CUSTOMER
<br />DATE:
<br />SCALE:
<br />SHEET #
<br />CUSTOMER
<br />E-3
<br />APN
<br />PLAN SET REVISIONS
<br />399-031-24 / 399-031-23
<br />6/8/2023
<br />SAMUELI ACADEMY
<br />1901/1919 N. FAIRVIEW ST.
<br />SANTA ANA, CA. 92705
<br />CONTRACTOR SIGNATURE:
<br />DAVID CLEVELAND
<br />CO
<br />N
<br />T
<br />R
<br />A
<br />C
<br />T
<br />O
<br />R
<br />'
<br />S
<br />
<br />L
<br />I
<br />C
<br />E
<br />N
<br />S
<br />E
<br />
<br />#
<br />
<br />1
<br />0
<br />8
<br />9
<br />1
<br />1
<br />7
<br />CO
<br />N
<br />T
<br />R
<br />A
<br />C
<br />T
<br />O
<br />R
<br />'
<br />S
<br />
<br />L
<br />I
<br />C
<br />E
<br />N
<br />S
<br />E
<br />
<br />#
<br />
<br />1
<br />0
<br />8
<br />9
<br />1
<br />1
<br />7
<br />DRAWN BY:
<br />CHECKED BY:
<br />APPROVED BY:
<br />ENGINEER STAMP
<br />ELECTRICAL NOTES
<br />ELECTRICAL SPECIFICATIONS
<br />1.SCOPE OF WORK
<br />1.1. THE PROJECT IS A NEW PHOTOVOLTAIC SYSTEM CONSISTING OF SOLAR ARRAY(S) AND
<br />ASSOCIATED POWER CONDITIONING EQUIPMENT.
<br />1.2. ALL CONSTRUCTION SHALL COMPLY WITH THE ADOPTED EDITION OF THE CALIFORNIA BUILDING
<br />CODE (CBC) AND CALIFORNIA ELECTRICAL CODE (2019 CEC) AS SPECIFIED IN THE PROJECT
<br />SPECIFIC NOTES. IT SHALL ALSO COMPLY WITH ALL APPLICABLE CITY, COUNTY, STATE AND
<br />LOCAL ELECTRICAL UTILITY CODES, RULES, AND REGULATIONS.
<br />1.3. THE SYSTEM WILL BE INTERCONNECTED TO THE ELECTRICAL UTILITY GRID IN ACCORDANCE
<br />WITH THE REQUIREMENTS OF THE ADOPTED CEC AND THE ELECTRICAL UTILITY COMPANY.
<br />1.4. THE CONTRACTOR SHALL PROVIDE LABOR FOR CONSTRUCTION OF THE ARRAY AND
<br />INSTALLATION OF ALL ELECTRICAL EQUIPMENT. THE CONTRACTOR WILL PROVIDE COMPETENT
<br />SUPERVISION FOR THE WORK TO BE ACCOMPLISHED. CONTRACTOR SHALL SUBMIT SHOP
<br />DRAWINGS FOR APPROVAL BY OWNER AS REQUIRED.
<br />1.5. THERE WILL BE NO SUBSTITUTION FOR ANY EQUIPMENT WITH A VENDOR PART NUMBER ON THE
<br />DRAWINGS WITHOUT WRITTEN APPROVAL OF MOTIVE ENERGY ENGINEERING. COMMON ITEMS
<br />SUCH AS CONDUIT, WIRE, FITTINGS, ETC. ARE NOT SPECIFIED BY VENDOR BUT THE SIZES
<br />CANNOT BE REDUCED.
<br />1.6. THE CONSTRUCTION CONTRACTOR AND HIS SUBCONTRACTORS AGREE THAT IN ACCORDANCE
<br />WITH GENERALLY ACCEPTED CONSTRUCTION PRACTICES, CONSTRUCTION CONTRACTOR AND
<br />HIS SUBCONTRACTORS WILL BE REQUIRED TO ASSUME SOLE AND COMPLETE RESPONSIBILITY
<br />FOR SAFETY OF ALL PERSONS AND PROPERTY, AND THAT THIS REQUIREMENT SHALL BE MADE
<br />TO APPLY CONTINUOUSLY AND IS NOT LIMITED TO NORMAL WORKING HOURS.
