6 <br />- <br />10 <br />- <br />4'-0" TYP.2 '-0 " <br />2 '-0 " <br />12'-0" <br />45.0° <br />6'-0" <br />MAX.6'-0"MAX12'-0"8" <br />45.0° <br />O .C .8"SEISMIC DESIGN CATEGORIES D,E AND F. <br />1. SUSPENDED CEILINGS IN SEISMIC DESIGN CATEGORIES D,E, AND F SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH ASTM <br />C635, ASTM 636 AND CISCA FOR SEISMIC ZONES 3-4 AS MODIFIED BY THE FOLLOWING: <br />2. A HEAVY DUTY T-BAR GRID SHALL BE USED <br />3. THE WIDTH OF THE PERIMETER SUPPORTING CLOSURE ANGLE SHALL BE NOT LESS THAN 2". IN EACH ORTHOGONAL HORIZONTAL <br />DIRECTION, ONE END OF THE CEILING GRID SHALL BE ATTACHED TO THE CLOSURE ANGLE. THE OTHER END IN EACH HORIZONTAL DIRECTION <br />SHALL HAVE A 0.75 ". CLEARANCE FROM THE WALL AND SHALL REST UPON AND BE FREE TO SLIDE ON A CLOSURE ANGLE <br />4. FOR CEILING AREAS EXCEEDING 1,000 SF HORIZONTAL RESTRAINT OF THE CEILING TO THE STRUCTURAL SYSTEM SHALL BE PROVIDED. THE <br />TRIBUTARY AREAS OF THE HORIZONTAL RESTRAINTS SHALL APPROXIMATELY EQUAL <br />EXCEPTION: <br />A. RIGID BRACES ARE PERMITTED TO BE USED INSTEAD OF DIAGONAL SPLAY WIRES. BRACES AND ATTACHMENTS TO THE STRUCTURAL <br />SYSTEM ABOVE SHALL BE ADEQUATE TO LIMIT RELATIVE LATERAL DEFLECTIONS AT POINT OF THE ATTACHMENT OF THE CEILING GRID TO <br />LESS THAN O.25" FOR THE LOADS PRESCRIBED IN SECTION 13.3.OF MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES <br />B. FOR CEILING AREAS EXCEEDING 2,500 SF, A SEISMIC SEPARATION JOINT OR FULL HEIGHT PARTITION THAT BREAKS THE CEILING UP INTO <br />AREAS NOT EXCEEDING 2,500 SF SHALL BE PROVIDED UNLESS STRUCTURAL ANALYSES ARE PERFORMED OF THE CEILING BRACING SYSTEM <br />FOR THE PRESCRIBED SEISMIC FORCES THAT DEMONSTRATE CEILING SYSTEM PENETRATIONS AND CLOSURE ANGLES PROVIDE SUFFICIENT <br />CLEARANCE TO ACCOMMODATE THE ANTICIPATED LATERAL DISPLACEMENT <br />C. EXCEPT WHERE RIGID BRACES ARE USED TO LIMIT LATERAL DEFLECTIONS, SPRINKLER HEADS AND OTHER PENETRATIONS SHALL HAVE A <br />2" OVERSIZE RING, SLEEVE, OR ADAPTER ROUGH THE CEILING TILE TO ALLOW FOR FREE MOVEMENT OF AT LEAST 1" IN ALL HORIZONTAL <br />DIRECTIONS. ALTERNATIVELY, A SWING JOINT THAT CAN ACCOMMODATE 1" OF THE CEILING MOVEMENT IN ALL HORIZONTAL DIRECTIONS IS <br />PERMITTED TO BE PROVIDED AT THE TOP OF THE SPRINKLER HEAD EXTENSION <br />D. SUSPENDED CEILINGS SHALL BE SUBJECT TO THE SPECIAL INSPECTION REQUIREMENTS