <br />0 <br />3 <br />, <br /> <br />C <br />o <br />e <br />u <br />r <br /> <br />d <br />' <br />A <br />l <br />e <br />n <br />e <br />, <br /> <br />I <br />D <br /> <br />8 <br />3 <br />8 <br />1 <br />5 <br />(9 <br />5 <br />1 <br />) <br />97 <br />2 <br />- <br />0 <br />7 <br />6 <br />9 <br /> <br /> <br /> <br />n <br />e <br />a <br />l <br />@ <br />n <br />g <br />w <br />e <br />n <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br />. <br />c <br />o <br />m <br />NG <br />W <br /> <br />EN <br />G <br />I <br />N <br />E <br />E <br />R <br />I <br />N <br />G <br />, <br /> <br />I <br />N <br />C <br />NG <br />W <br /> <br />EN <br />G <br />I <br />N <br />E <br />E <br />R <br />I <br />N <br />G <br />, <br /> <br />I <br />N <br />C <br />NG <br />W <br /> <br />EN <br />G <br />I <br />N <br />E <br />E <br />R <br />I <br />N <br />G <br />, <br /> <br />I <br />N <br />C <br />NG <br />W <br /> <br />EN <br />G <br />I <br />N <br />E <br />E <br />R <br />I <br />N <br />G <br />, <br /> <br />I <br />N <br />C <br />NG <br />W <br /> <br />EN <br />G <br />I <br />N <br />E <br />E <br />R <br />I <br />N <br />G <br />, <br /> <br />I <br />N <br />C <br />NG <br />W <br /> <br />EN <br />G <br />I <br />N <br />E <br />E <br />R <br />I <br />N <br />G <br />, <br /> <br />I <br />N <br />C <br />NG <br />W <br /> <br />EN <br />G <br />I <br />N <br />E <br />E <br />R <br />I <br />N <br />G <br />, <br /> <br />I <br />N <br />C <br />NG <br />W <br /> <br />EN <br />G <br />I <br />N <br />E <br />E <br />R <br />I <br />N <br />G <br />, <br /> <br />I <br />N <br />C <br />Bu <br />i <br />l <br />d <br />e <br />r <br /> <br />F <br />r <br />i <br />e <br />n <br />d <br />l <br />y <br /> <br />& <br /> <br />O <br />n <br /> <br />T <br />i <br />m <br />e <br />Bu <br />i <br />l <br />d <br />e <br />r <br /> <br />F <br />r <br />i <br />e <br />n <br />d <br />l <br />y <br /> <br />& <br /> <br />O <br />n <br /> <br />T <br />i <br />m <br />e <br />Bu <br />i <br />l <br />d <br />e <br />r <br /> <br />F <br />r <br />i <br />e <br />n <br />d <br />l <br />y <br /> <br />& <br /> <br />O <br />n <br /> <br />T <br />i <br />m <br />e <br />Bu <br />i <br />l <br />d <br />e <br />r <br /> <br />F <br />r <br />i <br />e <br />n <br />d <br />l <br />y <br /> <br />& <br /> <br />O <br />n <br /> <br />T <br />i <br />m <br />e <br />Bu <br />i <br />l <br />d <br />e <br />r <br /> <br />F <br />r <br />i <br />e <br />n <br />d <br />l <br />y <br /> <br />& <br /> <br />O <br />n <br /> <br />T <br />i <br />m <br />e <br />Bu <br />i <br />l <br />d <br />e <br />r <br /> <br />F <br />r <br />i <br />e <br />n <br />d <br />l <br />y <br /> <br />& <br /> <br />O <br />n <br /> <br />T <br />i <br />m <br />e <br />Pe <br />t <br />e <br />r <br /> <br />F <br />r <br />a <br />z <br />i <br />e <br />r <br />/ <br />O <br />c <br />t <br />o <br />b <br />e <br />r <br /> <br />5 <br />Fr <br />u <br />i <br />t <br /> <br />S <br />t <br />r <br />e <br />e <br />t <br /> <br />R <br />e <br />s <br />i <br />d <br />e <br />n <br />c <br />e <br /> <br />R <br />e <br />m <br />o <br />d <br />e <br />l <br />19 <br />2 <br />5 <br /> <br />E <br />. <br /> <br />F <br />r <br />u <br />i <br />t <br /> <br />S <br />t <br />r <br />e <br />e <br />t <br />Sa <br />n <br />t <br />a <br /> <br />A <br />n <br />a <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />1 <br />6/3/2024 <br />JMM, NGW <br />24-0303-ST <br />BU <br />I <br />L <br />D <br />I <br />N <br />G <br /> <br />D <br />E <br />P <br />A <br />R <br />T <br />M <br />E <br />N <br />T <br /> <br />C <br />O <br />R <br />R <br />E <br />C <br />T <br />I <br />O <br />N <br />S <br />, <br /> <br />N <br />G <br />W <br /> <br />1 <br />2 <br />/ <br />6 <br />/ <br />2 <br />0 <br />2 <br />4 <br />1 <br />1925 E Fruit St <br />2/26/2025