<br />1.7. CONSTRUCTION CONTRACTOR AND HIS SUBCONTRACTORS FURTHER AGREE TO DEFEND,
<br />INDEMNIFY AND HOLD HARMLESS THE DESIGN PROFESSIONAL FROM ANY AND ALL LIABILITY,
<br />REAL OR ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT,
<br />EXCEPT LIABILITY ARISING FROM THE SOL NEGLIGENCE OF DESIGN PERSONNEL.
<br />1.8. THE CONTRACTOR AND HIS SUBCONTRACTORS WILL BE REQUIRED TO REPAIR ANY DAMAGE
<br />DONE TO BUILDINGS, GROUNDS OR UTILITIES AT NO ADDITIONAL COST TO THE CUSTOMER.
<br />DEFECTIVE MATERIALS OR WORKMANSHIP WILL NOT SHALL BE CONDUCTED BOTH DURING THE
<br />EXECUTION OF AND AT THE CONCLUSION OF THE PROJECT.
<br />2.GENERAL
<br />2.1. THE ACTUAL SYSTEM EQUIPMENT SPECIFICATIONS FOR THE PHOTOVOLTAIC SYSTEM ARE
<br />INCLUDED IN THE PV SYSTEM SPECIFICATIONS TABLE ON THE TITLE PAGE AND THROUGHOUT
<br />THE DRAWINGS AS NECESSARY FOR CLARITY. IN ADDITION, THE ACTUAL VENDOR
<br />SPECIFICATION DATA SHEETS WILL BE INCLUDED AS PART OF THE PERMIT SUBMITTAL.
<br />2.2. ONLY NEW MATERIALS FREE OF DEFECTS WILL BE INSTALLED AS PART OF THE PROJECT. ALL
<br />NEW INSTALLED EQUIPMENT SHALL HAVE PERMANENT PLASTIC OR METAL ENGRAVED
<br />IDENTIFICATION TAGS INSTALLED.
<br />2.3. ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF NEW RACEWAYS AND
<br />EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. ALL WORK
<br />SHALL BE PERFORMED BY TRADESMAN EXPERIENCED IN THE WORK REQUIRED. ALL FINISHES
<br />SHALL MATCH THE EXISTING ADJACENT FINISHES. OPENINGS IN FIRE RATED WALLS WILL BE
<br />PATCHED IN A MANNER MAINTAINING THE ORIGINAL FIRE AND SMOKE RATINGS.
<br />2.4. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND CANNOT SHOW EVERY CONNECTION, JUNCTION
<br />BOX, WIRE, CONDUIT, ETC. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A
<br />COMPLETE AND FUNCTIONAL ELECTRICAL SYSTEM.
<br />2.5. CONTRACTOR WILL COORDINATE ALL POWER OUTAGES WITH THE OWNER'S REPRESENTATIVE
<br />IN ADVANCE.
<br />2.6. PANEL DESIGNATIONS SHOWN ON THESE DRAWINGS ARE GIVEN FOR CLARIFICATION OF
<br />CIRCUITING ONLY AND MAY NOT CORRESPOND TO THE DESIGNATIONS FOUND IN THE FIELD.
<br />3.CONDUIT AND WIRE
<br />3.1. ALL CONDUCTORS SHALL BE INSTALLED IN CONDUIT, UNLESS NOTED OTHERWISE ON PLANS.
<br />EXCEPTION: PV SOURCE CIRCUIT CONDUCTORS MADE OF TYPE USE-2 OR PV WIRE TYPE
<br />CABLES MAY BE INSTALLED IN FREE AIR BENEATH THE PV ARRAY.
<br />3.2. ALL CONDUCTOR SHALL BE COPPER OR ALUMINUM AS SPECIFIED ON THE DRAWINGS, WITH 90°C
<br />RATED INSULATION, UNLESS NOTED OTHERWISE.
<br />3.3. ALL SERVICE, FEEDER AND BRANCH CONDUCTORS SHALL BE IDENTIFIED TO MATCH THE
<br />EXISTING BUILDING OR STRUCTURE IDENTIFICATION SCHEME PER CEC 200.6, 210.5 AND 215.12.