OF ASCE 7-10, SECTION 11A.1.3.9, ITEM 2. <br />E. AS AN ALTERNATE TO PROVIDING LARGE CLEARANCES AROUND SPRINKLER SYSTEM PENETRATIONS THROUGH CEILING SYSTEMS, THE <br />SPRINKLER SYSTEM AND CEILING SYSTEM AND CEILING GRID ARE PERMITTED TO BE DESIGNED AND TIED TOGETHER AS AN INTEGRAL UNIT. <br />SUCH A DESIGN SHALL CONSIDER THE MASS AND FLEXIBILITY OF ALL ELEMENTS INVOLVED, INCLUDING THE CEILING SYSTEM, SPRINKLER <br />SYSTEM, LIGHT FIXTURES AND MECHANICAL (HVAC) APPURTENANCES. SUCH DESIGN SHALL BE PERFORMED BY A REGISTERED DESIGN <br />PROFESSIONAL <br />GENERAL NOTES: <br />1. LATERAL FORCE MEMBERS SHALL BE SPACED A MINIMUM OF 6" FROM ALL HORIZONTAL PIPING OR DUCTWORK THAT IS NOT <br />PROVIDED WITH BRACING RESTRAINS FOR HORIZONTAL FORCES. BRACING WIRES SHALL BE ATTACHED TO THE GRID AND TO THE <br />STRUCTURE IN SUCH A MANNER THAT THEY CAN SUPPORT A DESIGN LOAD OF NOT LESS THAN 200 POUNDS OR THE ACTUAL LOAD, <br />WHICHEVER IS GREATER, WITH A SAFETY FACTOR OF 2. <br />2. STRUTS OTHER THAN THE ONES LISTED ABOVE MAY BE USED WITH AN EVALUATION REPORT BY I.C.C. OR OTHER NATIONALLY <br />ACCREDITED TESTING LABORATORY. <br />3. ALL 24" x 48" CEILING LIGHT FIXTURES & 24" x 24" HVAC AIR REGISTERS SHALL BE SUPPORTED BY A MIN. OF (2) TWO HANGERS @ <br />OPPOSITE CORNERS. CEILING SYSTEM SHALL NOT SUPPORT OTHER ITEMS. <br />4. ALL INTERIOR WALL & CEILING FINISHES SHALL BE INSTALLED IN ACCORDANCE WITH ASTM E 84 SHALL BE FLAME SPREAD CLASS <br />III MIN. <br />5. SPRINKLER HEADS AND OTHER PENETRATION CLEARANCE MIN. 2" DIA. OPENING OR A SWING JOINT <br />6. ARMSTRONG ACOUSTICAL CEILING SUSPENSION SHALL BE INSTALLED IN ACCORDANCE TO ICC ESR-1308 <br />7. BRACING WIRES SECURED TO MAIN RUNNERS WITHIN 2" OF THE CROSS RUNNER INTERSECTION AND SPLAYED 90* FROM EACH <br />0THER AT AN ANGLE NOT EXCEEDING 45* FROM THE PLANE OF THE CEILING. <br />8. FOR ROOMS WITH SPAN IN EITHER DIRECTION LESS THAN 25', MAIN RUNNERS AND CROSS RUNNERS MAY BE ATTACHED TO THE <br />PERIMETER OF TWO ADJACENT WALLS WITH 3/8" CLEARANCE BETWEEN THE RUNNERS AND THE OTHER TWO WALLS. WHERE SPAN <br />OF THE CEILING SYSTEM BETWEEN PERIMETER WALLS EXEED 25' IN BOTH DIRECTIONS, A MINIMUM WALL ANGLE SIZE OF AT LEAST 2" <br />HORIZONTAL LEG SHALL BE USED AT PERIMETER WALLS AND INTERIOR FULL HEIGHT PARTITION. THE FIRST TILE SHALL BE 3/4 "CLEAR <br />FROM WALL SURFACE. <br />9. WHEN THE