Laserfiche WebLink
Scope: New PV system  installation, Busbar certification <br />PV OCPD: 30A  <br />Customer: JEFFREY KAHN <br />Address: 3202 S CENTER ST, SANTA ANA, CA 92704 <br />Utility: SCE <br />Dear Sir/Madam, <br />Due to age and maintenance conditions, the existing residential electrical panel label <br />specifications are no longer visible. A site surveyor performed site visit and obtained site <br />photos. I have reviewed the photo of the main service panel, and systems of similar panel <br />of 12 space  ‐ 24 poles max with label in the past and thus conclude: <br />The existing residential electrical main panel is Bryant – UB12-24R which has bus <br />rating of 125A and main circuit breaker of 100A (Center‐fed). The attached single <br />line diagram  design for this solar PV system  satisfies 2019 CEC article 690 and <br />705.12(B) requirements. <br />Should you have any questions, please feel free to contact me at the information listed below. <br />Respectfully, <br />Chi Fung Leung, P.E. <br />Chifung.leung@sunpowercorp.com <br />Chi F <br />Leung <br />Digitally signed <br />by Chi F Leung <br />Date: 2022.11.07 <br />01:22:19 -08'00' <br />3202 S Center St <br />12/28/22