<br />WHERE MORE THAN ONE NOMINAL VOLTAGE SYSTEM EXISTS IN A BUILDING OR STRUCTURE,
<br />EACH UNGROUNDED CONDUCTOR SHALL BE IDENTIFIED BY PHASE AND SYSTEM. THE
<br />IDENTIFICATION SCHEME SHALL BE PERMANENTLY POSTED AT EACH PANEL BOARD OR
<br />SWITCHBOARD. IF THE BUILDING OR STRUCTURE DOES NOT HAVE AN EXISTING SCHEME, USE
<br />THE FOLLOWING.
<br />208/120 VOLT PHASE 480/277 VOLT
<br /> BLACK A BROWN
<br /> RED B ORANGE
<br /> BLUE C YELLOW
<br /> WHITE NEUTRAL GRAY
<br /> GREEN GROUND GREEN
<br />3.4. THE IDENTIFICATION SCHEME SHALL BE PERMANENTLY POSTED AT EACH PIECE OF DC
<br />EQUIPMENT PER 690.31(B)(1).
<br />DC PHASE
<br />BLACK NEGATIVE
<br />RED POSITIVE
<br />3.5. ALL CONDUCTORS SHALL BE IDENTIFIED AT ALL TERMINATIONS, JUNCTION BOXES AND PULL
<br />BOXES.
<br />3.6. AC SYSTEM CONDUCTORS SIZED #6 AWG AND BELOW SHALL BE COLOR CODED WITH COLORED
<br />INSULATION. CONDUCTORS SIZED #4 AWG AND LARGER SHALL BE COLOR CODED OR IDENTIFIED
<br />WITH COLORED TAPE.
<br />3.7. ALL DC SYSTEM CONDUCTOR SIZES SHALL BE IDENTIFIED WITH COLORED INSULATION, TAPE,
<br />TAGGING ORE OTHER APPROVED MEANS PER CEC ART. 690.31(B).
<br />3.8. WHERE INSTALLED IN RACEWAY, ALL AC CIRCUIT CONDUCTORS #8 AWG AND LARGER SHALL BE
<br />STRANDED. ALL AC CIRCUIT CONDUCTORS #12 AWG AND SMALL SHALL BE SOLID.
<br />3.9. WHERE WIRING AND CONDUIT SIZES ARE INDICATED FOR HOMERUNS, THESE SIZES APPLY TO
<br />THE ENTIRE LENGTH FROM THE PROTECTIVE DEVICE IN THE PANEL TO THE EQUIPMENT OR
<br />LAST WIRING DEVICE.
<br />3.10. ALL EXISTING CONDUIT RUNS SHOWN ON PLANS ARE BASED ON EXISTING AS-BUILTS AND
<br /> LIMITED SITE OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT SIZES,
<br /> QUANTITIES, AND LOCATIONS PRIOR TO COMMENCEMENT OF WORK.
<br />3.11. INDOOR EMT FITTINGS MAY BE COMPRESSION TYPE OR STEEL SET SCREW TYPE.
<br />OUTDOOR EMT FITTINGS MUST BE COMPRESSION RAINTIGHT TYPE.
<br />3.12. ALL CONDUIT PENETRATIONS THROUGH ROOFS, FLOORS OR WALLS SHALL BE MADE WATER
<br /> TIGHT BY PROPER FLASHING, CAULKING OR SEALING.
<br />3.13. WHERE PORTIONS OF A RACEWAY ARE PASSING FROM INTERIOR TO THE EXTERIOR OF A
<br /> BUILDING OR UNDER GROUND TO ABOVEGROUND, THE RACEWAY SHALL BE FILLED WITH A
<br /> LISTED PRODUCT THAT IS INTENDED FOR THE APPLICATION NEAR THE TRANSITION TO PREVENT
<br /> THE CIRCULATION OF AIR, MOISTURE, AND WATER PER CEC 300.7.
<br /> 3.14. OPENINGS AROUND ELECTRICAL PENETRATIONS INTO OR THROUGH FIRE-RESISTANT-RATED
<br />WALLS, PARTITIONS, FLOORS OR CEILINGS SHALL BE FIRE STOPPED USING APPROVED
<br />METHODS TO MAINTAIN THE FIRE RESISTANCE RATING PER CEC 300.21.