DISTANCE BETWEEN THE STRUCTURAL DECK AND THE CEILING EXCEEDS 4', THE SPACING OF THE VERTICAL HANGERS <br />SHALLNOTEXCEED 2' 0.C.ALONG THE ENTIRE LENGTH OF THE MEANS OF EGRESS SERVICING AN OCCUPANT LOAD OF 30 OR MORE,AND <br />AT LOBBIES ACCESSORY TO GROUP A OCCUPANCIES. <br />1. VERTICAL STRUT: A STRUT FASTENED TO <br />THE MAIN RUNNER SHALL BE EXTENDED TO <br />AND FASTENED TO THE STRUCTURAL <br />MEMBERS SUPPORTING THE ROOF OR FLOOR <br />ABOVE. THE STRUT SHALL BE ADEQUATE TO <br />RESIST THE VERTICAL COMPONENT INDUCED <br />BY THE BRACING WIRE. <br />2. HORIZONTAL RESTRAINT POINTS SHALL BE <br />PLACED 12 FEET ON CENTER IN BOTH <br />DIRECTIONS WITH THE FIRST POINT WITHIN 6 <br />FEET FROM EACH WALL. <br />VERTICAL STRUT (TYP) STD INSTALLATION PER <br />ASCE SECTION 13.5.6.2.2. <br />2" (MAX) FROM BRACING WIRE TO CROSS <br />RUNNERS. <br />METAL STUD COMPRESSION STRUT PER <br />SCHEDULE <br />1/4" DIA. MACHINE BOLT <br />ACOUSTICAL CEILING TILES <br />CEILING CLIP ASSEMBLY - HILTI CC-CLIP <br />FASTENED W/.177 DIA. POWER DRIVEN <br />FASTENER DX-KWIK, <br />LARR-25651-ICC ESR-2184, OR APPROVED <br />EQUAL <br />1-1/2"-4 TIGHT TURNS <br />12 GA. VERTICAL WIRE <br />SPLAYED BRACE WIRE <br />COMPRESSION STRUT ATTACHMENT DETAILS <br />TYPICAL 12 GA. VERTICAL HANGER WIRE @ <br />4'-0" O.C. EACH WAY W/ MIN. 4 TIGHT TURNS <br />IN 1-1/2" BOTH ENDS OF WIRE. <br />12GA. BRACING WIRE W/ MIN. 4 TIGHT TURNS IN <br />1-1/2" BOTH ENDS OF WIRE TYP. 90 APART @ 12'-0" <br />O.C. EA. WAY. <br />STARTING 6' FROM WALLS <br />CEILING GRID MAIN RUNNER <br />12 GA. SPLAYED SEISMIC BRACING WIRE. <br />4 TIGHT TURNS <br />VERTICAL HANGER WIRE <br />ATTACHED TO STRUCTURE WITH 3/8" DIA. <br />HILTI KB-TZ (ESR-1917) EMBEDDED 2" MIN. @ <br />24" O.C. <br />CEILING CLIP ASSEMBLY - HILTI CC-CLIP <br />FASTENED W/.177 DIA. POWER DRIVEN <br />FASTENER DX-KWIK, <br />LARR-25651-ICC ESR-2184, OR APPROVED <br />EQUAL <br />EMT COMPRESSION STRUT PER SCHEDULE. <br />ENDS FLATTENED AND ATTACHED AS NOTED <br />COMPRESSION STRUT SCHEDULECOMPRESSION STRUT SCHEDULE <br />HEIGHT <br />3 / 4" EMT <br />METAL STUD OPTION <br />UP TO 5'-0"250TI25-33 (20 GA) <br />400S137-33 (20 GA) <br />-400S200-33 (20 GA) <br />UP TO 6'-0" <br />UP TO 7'-0" <br />UP TO 10'-0" <br />1" EMT <br />1 - 1 / 4" EMT <br />EMT OPTION <br />250TI25-33 (20 GA) <br />> 10'-0" : Provide structural design