-.e <br />Planning & Building Agency <br />Permits & Plan Check Section <br />20 Civic Center Plaza <br />P.O. Box 1988 (M-19) <br />Santa Ana, CA 92702 <br />(714)647-5800 <br />EXISTING ONE & TWO FAMILY DWELLINGS <br />ELECTRICAL SERVICES UNDERGROUND <br />EXCEPTION <br />CEC 2019 ELC-04 <br />All new utility connections are required to be installed below grade by Santa Ana Municipal Code 41- <br />626(b). There is a standing exception for existing one and two family dwellings. This exception <br />applies only when the new electrical service is designed to be fed from below grade as well as <br />overhead. <br />This diagram is a typical unit. The utility is able to feed this cabinet from the top or the bottom without <br />interfering with the distribution wiring. All the circuit breakers and branch circuits are contained in the <br />circuit breaker side of this cabinet. <br />Only listed combination overhead and underground feed service boxes may be used to connect to <br />an overhead utility drop. This exception to an underground fed service applies only to existing single <br />family and two family residences. <br />Rigid New service <br />Conduit location may NOT <br />Service <br />Entrance be under a patio <br />Conductor fl cover structure. <br />Riser -SCE <br />METER <br />PC��I�C�P <br />' Future <br />Underground <br />Service <br />Lateral <br />A surface -mounted combination service rquires no raceway provision for future underground feed. <br />When new service is semi -flush or flush mounted, a 3 inch rigid raceway is needed. Cap straight stub - <br />out at a depth of 12 inches below grade. A sweep is capped at 30 inches below grade. <br />Rev. 1/21/2020 <br />wwwsanta-ana.org/pba/ Page 1 of 1 <br />