<br /> 3.15. ALL FIXTURES AND DEVICES SHALL BE PROVIDED WITH SUITABLE METAL OUTLET BOXES,
<br />CONFORMING TO CEC ARTICLE 314. BOXES SHALL BE SUPPORTED RIGIDLY FROM THE
<br />STRUCTURE.
<br /> 3.16. ALL ABOVEGROUND CONDUITS LONGER THAN 3 FEET SHALL BE EMT, IMC, OR RMC. EMT SHALL
<br />ONLY BE ALLOWED WHERE CONDUIT IS NOT SUBJECT TO PHYSICAL DAMAGE.
<br /> 3.17. ALL CONDUITS INSTALLED IN UNDERGROUND TRENCHES SHALL BE SCHEDULE 40 PVC OR
<br />SCHEDULE 80 PVC. SCHEDULE 40 PVC SHALL NOT BE INSTALLED ABOVE GRADE. THE
<br />TRANSITION FROM PVC CONDUIT TO METALLIC CONDUIT SHALL OCCUR AT OR BELOW GRADE
<br />LEVEL. ALL METALLIC CONDUIT AND FITTINGS INSTALLED BELOW GRADE SHALL BE WRAPPED
<br />WITH LISTED, 20 MILL THICK 2" WIDE TAPE. WRAP TAPE WITH 1" OVERLAP.
<br /> 3.18. HORIZONTAL DIRECTIONAL DRILLING (A.K.A. BORING) MAY BE EMPLOYED WHERE INSTALLING
<br />CONDUITS IN A TRENCH IS NOT PRACTICAL. CONTRACTOR SHALL USE HIGH DENSITY
<br />POLYETHYLENE (HDPE) CONDUIT AND MAINTAIN THE SAME MINIMUM CONDUIT DEPTH
<br />DESCRIBED IN TRENCH DETAILS.
<br /> 3.19. THE CONDUIT ROUTES SHOWN ON THE PLANS ARE APPROXIMATE. THE CONTRACTOR SHALL
<br />DETERMINE THE BEST CONDUIT ROUTES BASED ON THE SITE CONDITIONS. THE CONTRACTOR
<br />SHALL COORDINATE WITH THE ENGINEER IF THE CONTRACTOR'S PREFERRED CONDUIT ROUTES
<br />ARE OTHER THAN WHAT ARE INDICATED ON THE DRAWINGS.
<br /> 3.20. PER CEC ART.300.7(B) WHERE CONDUITS ARE LOCATED ON ROOFTOPS OR EXPOSED TO DIRECT
<br />SUNLIGHT, EXPANSION FITTINGS MAY BE REQUIRED TO ALLOW FOR THERMAL EXPANSION.
<br />PROVIDE (1) EXPANSION FITTING ON EVERY STRAIGHT SECTION OF EXPOSED STEEL CONDUIT
<br />(EMT, IMC, RMC) THAT TERMINATES AT SECURELY MOUNTED FIXTURES AND EXCEEDS 35 FEET IN
<br />LENGTH. INSTALL EXPANSION FITTING PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
<br /> 3.21. USE LFMC CONDUIT AT POINTS ON THE STRUCTURE SUCH AS SEISMIC SEPARATIONS WHERE
<br />FLEXIBILITY IS REQUIRED. LFMC SHALL BE SUPPORTED AND SECURELY FASTENED IN INTERVALS
<br />NOT EXCEEDING 4-1/2 FEET AS REQUIRED BY CEC ART. 350.30.
<br />4. GROUNDING
<br />4.1. THE GROUNDING SYSTEM SHALL MEET THE REQUIREMENTS OF THE CEC AND THE LOCAL
<br />ADOPTED CODE. ALL ELECTRICAL EQUIPMENT AND RACEWAYS SHALL BE PROPERLY
<br />GROUNDED.
<br />4.2. AN INSULATED EQUIPMENT GROUNDING CONDUCTOR, IN ACCORDANCE WITH CEC 250.122 AND
<br />690.47, SHALL BE PROVIDED IN ALL CONDUITS WITH CURRENT CARRYING CONDUCTORS. ALL
<br />LUGS AND CONNECTORS SHALL BE RATED FOR THE CONDUCTOR MATERIAL AND THE
<br />CONDITIONS OF USE.