calculations. <br />COMPRESSION STRUTS 12' O.C, BOTH DIRECTIONS, <br />STEEL SECTION WITH L/R RATION OF 200 MAX. <br />ATTACH TO MAIN RUNNERS WITH 1/4" MACHINE <br />BOLTS AND TO STRUCTURE WITH 3/8" DIA. HILTI <br />KB-TZ (ESR-1917) EMBEDDED 2" MIN. @ 24" O.C. <br />COMPRESSION STRUT SHALL NOT REPLACE HANGER <br />WIRE. MAY BE STEEL STUD, BLACK IRON, EMT OR <br />WOOD STUD (IN COMBUSTIBLE CONSTRUCTION <br />TYPES ONLY) OR OTHER APPROVED EQUAL. <br />- <br />MAIN RUNNER <br />CROSS RUNNER <br />UNATTACHED WALLATTACHED WALL <br />- <br />3/8" AT TWO <br />ADJACENT WALLS OR <br />3/4" AT ALL FOUR <br />WALLS: SEE NOTE #8 <br />-3/8" MIN CLR CROSS <br />OR MAIN RUNNER <br />7/8" <br />8" MAX <br />7/8" <br />B <br />B <br />B SECTION VIEW <br />A ISOMETRIC VIEW <br />T-BAR CEILING (SEE REFLECTED CLG. PLAN) IF <br />APPLICABLE <br />SCREW TIGHTENED THROUGH MAIN <br />RUNNER/CROSS TEE BULB OR WEB <br />·CEILING TILE AND GRID <br /> ARMSTRONG ICC-ESR-1308 <br /> L.A. RR. #25032 <br />·SEISMIC WALL CLIP <br /> BERC2 OR EQUAL <br /> ICC - ESR 1308, LARR #25032 <br />ARMSTRONG 7/8" ANGLE MOLDING <br />ARMSTRONG BERC2 SEISMIC WALL <br />ATTACHMENT CLIP. <br />3 FULL TWIST MIN. <br />ARMSTRONG 7/8" ANGLE <br />MOLDING <br />ARMSTRONG BERC2 SEISMIC <br />WALL ATTACHMENT CLIP <br />HANGER WIRE <br />MAIN RUNNER/CROSS TEE <br />SCREW TIGHTENED THROUGH <br />MAIN RUNNER/CROSS TEE BULB <br />OR WEB <br />3/4" <br />7/8" <br />7/8" <br />B <br />B <br />B SECTION VIEW <br />A ISOMETRIC VIEW <br />8" MAX <br />3/4" <br />T-BAR CEILING (SEE REFLECTED CLG. PLAN) IF <br />APPLICABLE <br />·CEILING TILE AND GRID <br /> ARMSTRONG ICC-ESR-1308 <br /> L.A. RR. #25032 <br />·SEISMIC WALL CLIP <br /> BERC2 OR EQUAL <br /> ICC - ESR 1308, LARR #25032 <br />ARMSTRONG 7/8" ANGLE MOLDING <br />ARMSTRONG BERC2 SEISMIC WALL <br />ATTACHMENT CLIP. <br />LOOSE SLIP SCREW <br />ARMSTRONG 7/8" ANGLE <br />MOLDING <br />ARMSTRONG BERC2 SEISMIC <br />WALL ATTACHMENT CLIP <br />HANGER WIRE <br />MAIN RUNNER/CROSS TEE <br />LOOSE SLIP SCREW <br />3 FULL TWIST MIN. <br />#12 AWG STEEL WIRE CONNECTOR USED FOR BOTH GRID <br />SUPPORT AND FIXTURE SUPPORT. ATTACH TO PERMANENT <br />STRUCTURE. TYP. 6 PLACES. <br />2'X4' FIXTURE SHOWN. DETAIL IS TYPICAL FOR 2'X2' , 1'X4' AND MOST <br />OTHER RECESSED TROFFER FIXTURES. <br />TYPICAL OF A VARIETY OF TROFFER FIXTURE SUPPORT WIRE <br />CONNECTION