<br />4.3. THE GROUNDING RESISTIVITY WILL BE TESTED AFTER INSTALLATION TO CONFIRM 5 OHM OR
<br />LESS RESISTANCE FROM RACKING TO GROUND. IF GROUND RESISTANCE IS GREATER THAN 5
<br />OHMS, ADDITIONAL GROUNDING WILL BE INSTALLED UNTIL RESISTANCE IS LESS THAN 5 OHMS.
<br />5. EQUIPMENT
<br />5.1. ALL ELECTRICAL COMPONENTS INSTALLED OUTDOORS, EXPOSED TO THE WEATHER OR IN
<br />DAMP LOCATIONS SHALL BE RATED FOR NEMA 3R OR GREATER. INSTALLATION OF THESE
<br />COMPONENTS MUST COMPLY WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
<br />5.2. ALL RACEWAYS, CABINETS, BOXES, FIXTURES SHALL BE SUPPORTED FROM THE BUILDING
<br />STRUCTURE IN AN APPROVED MANNER.
<br />5.3. AT THE COMPLETION OF THE PROJECT, NEATLY TYPED ACCURATE PANELBOARD DIRECTORIES
<br />INDICATING ALL BRANCH CIRCUITS AND SPARES WILL BE PROVIDED. ALL SPARES SHALL BE LEFT
<br />IN THE OFF POSITION.
<br />5.4. ALL SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE WITH COVER INTERLOCK AND HANDLE
<br />LOCK OFF PROVISIONS. SWITCHES SHALL BE MANUFACTURED BY A COMPANY CONSISTENT
<br />WITH OTHER INSTALLED EQUIPMENT WHENEVER POSSIBLE. PART NUMBERS, RATING AND
<br />FUSING SHALL BE AS SHOWN ON THE DRAWINGS.
<br />5.5. CONTRACTOR SHALL ENSURE ALL CEC AND MAINTENANCE CLEARANCE REQUIREMENTS ARE
<br />MET FOR NEW EQUIPMENT AND MAINTAINED FOR EXISTING EQUIPMENT.
<br />5.6. CONTRACTOR SHALL FIELD VERIFY EQUIPMENT CLEARANCES AND PLACEMENTS WHILE
<br />COORDINATING LOCATIONS WITH OTHER TRADES, CONSTRUCTION MANAGERS, AND SITE
<br />SUPERVISORS PRIOR TO PURCHASING AND INSTALLING THE EQUIPMENT.
<br />5.7. EVERY STRUCTURE AND PORTION THEREOF, INCLUDING NONSTRUCTURAL COMPONENTS THAT
<br />ARE PERMANENTLY ATTACHED TO STRUCTURES AND THEIR SUPPORTS AND ATTACHMENTS,
<br />SHALL BE DESIGNED AND CONSTRUCTED TO RESIST THE EFFECTS OF EARTHQUAKE MOTIONS
<br />IN ACCORDANCE WITH ASCE 7, EXCLUDING CHAPTER 14 AND APPENDIX 11A. THE SEISMIC
<br />DESIGN CATEGORY FOR A STRUCTURE IS PERMITTED TO BE DETERMINED IN ACCORDANCE
<br />WITH SECTION 1613 OR ASCE 7.
<br />5.8. ALL CONNECTORS USED BETWEEN MODULES AND COMBINER BOXES SHALL BE THE SAME
<br />MANUFACTURER AND OF THE SAME MODEL SERIES. THERE SHALL BE NO MIXING
<br />MANUFACTURERS OR MODELS FOR ANY CONNECTION POINTS.
<br />6. WIRING DEVICES
<br />6.1. RECEPTACLES SHALL BE AS DESIGNATED ON THE DRAWINGS AND SHOULD BE A BRAND
<br />CONSISTENT WITH OTHERS IN THE VICINITY WHENEVER POSSIBLE.