TABS. <br />PROVIDE MIN. 3 COMPLETE TURNS OF WIRE NO MORE THAN 15" <br />LONG (TYP.) <br />#10 TEK SCREWS LOCATED AT OPPOSITE CORNERS OF RUNNERS THRU <br />INTEGRAL FIXTURE SUPPORT TABS - ONE SCREW SHOWN FOR CLARITY. <br />USE OF UL - LISTED ACCESSORY <br />FIXTURE SUPPORT TABS PROVIDED BY FIXTURE MANUFACTURER MAY BE <br />USED IF ACCEPTABLE WITH THE LOCAL CODES. SCREWS SHOULD NOT <br />EXTEND INTO THE BODY OF THE FIXTURE <br />AS THIS MAY DISTORT FIXTURE BODY CREATING LIGHT LEAKAGE. <br />1" <br />MIN. <br />FIELD CUT MAIN TEE <br />CROSS TEE <br />TEE-FACE SLEEVE <br />ONE SIDE OF SPLICE CAP CRIMPED TO ALLOW <br />MOVEMENT ONLY ON OPPOSITE END <br />4-WAY SEISMIC <br />EXPANSION JOINT CLIP <br />FASTENER MAIN TEE <br />HANGER WIRE <br />NEAR TEE END <br />45°REFER TO RCPREFER TO RCPLINE OF CEILING - SEE REFLECTED CEILING <br />PLAN FOR TYPE AND HEIGHT. <br />ATTACH KICKER TO TOP TRACK BOX <br />HEADER WITH #10 SHEET METAL SCREWS <br />5/8" GYPSUM BOARD <br />GYPSUM BOARD ASSEMBLIES <br />GYPSUM ASSOCIATION OR EQUAL <br />AS PER I.C.C. # ESR - 1338. <br />(1) #8 SHEET METAL SCREW <br />2-1/2" x 20 GAUGE METAL STUD <br />ATTACH TO STRUCTURE ABOVE WITH 3/8" DIA. <br />HILTI KB-TZ EMBEDDED 2" MIN. @ 24" O.C. <br />W/ FLOOR PLAN <br />VERIFY DIMENSION <br />EXISTING STRUCTURE <br />DATE: <br />DRAWN: <br />REVIEWED: <br />PROJECT NO: <br />SCALE: <br />OWNERSHIP AND USE OF DOCUMENTS ALL DRAWINGS, SPECIFICATIONS AND COPIES THEREOF <br />FURNISHED BY SAA INTERIORS ARE AND SHALL REMAIN IT'S PROPERTY. THEY ARE TO BE USED <br />ONLY WITH RESPECT TO THIS PROJECT. FEDERAL LAW PROHIBITS THE REPRODUCTION, <br />DISPLAY, SALE, OR OTHER DISPOSITION OF THIS DOCUMENT WITHOUT THE EXPRESS WRITTEN <br />CONSENT OF SHLEMMER ALGAZE ASSOCIATES. <br />COPYRIGHT © 2015 SHLEMMER ALGAZE ASSOCIATES ALL RIGHTS RESERVED <br />SHEET TITLE: <br />SHEET NO: <br />SEAL AND STAMP: <br />CONSULTANTS: <br />PROJECT: <br />CULVER CITY - IRVINE - LOS ANGELES - SAN FRANCISCO - <br />NEW JERSEY - NEW YORK <br />6083 Bristol Parkway <br />Culver City, CA 90230 <br />18600 MacArthur Blvd., Suite 100 <br />Irvine, CA 92612 <br />515 South Flower Street, Suite 1200 <br />Los Angeles, CA 90071 <br />T 310.553.3252 <br />T 949.724.8958 <br />T 213.929.1400 <br />DRAWINGS ISSUE <br />485C US Route 1 South, Suite 105 <br />Iselin, NJ 08830 <br />T 848.200.1200 <br />711 3rd Ave., 6th Floor <br />New York, NY 10017 <br />T 917.512.6688 <br />www.saaia.com <br />T 415.390.6793 <br />NOT FOR CONSTRUCTION <br />IF DRAWINGS AND MATERIALS DEVELOPED AND PROVIDED BY SAA INTERIORS + ARCHITECTURE <br />AT THE TIME OF AND RELATING TO COVID-19 CONTAIN RECOMMENDATIONS FROM THE <br />CENTER FOR DISEASE CONTROL AND PREVENTION (CDC) AND THE WORLD HEALTH <br />ORGANIZATION (WHO), SUCH RECOMMENDATIONS ARE ONLY VALID AS OF THE DATE THE <br />DRAWINGS AND MATERIALS ARE PRODUCED. THE CDC AND/OR WHO MAY UPDATE OR MODIFY <br />THEIR RECOMMENDATIONS AT ANY TIME PER THEIR DISCRETION. IN USING <br />RECOMMENDATIONS FROM THESE DRAWINGS AND MATERIALS, THE RECIPIENT <br />ACKNOWLEDGES THAT IT WAS BASED ON THEIR OWN DECISION AND TAKE FULL RESPONSIBILITY <br />AND LIABILITY. THE INTENDED RECIPIENT INDEMNIFIES AND DEFENDS SAA FOR ANY USE OF <br />THESE DRAWINGS AND MATERIALS BY OTHERS. SAA’S SERVICES ARE INTENDED TO ONLY BE OF <br />ASSISTANCE AND GUIDANCE FOR OUR CLIENT’S STRATEGIES AND DO NOT CONSTITUTE AS <br />REQUIREMENTS OR ANY FORM OF HEALTH, ILLNESS OR DISEASE ADVICE. SAA MAKES NO <br />REPRESENTATIONS OR WARRANTIES REGARDING THE ACCURACY OR COMPLETENESS OF THE <br />DRAWINGS AND MATERIALS. ANY RECOMMENDATIONS OR USE OF ANY CDC OR WHO <br />INFORMATION DOES NOT CONSTITUTE ENDORSEMENT BY THE U.S. GOVERNMENT, <br />DEPARTMENT OF HEALTH AND HUMAN SERVICES OR THE CDC AND WHO NOR ITS AFFILIATES. <br />575 Market Street, #502 <br />San Francisco, CA 94105 <br />As indicated <br />A-30.2 <br />04/10/24 <br />AW <br />JN/MP <br />634495 <br />CEILING DETAILS <br />X ENGINEERING <br />6 E HUTTON CENTRE <br />DRIVE <br />SANTA ANA, CA 92707 <br />SUITE 650 EXPANSION <br />SCALE: <br />1 1/2" = 1'-0"SUSPENDED CEILING GRID DETAIL 4 <br />SCALE: <br />3" = 1'-0"ATTACHED - GRID TO WALL DETAIL 6SCALE: <br />3" = 1'-0"UNATTACHED - GRID TO WALL DETAIL 10 <br />SCALE: <br />1 1/2" = 1'-0"LIGHT FIXTURE SEISMIC SUPPORT3 8 <br />SCALE: <br />1 1/2" = 1'-0"EXPANSION JOINT 13 <br />SCALE: <br />1 1/2" = 1'-0"FRAMED OPENING / SOFFIT DETAIL 7 <br />DATE DESCRIPTION DELTA <br />04/16/24 ISSUE FOR ENGINEERING <br />05/08/24 TENANT REVISION <br />05/20/24 ISSUE FOR PLAN CHECK <br />NELSON <br />ALGAZE <br />No. C-21090 <br />REN. 03/31/2025L,CEN S E ' ARC+,7 <br />E <br />C7S7A <br />7 <br />E O) CA L ,)O RN,A6 E Hutton Center Dr <br />Unit# 625 & 6509/23/2024