<br />6.2. ALL WIRING DEVICES SHALL BE PROVIDED WITH APPROPRIATE COVER PLATES. ANY EMPTY
<br />BOXES WILL HAVE BLANK COVER PLATES. COVER PLATES SHALL BE LEXAN, PLASTIC OR
<br />STAINLESS STEEL IN FINISHED AREA. GALVANIZED COVER PLATES MAY BE USED IN EQUIPMENT
<br />ROOMS.
<br />ELECTRICAL ABBREVIATIONS, SYMBOLS, AND LINE TYPE LEGEND
<br />ABBREVIATIONS
<br />DRAWINGS
<br />AC - ALTERNATING CURRENT
<br />AF - AMP FUSE/AMP FRAME (RATING)
<br />AFF - ABOVE FINISHED FLO
<br />AIC - AMPERE INTERRUPTING CAPACITY
<br />AL - ALUMINUM
<br />AS - AMP SWITCH (RATING)
<br />AT - AMP TRIP (RATING)
<br />ATS - AUTOMATIC TRANSFER SWITCH
<br />AWG - AMERICAN WIRE GAUGE
<br />BESS - BATTERY ENERGY STORAGE SYSTEM
<br />CB - COMBINER BOX
<br />CT - CURRENT TRANSFORMER
<br />CU - COPPER
<br />DAS - DATA ACQUISITION SYSTEM
<br />DC - DIRECT CURRENT
<br />DIA - DIAMETER
<br />E - ELECTRICAL
<br />(E) - EXISTING
<br />EGC - EQUIPMENT GROUNDING CONDUCTOR
<br />EMS - ENERGY MANAGEMENT SYSTEM
<br />EMT - ELECTRICAL METALLIC TUBING
<br />EO - ELECTRICALLY OPERATED
<br />ESS - ENERGY STORAGE SYSTEM
<br />FO - FIBER OPTIC
<br />G - GROUND
<br />GEC - GROUNDING ELECTRODE CONDUCTOR
<br />GFP - GROUND FAULT PROTECTION
<br />GND - GROUND
<br />GFCI - GROUND-FAULT CIRCUIT INTERRUPTER
<br />GFDI - GROUND-FAULT DETECTION AND INTERRUPTION
<br />HVAC - HEATING, VENTILATION & AIR CONDITIONING
<br />IMC - INTERMEDIATE METAL CONDUIT
<br />IMP - CURRENT AT MAXIMUM POWER
<br />ISC - CURRENT AT SHORT CIRCUIT
<br />KAIC - KILO-AMPERE INTERRUPTING CAPACITY
<br />KCMIL - KILO (THOUSAND) CIRCUILAR MILS
<br />LFMC - LIQUIDTIGHT FLEXIBLE METAL CONDUIT
<br />LV - LOW VOLTAGE (0-2000V)
<br />MO - MOTOR OPERATED
<br />MTS - MANUAL TRANSFER SWITCH
<br />MV - MEDIUM VOLTAGE (>2000V)
<br />N - NEUTRAL
<br />(N) - NEW
<br />NC - NORMALLY CLOSED
<br />NEM - NET ENERGY METER
<br />NFPA - NATIONAL FIRE PROTECTION ASSOCIATION
<br />NGOM - NET GENERATION OUTPUT METER
<br />NO - NORMALLY OPEN
<br />N/S - NORTH-SOUTH
<br />P - POLE
<br />PLC - PROGRAMMABLE LOGIC CONTROLLER
<br />PT - POTENTIAL TRANSFORMER
<br />PTC - PV USA TEST CONDITIONS (RATING)
<br />PV - PHOTOVOLTAIC
<br />PVC - POLYVINYL CHLORIDE (CONDUIT)
<br />RMC - RIGID METAL CONDUIT
<br />S - STRUCTURAL
<br />SCCR - SHORT-CIRCUIT CURRENT RATING
<br />SCH - SCHEDULE
<br />SS - STAINLESS STEEL
<br />ST - SHUNT TRIP
<br />STC - FACTORY STANDARD TEST CONDITIONS (RATING)
<br />TYP - TYPICAL
<br />VMP - VOLTAGE AT MAXIMUM POWER
<br />VOC - VOLTAGE AT OPEN CURRENT
<br />XFMR - TRANSFORMER
<br />+ - POSITIVE
<br />- - NEGATIVE
<br />ɸ - PHASE
<br />UNITS OF MEASUREMENT
<br />A - AMPERE
<br />C - CELSIUS
<br />FT - FEET
<br />HZ - HERTZ
<br />IN - INCH
<br />MW - MEGAWATT
<br />KV - KILOVOLT
<br />KVA - KILOVOLT-AMPERE
<br />KW - KILOWATT
<br />KWH - KILOWATT HOUR
<br />V - VOLTS
<br />VAC - VOLTS IN AC
<br />VDC - VOLTS IN DC
<br />W - WATT / WIRE
<br />PLAN LINES
<br />GENERAL SYMBOLS
<br />#
<br />DETAIL REFERENCING
<br />SHEET NUMBERING
<br />KETNOTE
<br />G
<br />G
<br />GG
<br />G
<br />G
<br />G
<br />-
<br />J
<br />M
<br />REVISION
<br />SECTION
<br />LABELS & WARNINGS
<br />REFERENCING NUMBER
<br />DC CONDITIONER/OPTIMIZER
<br />SURGE ARRESTOR
<br />FUSED SWITCH OR CUTOUT
<br />MEDIUM VOLTAGE FUSE
<br />CABLE LIMITER
<br />ARRESTER
<br />BIRD DETERRENT
<br />CIRCUIT BREAKER
<br />CIRCUIT BREAKER
<br />DRAW-OUT STYLE
<br />CURRENT TRANSFORMER
<br />FUSE
<br />FUSED SWITCH
<br />GROUND
<br />GROUND TERMINAL/LUG
<br />GROUND BUS
<br />GROUND BUS BAR
<br />GROUND BUS BAR
<br />JUNCTION BOX
<br />POLE-MOUNTED LUMINAIRE /
<br />LIGHT FIXTURE
<br />UNDER CANOPY LUMINAIRE /
<br />LIGHT FIXTURE
<br />POST TOP LUMINAIRE /
<br />LIGHT FIXTURE
<br />WALL PACK LUMINAIRE /
<br />LIGHT FIXTURE
<br />METER
<br />NEGATIVE TERMINAL/LUG
<br />NEGATIVE BUS
<br />_
<br />NEGATIVE BUS BAR
<br />N
<br />N
<br />NEUTRAL TERMINAL/LUG
<br />NEUTRAL BUS
<br />_
<br />_
<br />_
<br />_
<br />NEUTRAL BUS BAR
<br />NN
<br />N
<br />N
<br />N
<br />NC NORMALLY CLOSED
<br />CONTACT
<br />NO NORMALLY OPEN
<br />CONTACT
<br />DUPLEX RECEPTACLE,
<br />NEMA 5-20R
<br />POSITIVE TERMINAL/LUG
<br />POSITIVE BUS
<br />NEUTRAL BUS BAR
<br />POTENTIAL TRANSFORMER
<br />G
<br />_+PV MODULE
<br />SWITCH
<br />TAP
<br />TRANSFORMER
<br />LOW SIDE TRANSFORMER
<br />NEUTRAL CONNECTIONXO
<br />HIGH SIDE TRANSFORMER
<br />NEUTRAL CONNECTIONHO
<br />SWITCH
<br />G GENERATOR
<br />BATTERY
<br />WIRELESS
<br />COMMUNICATION/ANTENNA
<br />DELTA TRANSFORMER
<br />WINDING
<br />WYE GROUNDED
<br />TRANSFORMER WINDING
<br />WEATHER STATION
<br />FENCE LINE
<br />CONDUIT RUN ABOVE GROUND LINE
<br />CONDUIT RUN BELOW GRADE LINE
<br />PROPERTY LINE
<br />OFFSET LINE
<br />SITE & MODULE LINE
<br />SUBARRAY LINE
<br />PV SOURCE CIRCUIT LINE
<br />EXISTING OR "OUT-OF-SCOPE" EQUIPMENT
<br />BUS LINE
<br />ENCLOSURE/GROUPING LINE
<br />EXISTING CONDUCTOR/WIRE LINE
<br />EXISTING ENCLOSURE/GROUPING LINE
<br />GROUNDING WIRE LINE
<br />CONDUCTOR/WIRING LINE
<br />ELECTRICAL LINES